Pass Presents the Fluke ii910 Acoustic Imager
The Fluke ii910 Precision Acoustic Industrial Imager is a handheld, easy-to-use, ultrasonic camera that can be used to locate partial discharge in power distribution systems and high-voltage equipment, as well as, leaks in compressed air, gas, steam and vacuum systems.
The Fluke ii910 Sonic Industrial Imager is more sensitive than its predecessor the, Fluke ii900. It has a frequency range of 2kHz to 100kHz and a detection range of up to 120m. This means that it can identify leaks that are both smaller and further away; it also makes it especially well suited to locating partial discharge from a safe distance.
The Fluke ii910 Acoustic Camera is ideal for inspecting and scanning for PD:
- Insulators,
- Transformers,
- Switch gears
- High-voltage powerlines
- Arrestors
- Busbars
- High Voltage coils
- Beakers
- Capacitors
The Fluke ii910 Sonic Industrial Imager can be used to locate faults earlier allowing professionals to take corrective action sooner, thereby limiting damage, maximising uptime, and preventing injury or fatality.
Multiple minuscule microphones capture ultrasonic sound which is converted into a SoundMap™ by the Fluke ii910 Sonic Industrial Imager’s SountSight™ technology. The SoundMap is superimposed onto the visual image allowing the user to pinpoint problems quickly and simply. Moreover, the background noise is automatically filtered out of the SoundMap depending on the frequency range selected.
Images are displayed on the Fluke ii910 Acoustic Industrial Imager’s 7-inch, 1280 x 800 LCD with a simple-to-use touchscreen interface. This easy-to-use acoustic camera requires minimal training to operate and can be easily integrated into existing maintenance routines.
The Fluke ii910 Sonic Industrial Imager is ideal for manufacturers, high-voltage electricians, electrical test engineers, and grid maintenance teams.
Onboard Quantification & Reporting Tools
Like its sister product, the Fluke ii900 Acoustic Imager, the Fluke ii910 includes a LeakQ mode. It also offers a PDQ mode and MecQ mechanical scanning.
LeakQ Mode
Prioritise leak repairs based on their severity using the LeakQ mode. This function quantifies both the distance to and the size/rate of the leak. LeakQ images can be uploaded to Fluke’s reporting tool to determine the estimated cost of the leak, i.e., the expense accrued due to the rate of wasted resources.
PDQ Mode
Similarly, the PDQ mode, unique to the Fluke ii910, calculates the distance to and classifies the type of partial discharge. Images captured in this mode can also be used with Fluke’s online tool to create reports.
MecQ Mechanical Scanning
MecQ mechanical scanning allows you to pinpoint mechanical failings, such as bearings wear, from a safe distance. It can be used to narrow down the areas with potential mechanical problems. MecQ Mechanical Scanning can be used in three sub-modes:
- 30Hz
- User-selectable (2-100kHz)
- Fixed Multi-Mode (15, 20, 30, 40, 60 kHz)
Fluke ii910 Precision Acoustic Imager Key Features
- A handheld, easy-to-use ultrasonic Acoustic camera
- Locate partial discharge in power distribution systems and high-voltage equipment
- Locate leaks in compressed air, gas, steam and vacuum systems
- Frequency range: 2kHz to 100kHz
- Detection range: 120m
- Can detect leaks that are both smaller and further away
- Inspect insulators, transformers, switchgear and high-voltage powerlines from a safe distance
- Locate faults earlier
- Limit damage
- Maximise uptime
- Prevent injury or fatality
- Multiple minuscule microphones
- SoundSight™ technology: converts sound into a SoundMap which is superimposed onto the visual image
- Background noise is filtered out of the SoundMap depending on the frequency range selected
- 7-inch, 1280 x 800 LCD
- Simple-to-use touchscreen interface
- Minimal training required
- Easily integrated into existing maintenance routines
- Ideal for high-voltage electricians, electrical test engineers, grid maintenance teams and manufacturers
What’s Included?
