Fluke's i3000s is an optional accessory designed to be used with Fluke devices such as multimeters and scopemeters in order to carry out current measurements without breaking the circuit.
Unlike other clamping devices, the i3000s does not use jaws to clamp around an application. This device instead ships with 610mm (24inches) of flexible cabling which can be bent around a conductor and secured in place, making it significantly easier to connect to conductors that are difficult to measure using conventional clamp meters .It can be used in combination with conductors up to 178mm in diameter (7")
The i3000s can be used to measure current across three ranges of 30A, 300A and 3000A with 1, 10 or 100mV/A output.
This product is CAT III 600V safety rated.
Fluke i3000s Flexible Current Clamp Key Features
Compatible with many Fluke devices
Measure current up to 3000A
Flexible cable allows attachment to hard to reach conductors
Measure current without breaking a circuit
Three measurement ranges of 30A, 300A and 3000A
£567.00
£680.40 inc vat
Free Delivery*
Stock Due:Typically 1-2 Weeks
Important Notice This item is made-to-order exclusively for you once your order is placed. As a result, it is not eligible for cancellation or return under our standard policy. Your statutory rights remain unaffected.
Spend £150+ (Ex VAT) on any qualified Fluke or Beha-Amprobe product(s) and claim a free tool of your choice from the list at Fluke Promotion. Valid February 17 2025 - July 31 2025.
Claims are made direct to Fluke. Terms and conditions apply.
Technical Information
Specification
Specifications
Current ranges 30 A, 300 A, 3000 A, AC rms
Output sensitivity (AC-coupled) 100 mV, 10 mV, 1 mV per A
Load impedance 100 kΩ minimum
Accuracy at +25 °C ± 1 % of range (45 Hz to 65 Hz)
Linearity 10 % to 100 % of range ± 0.2 % of reading
Noise 8 mV ac rms (30 A), 2 mV ac rms (300 A, 3000 A)
Position sensitivity with cable > 25 mm from the coupling ± 2 % of range
External field with cable > 200 mm from the head ± 1 % of range
Power supply 2 x AA/MN 1500/LR6 Alkaline, , 400 hours, low battery indicator or dedicated external power supply
Temperature Coefficient ± 0.08% of reading per °C
Working voltage see Safety standards section 600 V AC rms or DC
Head Circumference 610 mm (24 in)
Head cable diameter 14.3 mm (0.56 in)
Head bend radius 38.1 mm (1.5 in)
Cable length (head to electronics) 2 m (6.56 ft)
Output connection 0.5 m cable terminated with safety BNC connector. Supplied with 4mm safety plug adapter
Operating temperature range -20 °C to +90 °C (-4 °F to 190 °F) (head) -20 °C to +85 °C (-4 °F to 185 °F) (electronics)
Storage temperature range -40 °C to +105 °C (-40 °F to 221 °F) (head) -20 °C to +85 °C (-4 °F to 185 °F) (electronics)
Operating humidity 15 % to 85 % (non-condensing)
Weight 180 g (0.396 lb) (head) 190 g (0.419 lb) (electronics)
Safety standards BS EN 61010-1: 2001 BS EN 61010-2-032: 2002 BS EN 61010-031: 2002 600 Vrms, Category III, Pollution Degree 2 Use of the probe on uninsulated conductors is limited to 600 V AC rms or dc and frequencies below 1 kHz.
EMC standards EN 61326: 1998 +A1, A2, & A3
Maximum conductor size 610 mm or 914 mm, depending on model