The Megger LRCD210 Combined Loop and RCD Tester has been designed as a combined non tripping loop and RCD tester.
With simple, flexible test tools for electrical contractors testing energised circuits, the Megger LRCD210 is an ideal combined testing machine.
The combined tester provides three phase safe non trip loop testing and 1/2I, I and 51 RCD tests for standard selective and DC RCDs.
This 17th edition tester will not trip RCDs rated at 3mA or greater during loop testing, this includes digital RCDs.
Including a tough rubber tester case with a built in front cover, the machine is a highly robust piece of equipment.
The Megger LRCD210 Loop and RCD Tester has easy to use functions and layout, and is weatherproof to IP54.
The LNE connection indicator LEDs show connection status and reverse polarity supplies.
Voltage measurement: 0 V - 500 V
Accuracy: ±2% ±2 digits
Range: 25Hz to 450Hz
Accuracy: 25.0Hz to 199.9Hz ±0.1Hz, 200Hz to 450Hz ±1Hz
Supply: LRCD210 200V - 280 V 45Hz to 65Hz,
Nominal test current: 15 mA
Loop accuracy: 0.01 ½ - 9.99 ½ (±5% ±0.03 ½), 10.0 ½ - 99.9 ½ (±5% ±0.5 ½), 100 ½ - 999 ½ (±5% ±5 ½), 1.00 k½ - 2.00 k½ (±5% ±30 ½)
Prospective fault current = Nominal supply voltage/Loop resistance.
Accuracy is derived from loop test:
RCD test ranges (to EN61557-6): 10mA, 30mA,100mA, 300mA, 500mA
Supply voltage: 200 V - 280 V 45Hz to 65Hz
No trip test: (1/2I) –8% to –2%
Trip test: (I, 5I) +2% to +8%
Trip time: ±1% ±1ms
Displayed range: 0 V to 50 V
Error: +5%/+15% ±0.5 V
Operating range: -5°C to +40°C
Operating humidity: 93% R.H. at +40°C max.
Storage range: -25°C to +70°C
Maximum altitude: 2000m
Environmental protection: IP54
Battery: 8 x 1,5 V cells IEC LR6 type (AA alkaline).
Rechargeable: 8 x 1.2V NiCd or NiMH cells.
Battery life: 2000 consecutive tests
Weight: 980gms
Dimensions: All units 203 x 148 x 78 mm
In accordance with: IEC 61326-1 and IEC 61010 (Cat III 300V phase to earth)