The Di-LOG ALVA MFT Pro is the flagship model in the ALVA range. Built to BS EN 61557 standards and packed with next-generation automation, it delivers advanced diagnostics, EV-ready capabilities, and data management.
A high-contrast full-colour TFT display with interactive pass/fail settings delivers instant feedback. Built-in fuse tables display maximum permitted Zs values on-screen, while intelligent 2/3 wire high-current loop detection and Automated Continuity & Earth Loop Auto Start minimises user input without compromising accuracy.
The RCD-LOC+ Xpert Loop Technology delivers high-accuracy, low-current Earth Loop measurements with adjustable test currents. RCD testing covers AC, A, B, B+, EV, F, and 6mA RDC-PD/MD types, with 1A RCD testing, and an automated EV Auto Test Sequence.
The 15mA continuity testing assesses inductive loads, while Zmax and Imax tracking capture worst-case loop impedance and fault current values. The ALVA MFT Pro also supports 3- and 4-pole Earth Resistance Testing using an optional accessory kit. It's 1,000-test internal memory permits data storage, traceability, and report integration.
Discover the full Di-Log ALVA range: the ALVA MFT Multifunction Installation Tester, and the ALVA MFT EV Multifunction Installation Tester Kit , and the ALVA MFT Pro EV Multifunction Installation Tester Kit .
Purchase a Di-LOG ALVA Series MFT from us and receive the following free gift upon registration with Di-Log:
Once received, register your product online and Di-LOG will send your FREE CombiVolt item directly to you. Ends 30 April 2026.
| Measurement Range | Resolution | Basic Accuracy | |
|---|---|---|---|
| Voltage & Frequency | |||
| AC Voltage TRMS 0V - 550V |
1V | ±2% ± 2 dgts | |
| DC Voltage 0V - 550V |
1V | ±2% ± 2 dgts | |
| Frequency 10 - 499Hz |
0.1Hz | ±0.2% ± 1 dgts | |
| Phase Rotation | |||
| 0V - 550V Measurement range BS EN 61557-7 |
Right:1-2-3 ; Left: 3-2-1 | ||
| Continuity | |||
| Low R (200mA) | 0.01Ω - 19.99Ω 20.1Ω - 99.9Ω 100Ω - 1999Ω |
±3% ± 3 dgts ±5% ± 5 dgts ±5% ± 5 dgts |
|
| Continuity (4mA) | 0.1Ω - 99.99Ω 100Ω - 1999Ω |
±5% ± 3 dgts ±5% ± 5 dgts |
|
| Insulation | |||
| 50V, 100V & 250V (50kΩ-80MΩ @ 50V | 100kΩ-199.9MΩ @ 100V & 250V) |
<0.01MΩ - 19.999MΩ 19.99MΩ - 99.99MΩ 20.0MΩ - >199.9MΩ |
±5% ± 3 dgts ±5% ± 3 dgts ±5% ± 5 dgts |
|
| 500V & 1000V (500kΩ-199.9MΩ @ 500 & 1000V) |
<0.01MΩ - 19.999MΩ 19.99MΩ - 99.99MΩ 20.0MΩ - >199.9MΩ 200MΩ - >999MΩ |
±5% ± 3 dgts ±5% ± 3 dgts ±5% ± 5 dgts ±10% |
|
| Line Impedance (L-L | L-N) | |||
| 0.20Ω - 9999Ω Measurement range BS EN 61557-3 is 0.25Ω - 1999Ω |
0.01Ω - 19.99Ω 20.0Ω - 99.9Ω 100Ω - 9999Ω |
±5% ± 5 dgts |
|
