Price Match Request
Megger / Programma SVERKER 750 Relay Test Set (230V)

The Megger SVERKER750 is the engineer's toolbox for secondary testing of protective relay equipment.

The SVERKER750 can be used to test a wide variety of equipment, including overcurrent relays, inverse time overcurrent relays, undercurrent relays, ground fault relays, directional overcurrent relays, undervoltage relays, power factor relays, time-delayed relays and much, much more.

Whether you're new to the SVERKER family or have used other models such as the SVERKER650 in the past, the SVERKER750's intuitive interface with local layout and built-in digital screen make the system as simple to use as possible. Once configured, the SVERKER750 can be used to measure and display time, voltage, current, Z, R, X, S, P, Q, phase angle and cos φ.

You can also use the Megger SVERKER750 for a wide variety of other applications including plotting excitation curves, current/voltage transformer ratio tests, burden measurements, impedance measurements, efficiency tests, polarity tests and more.

For added convenience, select SVERKER750 models even come with a useful carrying handle for easy porting from test to test.

Megger SVERKER750 Feature/Benefit Breakdown

The following table outlines the functionality of the Megger SVERKER750.

1 - Set of Resistors Made for fine adjustments and regulation of current and voltage
2 - Start and Stop Conditions The timer's start and stop inputs respond to changes, voltage or contact closing/openings. The timer's start input is also used when testing auto-reclosing relays to synchronise two or more SVERKER units and to start generation with an external signal
3 - Display Shows time, current, voltage and other parameters. Also used to make settings (access setting mode by pressing MODE button)
4 - Freeze Function (HOLD) Makes it possible to measure voltage and current as short as a quart of a mains voltage period by saving a reading on the display. Voltage and current readings are frozen when the timer stops. If it doesn't stop, the reading present when the current was interrupted is frozen on the display.
5 - Make/Break Contact Changes state automatically when a test is started. Can be used (for example) to synchronise two or more SVERKER units, other external equipment or to switch the voltage applied to the protective relay equipment back and forth between faulty and non-faulty.
6 - Ammeter and Voltmeter Current and voltage are measured by the built-in ammeter/voltmeter. Resistance, impedance, phase angle, power and power factor can also be measured. Reading appear on the display. These instruments can also be used to take measurements in external circuits. The voltmeter can also be used as 2nd ammeter (when testing differential relays, for example, using CSU20A). Current and voltage can be displayed either as amperes or volts or as percantages of a given voltage or current (the present settings of the protective relay equipment, for example).
7 - Current Source Provides 0-250A AC, 0-250V AC or 0-300V D, depending on the ouput being used. Setting are made using the main knob. The readings of current, voltage and other entities appear on the display. The start switch is used to turn the current source on and off. When time is being measured, this is done in synchronisation with the timer.
8 - Auxiliary Voltage Source Provides 20-220V DC in two ranges. Equipped with overload protection and separate from the other outputs. Used frequently to supply the object being tested.
9 - Status Indicator The timer's start and stop inputs are each equipped with indicator lamps which, when lighted, indicate a closed circuit (useful for detecting contact closings/opening) or the presence of voltage. These indicator lamps make it possible (for example) to check circuits before starting a measurement cycle.
10 - Timer Inputs The timer has separate start and stop inputs, and it can be used to measure both external cycles and sequences initiated by the SVERKER. The measured time appears on the display. Each input can be set to respond to the presence of absence of voltage (AC/DC) at a contact.
11 - Start Switch Controls the turning on and off of the current source and timer. Can be set to one of four states. ON+TIME. Starts generation and timing simultaneously. Used to test over current, voltage or other parameter relays. Generation continues a) until the protective relay equipment operates and stops the timer or b) until the maximum time expires or the start switch is released if time-limited generation has been selected.
OFF function turns of the current source, wherupon generation is interrupted. ON function turns on the current source in the generating state.
OFF+TIME function interrupts generation and starts the timer simultaneously. Used when testing current, voltage or other parameter relays. The timer is stopped when the protective relay equipment operates. When automatically reclosing is set to be tested, the SVERKER can be set to start a new generation when the timer's start input is activated by the closing command.
12 - Computer Interface (USB) Serial port for communication with PC and SVERKER Win PC software
13 - Tripping Indicator Lights when a stop condition is fulfilled to indicate operation of the protective relay equipment. If the test being conducted incorporates timing, this indicator starts to blink when relay operation occurs.
14 - Main Knob Used to set current output from the current source
15 - AC Voltage Source Since the AC voltage source is separated from other outputs, it is set independently of the current source. The AC voltage source is intended primarily for the relay protection equipment's voltage input

Megger SVERKER750 Relay Test Set Key Features

  • Portable solution for testing a wide variety of single phase relays
  • Built-in carrying handle for easy transportation
  • Rugged and reliable design for field use
  • Logical design with simple interface
  • Display can show time, voltage, current, Z, R, X, S, P, Q, phase angle and cos φ
  • Intergated voltmeter and ammeter
  • Variable voltage source
  • Serial port for communication with PC and SVERKER Win PC software (software sold separately)
  • Two SVERKER units can be synchronised to create a basic 3-phase test set
  • Suitable for voltage relays with frequency range from 15Hz up to 550Hz
  • Use to plot excitation curves
  • Suitable for burden measurements on protective relays
  • Impedance, efficiency and polarity measurement possible

What's Included?

