The Sauermann Si-CA 230 Flue Gas Analyser can be used to monitor the emissions of boilers, engines, and other combustion appliances. It supports a combination of up to six gas sensors, enabling potential measurement of:
Sauermann Si-Ca 230 Flue Gas Analyser Kit Comparison
Sensors | O2 | CO | NO | NO Low Range | NO2 | NO2 Low Range | SO2 | SO2 Low Range | CxHy | H2S | |
---|---|---|---|---|---|---|---|---|---|---|---|
KIT 2 | 2 | ✓ | ✓ | - | - | - | - | - | - | - | - |
KIT 3N | 3 | ✓ | ✓ | ✓ | - | - | - | - | - | - | - |
KIT 3NL | 3 | ✓ | ✓ | - | ✓ | - | - | - | - | - | - |
KIT 4ND | 4 | ✓ | ✓ | ✓ | - | ✓ | - | - | - | - | - |
KIT 4NS | 4 | ✓ | ✓ | ✓ | - | - | - | ✓ | - | - | - |
KIT 4NC | 4 | ✓ | ✓ | ✓ | - | - | - | - | - | ✓ | - |
KIT 4NLDL | 4 | ✓ | ✓ | - | ✓ | - | ✓ | - | - | - | - |
KIT 4NLSL | 4 | ✓ | ✓ | - | ✓ | - | - | - | ✓ | - | - |
KIT 5NDS | 5 | ✓ | ✓ | ✓ | - | ✓ | - | ✓ | - | - | - |
KIT 5NDC | 5 | ✓ | ✓ | ✓ | - | ✓ | - | - | - | ✓ | - |
KIT 5NSC | 5 | ✓ | ✓ | ✓ | - | - | - | ✓ | - | ✓ | - |
KIT 5NSH | 5 | ✓ | ✓ | ✓ | - | - | - | ✓ | - | - | ✓ |
KIT 5NLDLSL | 5 | ✓ | ✓ | - | ✓ | - | ✓ | - | ✓ | - | - |
KIT 6NDSC | 6 | ✓ | ✓ | ✓ | - | ✓ | - | ✓ | - | ✓ | - |
KIT 6NDSH | 6 | ✓ | ✓ | ✓ | - | ✓ | - | ✓ | - | - | ✓ |
KIT 6NLDLSLH | 6 | ✓ | ✓ | - | ✓ | - | ✓ | - | ✓ | - | ✓ |
Sauermann Si-Ca 230 Flue Gas Analyser Overview
The Sauermann Si-CA230 Flue Gas Combustion Analyser is also capable of calculating total NOx and Low NOx and supports other useful features such as:
- CO dilution auto-range with measurements to 50 000ppm
- CO and CO2 monitoring in ambient air
- Emissions adjustment for reference O2
- Draft and differential pressure measurements
- Stack gas velocity measurements with Pitot tube
All sensors are pre-calibrated and field-replaceable. Moreover, the Sauermann Si-CA230 Flue Gas Analyser will predict the remaining sensor life and issue calibration reminders, ensuring that your downtime is kept to a minimum.
Additionally, to protect the longevity of sensors, the Sauermann Si-CA230 Flue Gas Analyser includes a one-touch pump with On/Off purge, as well as an automatic pump cut-off for high CO levels.
Readings are indicated on the large, colour touchscreen graphical data display. The Sauermann Si-CA230 Flue Gas Analyser delivers data management with automatic measurement logging and report creation. You can also customise the Sauermann Si-CA230 Combustion Flue Gas Analyser’s display to show the gas analysis you require.
Additionally, measurements may be sent wirelessly to a smartphone/tablet with the Sauerman Kimo App installed or to a PC via a Wi-Fi or USB interface. The Sauermann Si-CA230 Flue Gas Analyser also supports use with a wireless printer.
