Fluke N5K 3PP54IP Norma 5000 Three Phase Power Analyser
This version of the Fluke Norma 5000 comes as standard with 3 x PP54 power phase input modules, an IEEE488/Ethernet interface and analogue/digital output channels.
Fluke's Norma 5000 is one of the most advanced power quality analysers on the market. With extremely high bandwidth, the latest measurement technology and several useful advanced features built-in, these power instruments are ideal for use on motors, inverters, lighting, power supplies, transformers, automotive components and wherever else power quality needs to be quantified.
The Fluke Norma 5000 is built with high bandwidth built-in, making it suitable for the development of frequency converters and lighting equipment. It can test all aspects of power, including voltage, current and power harmonics to the 40th, can perform FFT analysis with vector diagram display and even includes an integrated digital oscilloscope for simultaneous display of up to 3 measured values with quick view of waveform/distortion.
This power analyser can interface directly with a PC for further analysis of data using Fluke's included software package.
Key Features
Compact, high precision design - easy to carry and perfect for use in busy labs and other environments
Designed for ease of use - simple user interface makes adjusting and using the various functions as simple as possible
Standard configurations allow users to specific the exact functionality required for their own unique application
Galvanically-isolated inputs avoid short circuits
Three phase instruments with dynamic events - shows all phase events simultaneously with parallel acquisition
Voltage, current and power harmonics up to the 40th
FFT (Fast Fourier Transformation) function - calculates harmonics with graphical respresentation
Recorder function and digital oscilloscope built in
User-selectable average time - adjust from 15ms to 3600s
Integrated memory for storage of measured values
RS232, USB and IEEE 488/Ethernet interfaces included
341kHz or 1MHz sample rates for detailed signal analysis
High bandwidth from DC to 3MHz to 10MHz
What's Included?
Fluke Norma 5000 Power Analyser w/ Ethernet Interface and Analogue/Digital Channels
Power Supply Cable
Internal Printer
Fluke NormaView PC Software
User Manual
Test Certificate
Calibration Values
£23,934.00
£28,720.80 inc vat
Free Delivery*
Important Notice This item is made-to-order exclusively for you once your order is placed. As a result, it is not eligible for cancellation or return under our standard policy. Your statutory rights remain unaffected.
Spend £150+ (Ex VAT) on any qualified Fluke or Beha-Amprobe product(s) and claim a free tool of your choice from the list at Fluke Promotion. Valid February 17 2025 - July 31 2025.
Claims are made direct to Fluke. Terms and conditions apply.
Technical Information
Specification
Specifications
General
Number of Phases Fluke Norma 4000: 1 to 3
Weight Fluke Norma 4000: Approx. 5 kg (11 lb.)
Size Fluke Norma 4000: 150 mm x 237 mm x 315 mm (5.9 in x 9.3 in x 12.4 in)
On-board Printer Fluke Norma 4000:
Display Color, 5.7“ / 144 mm - 320 x 240 pixel User-selectable background lighting and contrast.
Bandwidth dc to 3MHz or dc to 10MHz depending on input module
Basic Accuracy 0.2%, 0.1% or 0.03% depending on input modules
Sampling Rate 0.33 MHz or 1 MHz depending on input modules
Voltage Input Range 0.3 V to 1000 V
Current Input Range (direct, not via shunt) 0.03 mA to 20 A depending on input module
Memory for Configurations 4 MB
Memory for Settings 0.5 MB
Fast Fourier Transformation (FFT) To the 40th harmonic
RS232/USB Interface Standard
PI1 Process interface (8 analog/impulse inputs and 4 analog outputs) Optional
Fluke NormaView PC software (for data download, analysis & report writing) Standard
Basic Functions
Fast Fourier Transformation (FFT) Calculation of harmonics with graphical representation. Up to 3 bar graphs are displayed at the same time.
Measured values: U, I, P per phase, order: 1st to 40th harmonics, maximum half sample frequency
Digital Oscilloscope (DSO) Simultaneous display of up to 3 measured values on sample level. Quick view of curve form and distortion.
Integration function (energy) Simultaneous display of up to 6 configurable numeric values. Start/Stop conditions and positive negative direction available.
Vector Display Vector display of HO1 up to 6 signals. For easy testing of the right connection of the instrument and quick overview of the phase angle of each signal.
Recorder Display of average values over time for trend determination.
RAM data memory Storing of sample and average values; setting of start and stop conditions. From the RAM approximately 4 MB are available for the storage of measured values.
Configuration Set up the analyzer to measure and display data in the format required.
Ambient Conditions
Working Temperature Range 5 °C to 35 °C (41 °F to 95 °F)
Storage Temperature Range -20 °C to 50 °C (-4 °F to 122 °F)
Housing Material Fluke Norma Power Analyzers are extremely compact and equipped with a solid metal case to meet stringent EMC requirements.
Climatic Class KYG DIN 40040, max. 85 % relative humidity, non-condensing.
Power supply 85 V ac to 264 V ac, 50 Hz to 60 Hz, dc 100 to 260 V, ca. 40 VA European plug with switch. Binding post for current available on some models.
Measuring Inputs Safety sockets 4 mm, 2 for each input. External shunt connection over BNC socket.
Operation Membrane keyboard with cursor – function keys and direct functions.
Connections Rear panel of the 3-phase Analyzer
Frequency and Synchronization
Range DC and 0.2 Hz to sample rate
Accuracy ±0.01 % of measured value (reading)
Standards and Safety
Electrical Safety EN 61010-1 / 2nd Edition 1000 V CAT II (600V CAT III), Degree of pollution 2, safety Class I, EN 61558 for transformer, EN 61010-2-031/032 for accessories
Maximum inputs For voltage inputs Measurement range 1000 Veff, 2 kVpeak, For current inputs Measurement range 10 Aeff, 20 Apeak
Test voltage Net input case (protective conductor): 1.5 KV AC Net connection Measurement input: 5.4 kV AC Measurement inputs Case: 3.3 kV AC Measurement input input: 5.4 kV
Electromagnetic susceptibility Emission: IEC 61326-1, EN 50081-1, EN 55011 Class B Immunity: IEC 61326-1 / Annex A (industrial sector), EN 50082-1
Power Phases
The Fluke Norma 4000 Power Analyzer can be equipped with up to three power phases and the Fluke Norma 5000 Power Analyzer can be equipped with up to six power phases. Users can select the power phase best suited for their application. Specifications vary depending on the model of the power phase. Each modular plug-in power phase consists of a voltage and a current measurement channel. Each measuring channel is available for each basic unit, however only one kind of channel can be used per unit. Check standard configurations.
Power Phase Channels
PP42 Accuracy: 0.2% (0.1% rd + 0.1 % rg) Current range: 20 A Sampling rate: 341 kHz Bandwidth: 3 MHz
PP50 Accuracy: 0.1% (0.05% rd + 0.05 % rg) Current range: 10 A Sampling rate: 1 MHz Bandwidth: 10 MHz
PP54 Accuracy: 0.1% (0.05% rd + 0.05 % rg) Current range: 10 A Sampling rate: 341 kHz Bandwidth: 3 MHz
PP64 Accuracy: 0.03% (0.02% rg + 0.01% rg) Current range: 10 A Sampling rate: 341 kHz Bandwidth: 3 MHz