  CD-13390 CD-12300 CD-12390
Megger SVERKER750 Relay Test Set
GA-00030 Test Lead Set
Fix Mounted Case
GD-00182 Case

Optional Accessories

  • CD-8102X: SVERKER Win PC Software + RS232/USB Cables (please specify SVERKER serial number when ordering)
  • CSU20A: 230V Current and Voltage Source
  • PSS750: Phase Selector Switch
  • AA-00100: Cable Organiser (Velcro Straps x 10)

Megger SVERKER 750/780 Technical Specifications

Specifications are valid at nominal input voltage and an ambient temperature of +25°C, (77°F). Specifications are subject to change without notice.

Current Outputs - AC
Range No-Load voltage (min) Full-Load Voltage (min) Full-Load Current (max) Load/Unload Times On (max) / Off (min)
0-10A 90V 75V 10A 2/ 15 minutes
0-40A 25V 20V 40A 1/ 15 minutes
0-100A 10V 8V 100A 1/ 15 minutes
0-100A 10V - 250A*
200A**
1 sec/ 5 minutes
* Mains voltage 230V AC
** Mains voltage 115V AC
Voltage Outputs - AC/DC
Range No-Load Voltage (min) Full-Load Voltage (min) Full-Load Current (max) Load/Unload Times On (max) / Off (min)
0-250V AC 290V AC 250V AC 3A 10 min/ 45 min
0-300V DC 320V DC 250V DC 2A 10 min / 45 min
Seperate AC Voltage Source (SVERKER 750)
Range No-Load Voltage (min) Full-Load Voltage (min) Full-Load Current (Max)
0-60V AC 70V 60V 0.25A
60 to 120V AC 130V 120V 0.25A
Both ranges are divided into voltage steps of 10V that are steplessly variable
Separate AC Voltage Source (SVERKER 780)
Range No-Load Voltage (min) Full-Load Voltage (min) Full-Load Power (max)
5-220V AC, minimim step 0.1V 240V AC 220V AC at 33W
200V AC at 46W
33W continuously.
46W 1 minute
Phase Angle 0 to 359°
Resolution
Inaccuracy ±2°
Frequency 15 to 550Hz
Resolution 1mHz
Inaccuracy ±0.1%
Auxiliary DC Output
Range Voltage Max Current
20 to 130V 20V
130V DC
300mA
375mA
130 to 220V DC 130V
220V DC
325mA
400mA
Environment
Application Field This instrument is intended for use in HV substations and industrial environments
Operating Temperature 0 to +50°C (32 to +122°F)
Storage/Transport Temperature -40 to +70°C (-40 to +158°F)
Humidity 5 to 95% RH non-condensing
CE-Marking
LVD Low voltage directive 2006/95/EC
EMC EMC directive 2004/108/EC
General Specifications
Mains Voltage 115/230V AC, 50/60Hz
Power Consumption (Max) 1380W
Protection Thermal Cutouts, automatic overload protection
Dimensions  
Instrument 250 x 270 x 220mm (13.8 x 10.6 x 8.7")
Transport Case 610 x 350 x 275mm (24.0 x 13.8 x 10.8")
Weight  
SVERKER 750 17.6kg (38.1lbs)
26.3kg (58lbs) with accessories + case
SVERKER 780 18.1kg (39.9lbs)
27.1kg (59.7lbs) with accessories + case
Other Specs  
Display LCD
Languages Bulgarian, Czech, English, French, German, Russian, Spanish, Swedish and Turkish
Ammeter
Measurement Method AC, true RMS
DC, mean value
Ranges  
Internal 0.00 to 250.0A
External 0.000 to 6.000A
Inaccuracy (Internal Range)  
0-10A AC ±(1% + 20mA)
0-40A AC ±(1% + 40mA)
0-100A AC ±(1% + 200mA)
Inaccuracy (External Range)
0-0.6A AC ±(1% + 20mA)
0-6A AC ±(1% + 20mA)
0-0.6A DC ±(0.5% + 2mA)
0-6A DC ±(0.5% + 20mA)
Resolution  
Internal Range 10mA (range <100A)
100mA (range >100A)
External Range 1mA
Voltmeter
Measurement Method AC, true RMS
Range 0.00 to 600.0V
Inaccuracy AC, ±(1% + 200mV) Max value
DC ±(0.5% + 200mV) Max value
Values are range dependant
Power Factor and Phase Angle Measurements
  Range Resolution Inaccuracy
Power Factor cos φ -0.99 (cap) to +0.99 (ind) 0.01 ±0.04
Phase Angle cos φ (°) 000 - 359° ±2°
Impedance/Power Measurements
AC Z (Ω and °), Z (Ω), R and X (Ω and Ω), P (W), S (VA), Q (VAR)
DC R (Ω), P (W)
Range Up to 999kΩ (X=unit)
Make/Break Contact  
Max Current 1A
Max Voltage 250V AC or 120V DC
Reclosing Test  
Items Measured Tripping and reclosing times
Display After test is finished a list of all times appears in the display
Break State Feedback The make/break contact can be used to feed back the breaker state
Max Number of Reclosings 49
Max Testing Time 999s