Finally, the Sauermann Si-CA230 Flue Gas Analyser is ergonomic, lightweight, and resilient. It features a protective rubber holster and can be used with hose extensions to access difficult-to-reach areas.
The Sauermann Si-CA230 Combustion Flue Gas Analyser is a versatile, durable, comprehensive combustion gas tester.
Sauermann Si-CA230 Flue Gas Analyser Key Features
- Combustion analyser for monitoring the emissions of boilers, engines, and other combustion appliances
- Supports a combination of up to six gas sensors: O2,CO, NO, low-range NO, NO2, low-range NO2, SO2, low-range SO2, H2S, and CxHy
- Calculate total NOx and low NOx
- CO dilution auto-range with measurements to 50 000ppm
- CO and CO2 monitoring in ambient air
- Emissions adjustment for reference O2
- Draft and differential pressure measurements
- Stack gas velocity measurements with Pitot tube
- Sensors are pre-calibrated and field-replaceable
- Predicts the remaining sensor life
- Issues calibration reminders
- One-touch pump with On/Off purge
- Auto pump cut off for high CO levels
- Large, colour touchscreen
- Graphical data display
- Data management with automatic measurement logging and report creation
- Customisable gas analysis display
- Send data wirelessly to a smartphone/tablet
- Upload data to a PC via a Wi-Fi or USB interface
- Supports use with a wireless printer
- Ergonomic, lightweight, and resilient
- Protective rubber holster
- Can be used with hose extensions to take readings in difficult-to-access areas
- A versatile, durable, comprehensive combustion gas tester
What’s Included?
- Sauermann Si-CA230 Flue Gas Combustion Analyser with Your Choice of Gas Sensors
- Protective Rubber Holster
- 300mm Flue Gas Probe with 3m Dual Hose
- Water Trap with Filter
- AC Power Supply & Charger
- USB cable
- Carrying Case
- Quick Start Guide
Sauermann Si-CA 230 Flue Gas Combustion Analyser Specification
Parameter | Sensor | Measuring range | Resolution | Accuracy(1) | Response Time |
O2 | Electrochemical | 0 to 25% | 0.01% | ±0.2% vol | T90 < 30 s |
CO (H2 comp.) | Electrochemical | 0 to 10,000 ppm | 1 ppm | ±8 ppm < 160 ppm | T90 < 40 s |
±5% rdg up to 2000 ppm | |||||
±10% rdg > 2000 ppm | |||||
CO (with dilution) | Electrochemical | 100 to 50,000 ppm | 1 ppm | ±10% rdg | T90 < 40 s |
CO2 | Calculated | 0 to 99.9% | 0.1% | - | - |
NO | Electrochemical | 0 to 5000 ppm | 1 ppm | ±5 ppm < 100 ppm | T90 < 40 s |
±5% rdg > 100 ppm | |||||
Low NO | Electrochemical | 0 to 300 ppm | 0.1 ppm | ±1.5 ppm < 30 ppm ±5 % rdg > 30 ppm |
T90 < 40 s |
NO2 | Electrochemical | 0 to 1000 ppm | 1 ppm | ±5 ppm < 100 ppm ±5 % rdg > 100 ppm |
T60 < 60 s |
Low NO2 | Electrochemical | 0 to 100 ppm | 0.1 ppm | ±1.5 ppm < 30 ppm ±5% rdg > 30 ppm |
T60 < 60 s |
NOx | Calculated | 0 to 7500 ppm | 1 ppm | - | - |
Low NOx | Calculated | 0 to 450 ppm | 0.1 ppm | - | - |
