An essential tool for HVAC and IAQ professionals, the Fluke 985 can be used to easily determine particle concentration and is suited for measuring filter efficiency, monitoring industrial cleanrooms and locating particle sources.
Featuring internal 10000 record memory, the Fluke 985 can store a huge amount of measurement data captured using its six channels. This information can be viewd as standard measurements, or alternatively can be viewed in a tabular or trend graph. By using a USB memory stick or cable this data can then be sent to PC and interacted with using a standard Excel software package.
The 985 can be fully configured to the user's specifications. With just a few button presses, makes adjustments to sample methods and set your own alarm thresholds for raw count, per cubic feet, cubic meter or in litres.
This products meets ISO 21501, JIS B921 and CE standards.
Fluke 985 Airbone Particle Counter Key Features
- Six channel measurements
- Particle size range from 0.3 to 10μm
- Ultra lightweight, ergonomic design for ease of use in difficult applications
- Long ten hour battery life
- Large-size 3.5" QVGC colour display with integral backlight, icons and large font options
- 10000 record internal memory
- View data as a tabular or trend graph
- Conifgurable display - set sample methods and alarm settings for raw count, per cubic feet, cubic metres or litres
- Data export to PC using a USB memory stick or USB cable
- Ethernet-enabled
- Set an administrator password to prevent unauthorised use
What's Included?
- Fluke 985 Airborne Particle Counter
- USB/Ethernet Charging Cradle
- Ethernet Cable
- USB Cable
- 12V DC Power Supply
- Zero Count Inlet Filter
- Filter Adapter
- Sample Inlet Protective Cap
- Hard Carrying Case
- Getting Started Manual
- User Manual on CD
Fluke 985 Technical Specifications
Six Size Channels | 0.3μm, 0.5μm, 1.0μm, 2.0μm, 5.0μm, 10.0μm |
Flow Rate | 0.1cfm (2.83L/min) |
Light Source | 775nm to 795nm, 90mW class 3B laser |
Count Modes | Raw counts, #/m³, #/ft³, #litre in cumulative or differential mode |
Counting Efficiency | 50% @ 0.3μm; 100% for particles > 0.45μm (per ISO 21501) |
Zero Count | 1 count/5 minute (JIS B9921) |
Concentration Limits | 10% at 4,000,000 particles per ft³ (per ISO 21501) |
Data Storage | 10000 records (rotating buffer) |
Alarms | User selected particle channels and limits |
Display | QVGA colour with backlight |
Delay Time | 0 to 24 hours |
Sample Inlet | Isokinetic probe |
Security | Administrator password controlled (optional) |
Communication Mode | USB or Ethernet |
Dimensions (L x W x D) | 27.2 x 9.9 x 5.3cm (10.7 x 3.9 x 2.1") |
Weight | 0.68kg (1.5lbs) |
Power Adapter | 100V AC to 240V AC, 12V DC, 2.5A |
Rechargeable Battery | Li-ion 7.4V 2600mAh |
Battery Duration/Charge Time | 10 hours typical use (5 hours continuous sampling)/3.5 hours |
Calibration | PSL particles in air (NIST traceable) |
Operating Environment | 50 to 104°F (10 to 40°C)/<95% non-consending relative humidity |
Storage Environment | 14 to 122°F (-10 to 50°C)/Up to 98% non-condensing relative humidity |
Warranty | 1 year |
Reviews
SKU | Fluke 985 |
---|---|
Manufacturer Part Code | 4131397 |
Country of Origin | United States |