- Fluke ii910 Precision Acoustic Industrial Imager
- AC Power Supply and Battery Pack Charger with Universal AC Adapters
- 2x Rugged Lithium-ion Battery Packs
- USB Cable
- Hard Carrying Case
- Adjustable Hand Strap and Neck Strap
Fluke ii910 Sonic Industrial Imager Technical Specifications
Specifications | ii910 | ii900 | Definitions |
Sensors | |||
Frequency band | 2 kHz to 100 kHz | 2 kHz to 52 kHz | |
Detection range | .5 m to 120 m (1.6 to 393 feet)* | 0.5 to > 70 meters (1.6 to > 230 feet)* | |
Field of view | 63°± 5° | ||
Nominal frame rate | 25 FPS | The number of Frames Per Second (FPS) indicates the number of times the image on the screen is refreshed each second |
|
Built-in Digital Camera (Visible Light) | |||
Field of view (FOV) | 63°± 5° | ||
Focus | Fixed lens | ||
Display | |||
Size | 7" LCD with backlight, sunlight readable | ||
Resolution | 1280 x 800 (1,024,000 pixels) | ||
Touchscreen | Capacitive | Extremely precise and quick responding |
|
Acoustic image | Yes, SoundMap™ image | A SoundMap™ is a visual map of noise sources using an acoustical array |
|
Image Storage | |||
Storage capacity | Internal memory with the capacity for 999 picture files and 20 video files | ||
Image format | Blended visual and SoundMap™.JPG or .PNG | ||
Video format | Blended visual and SoundMap™.MP4 | ||
Video length | Up to 5 minutes | ||
Digital export | USB-C for data transfer | ||
Acoustic Measurements | |||
Measurement range | 12.1 dB SPL to 114.6 dB SPL ±1 dB SPL 2 kHz 4.4 dB SPL to 101.2 dB SPL ±2 dB SPL 19 kHz 12.8 dB SPL to 119.2 dB SPL ±1 dB SPL 35 kHz 19.8 dB SPL to 116.1 dB SPL ±3 dB SPL 52 kHz 41.4 dB SPL to 129.0 dB SPL ±1 dB SPL 80 kHz 54.4 dB SPL to 135.5 dB SPL ±1 dB SPL 100 kHz |
15.4 dB SPL to 115.2 dB SPL ±1 dB SPL 2 kHz 5.6 dB SPL to 102.5 dB SPL ±2 dB SPL 19 kHz 28.4 dB SPL to 131.1 dB SPL ±1 dB SPL 35 kHz 41.8 dB SPL to 133.1 dB SPL ±3 dB SPL 52 kHz |
Sound pressure level (dB SPL) or acoustic pressure is the local pressure deviation from the ambient–decible and sound pressure level |
Auto max/min dB gain | Auto or manual, user selectable | ||
Frequency band selection |
User selectable through user-made presets or manual entry | ||
Software | |||
Ease of use | Intuitive user interface | ||
Trend graphs | Frequency and dB scale | ||
Spot markers | dB level reading at centre point of the image | ||
Battery | |||
Batteries (field-replaceable, rechargeable) | 2 x Rechargeable Li-ion, Fluke BP291 | ||
Battery life | 6 hours/battery (product includes spare battery) | ||
Battery charging time | 3 hours | ||
Battery charging system | External dual-bay charger, EDBC 290 | ||
General Specifications | |||
Standard palettes | 3: Grayscale, Ironbow and Blue-Red | ||
Operating temperature | -10 °C to 40 °C (14 °F to 104 °F) | -10 °C to 45 °C (14 °F to 113 °F) | |
Storage temperature | -20 °C to 70 °C ( -4 °F to 158 °F) without batteries installed | ||
Relative humidity | 10 % to 95 % non-condensing | ||
Size (H x W x L) | 186 mm x 322 mm x 68 mm (7.3 inches x 12.7 inches x 2.7 inches) | ||
Weight (battery included) |
1.7 kg (3.75 pounds) | ||
Ingress Protection (IP) | IP40 | Protection against particles 1 mm or greater and dripping water |
|
Warranty | 2 year | ||
Self-diagnostic notification |
Array-health test to identify when microphone array needs attention | ||
Supported languages | Dutch, English, Finish, French, German, Italian, Japanese, Korean, Polish, Portuguese, Russian, Simplified Chinese, Spanish, Swedish, Traditional Chinese | ||
RoHS compliant | Yes | ||
Safety | |||
General Safety | IEC 61010-1 | ||
Electromagnetic Compatibility (EMC) International |
IEC 61326-1: Portable Electromagnetic Environment IEC 61326-2-2 CISPR 11: Group 1, Class A |
||
Korea (KCC) | Class A Equipment (Industrial Broadcasting and Communication) | ||
USA (FCC | 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103 | ||
Note | *Depending on ambient conditions |
Reviews
SKU | FLK-II910 |
---|---|
Manufacturer Part Code | 5233904 |
Country of Origin | Romania |