SO2 | Electrochemical | 0 to 5000 ppm | 1 ppm | ±5 ppm < 100 ppm ±5% rdg > 100 ppm |
T60 < 30 s |
Low SO2 | Electrochemical | 0 to 100 ppm | 0.1 ppm | ±1.5 ppm < 30 ppm ±5% rdg > 30 ppm |
T60 < 30 s |
CxHy (HC) | Pellistor | 0 to 5% | 0.01% | ± 5% full scale | T90 < 40 s |
H2S | Electrochemical | 0 to 500 ppm | 0.1 ppm | ±5 ppm < 100 ppm ±5% rdg > 100 ppm |
T60 < 35 s |
Flue temperature | TcK | 20 to +1250 °C -4 to +2282 °F |
0.1 °C 0.1 °F |
±2 °C or ±0.5% rdg(2) ±3.6 °F or ±0.5% rdg(2) |
- |
Air temperature | NTC or TcK | -20 to +120 °C -4 to +248 °F |
0.1 °C 0.1 °F |
±2 °C ±3.6 °F |
- |
Pt100 | -40 to 250 °C -40 to 482 °F |
0.1 °C 0.1 °F |
±(0.3% rdg ±0.25) °C -40°F to 32 °F: ±(-0.3% rdg +0.6) °F 32°F to 482 °F: ±(0.3% rdg +0.4) °F |
- | |
Differential temperature | Calculated | 0 to 1250 °C 0 to 2282 °F |
0.1 °C 0.1 °F |
- | - |
Pressure/Draft | Semiconductor | -200 to +200 mbar -80 to +80 inH2O |
0.01 mbar 0.001 inH2O |
±1% rdg ±0.03 mbar ±1% rdg ±0.012 inH2O |
- |
High accuracy draft | Semiconductor | 500 Pa | 0.1 Pa | ±0.5 Pa < 10 Pa ±3 Pa up to 150 Pa ±1% rdg ±1.5 Pa > 150 Pa |
- |
Excess air | Calculated | 0 to 999% | 1% | - | - |
Efficiency | Calculated | 0 to 100% (Gross/ HHV(3) |
0.1% | - | - |
Efficiency (condensation) | Calculated | 0 to 125% (Net/ LHV(4)) |
0.1% | - | - |
Stack Gas velocity | Calculated | 0 to 99 m/s 0 to 19,500 fpm |
0.1 m/s 1 fpm |
- | - |
Dimensions | 28 x 11.2 x 5.5 cm (11 x 4.3 x 2’’) | ||||
Weight | 825 g (30 oz) | ||||
Display | Color Touch Screen with Graphing; Size: 480 x 272 pixels | ||||
Keypad | 1 On-Off key | ||||
Material | ABS-PC | ||||
Protection | IP42 | ||||
Connection | - Wireless: class 2 range, range frequency from 2402 MHz to 2480 MHz with a transmit power of 1 dBm. Range up to 15 m (50 ft), depending on smartphone radio strength. Minimum required versions: Android 8.0, iOS 12.4, BLE 4.0 Low Energy - USB |
||||
Power supply | Rechargeable battery, USB power supply Li-Ion 5100 mA/h 3.6 V battery / Power supply voltage of the mains unit: 100-240 Vac, 50-60 Hz Mains unit: 5 Vdc/2A |
||||
Battery | Battery life > 8 h; Charging time: Fully charge: < 6.5 h; 50%: < 2.5 h | ||||
Memory | Internal memory up to 2000 tests | ||||
Environmental conditions of use |
Temperature: from -5 to 45 °C (23 to 113 °F), Hygrometry: in non-condensing conditions (< 85% RH) Maximum altitude: 2000 m (6561’) |
||||
Storage temperature | From -20 to 50 °C (-4 to 122 °F) | ||||
Languages | English, French, German, Spanish, Italian, Portuguese, Chinese | ||||
European Union Directives | 2014/53/EU (RED); 2015/863 EU (RoHS 3) | ||||
Regulations | EN 50379-1 and EN 50379-2; UNI 7129; UNI 11137; UNI 10389; UNI 10845; UL & cUL Certification; BS 7967:2015; BS EN 50543:2011; UNE 60670-10; ES.02173.ES; TÜV SÜD Certification |
SKU | K-SICA230-KITS |
---|