| Perspective Short Circuit Current (PSC) | |||
| 0.00A - 19.99A 20.0A - 99.9A 100A - 999A 1.00kA - 9.99kA 10.0kA - 100.0kA |
0.01A 0.1A 1A 0.01kA 0.1kA |
Calculated value taking into account the Earth Loop Accuracy of ±5% ± 5 dgts |
|
| Earth Fault Loop Impedance (Z-loop L-PE High Current) | |||
| 0.20Ω - 9999Ω Measurement range BS EN 61557-3 is 0.25Ω - 1999Ω |
0.01Ω - 19.99Ω 20.0Ω - 99.9Ω 100Ω - 9999Ω |
±5% ± 5 dgts |
|
| Perspective Earth Fault Current (PFC - High Current) | |||
| 0.00A - 19.99A 20.0A - 99.9A 100A - 999A 1.00kA - 9.99kA 10.0kA - 100.0kA |
0.01A 0.1A 1A 0.01kA 0.1kA |
Calculated value taking into account the Earth Loop Accuracy of ±5% ± 5 dgts |
|
| Earth Fault Loop Impedance (Z-Loop (Zs) Non-Trip) | |||
| 0.40Ω - 19.99Ω 20.0Ω - 9999Ω Measurement range BS EN 61557 is 0.75Ω - 1999Ω |
0.01Ω - 19.99Ω 20.0Ω - 99.9Ω 100Ω - 9999Ω |
±5% ± 10 dgts ±10% |
|
| Perspective Earth Fault Current (PFC-Non-Trip) | |||
| 0.00A - 19.99A 20.0A - 99.9A 100A - 999A 1.00kA - 9.99kA 10.0kA - 100.0kA |
0.01A 0.1A 1A 0.01kA 0.1kA |
Calculated value taking into account the Earth Loop Accuracy of ±5% ± 5 dgts |
|
| RCD Tripping Time | |||
| 0.0 - 500.0ms (Measurement range BS EN 61557-6) |
0.1ms | ±3ms |
|
| Test Current - ½ x I∆n | 1 x I∆n | 2x I∆n | 5 x I∆n | |||
| RCD Types- AC | A | B | B+ | EV | F | S (Selective - Time Delayed) | |||
| RCD Tripping Current | |||
| 0.0 - 500.0ms (Measurement range BS EN 61557-6) |
0.1ms | ±3ms |
|
| 0.2 x IΔn - 1.1 IΔn (AC type) 0.2 x IΔn - 1.5 IΔn (A type, IΔn ≧30mA ) 0.2 x IΔn - 2.2 IΔn (A type, IΔn ≧10mA ) 0.2 x IΔn - 2.2 IΔn (B type) |
0.05 x IΔn | ±0.1 x IΔn | |
| Nominal RCD Currents- 6mA | 10mA | 30mA | 100mA | 300mA | 500mA | 650mA | 1A | |||
| Contact Voltage | |||
| 3.0V - 9.9V 10.0V - 99.9V |
0.1V | -0/+10% ±10 dgts | |
| Earth Resistance RE (3-Wire & 4-Wire Method) | |||
| 1.0Ω - 9999Ω Measurement range BS EN 61557-5 is 100Ω - 1999Ω |
1.00Ω - 19.99Ω 20.0Ω - 99.9Ω 100Ω - 9999Ω |
±5% ± 5 dgts |
|
| Earth Resistance Ro (4-Wire Wenner Method) | |||
| 6.0 Ωm … 99.9 Ωm 100 Ωm ... 999 Ωm 1.00 kΩm ... 9.99 kΩm 10.0 kΩm ... 99.9 kΩm 100 kΩm ... 9999 kΩm Measurement range BS EN 61557-5 is 100Ω - 1999Ω |
0.1 Ωm 1 Ωm 0.01 kΩm 0.1 kΩm 1 kΩm 20.0Ω - 99.9Ω 100Ω - 9999Ω |
±5 % of + 5 dgts ±5 % of + 5 dgts ±10% ( Re 2kΩ…19.99kΩ) ±10% Re (2kΩ…19.99kΩ) ±20% Re (> 20 kΩ) |
|
| General Information | |||
| EN61010 Overvoltage Safety Rating |
CAT III 600V | CAT IV 300V | |
| Display | 480 x 320 TFT | LCD Screen | |
| Power supply | 6 x AA 2100mAh NiMH batteries (included) | ||
| Recharge Time | Typical 6 hours | ||
| Dimensions | 250 x 107 x 135 mm | ||
| Weight | 1300g (Excluding batteries) | ||