These Megger VLF Sine Systems are suitable for medium-voltage cable testing and are available with 5m, 10m, and 15m high-voltage leads. These units are engineered to perform a wide range of cable diagnostics, including voltage withstand testing, sheath testing, and sheath fault pinpointing when used wth the step voltage probe ESG NT2. Optional internal tan delta measurement expands the system’s capability to assess both cable integrity and long-term condition, making it a complete solution for both commissioning and maintenance of MV networks.
The system automatically adjusts the test frequency to match the cable length, enabling reliable testing even on 35kV-rated cables up to 25km. It features a large colour touch display and intuitive software with an analogue residual voltage indicator.
Connectivity and reporting are seamless: all test data can be exported via USB or, soon, wireless connection to mobile devices. Using the MeggerBook Lite software (included), users can generate clear, professional reports for documentation or regulatory compliance.
For users requiring expanded diagnostic capabilities, the system can act as a voltage source for the PDS 62-SIN partial discharge coupler, creating a universal platform for VLF withstand testing, tan delta assessment, and offline partial discharge measurement.
Get a free gift this Black! Even better, this bonus stacks with any other offer.
Free item will automatically add to your basket. Limited Stock. Offer is based on ex VAT basket total after discounts and before shipping costs. See Black Friday Offers for details.
Remember: We will not be beaten on price. Contact us if you've seen a cheaper price.
| Output Voltage | |
|---|---|
| VLF Sine Wave | 0 … 44 kVRMS / 0 ... 62 kVpeak |
| DC Voltage | ± 0 … 62 kV |
| VLF Rectangular Voltage | 0 … 62 kV |
| Accuracy | ± 1 % |
| Resolution | 0.1 kV |
| Output Current | |
| Source Output Current | 23 mA @ 62 kVpeak |
| Accuracy | ± 1 % |
| Resolution | 1 μA |
| Frequency Range | 0.01 ... 0.1 Hz autom. frequency adjustment |
| Output Load | 1 μF @ 0,1 Hz at 44 kVRMS 10 μF maximum test capacity |
| Internal Tan Delta | |
| Measuring Frequency | 0.01 ... 0.1 Hz |
| Measuring Range | 10-4...100 |
| Accuracy | 10-4 |
| Resolution | 10-5 or 10-6 |
| Sheath Testing | 0 … -20 kV DC |
| Sheath Fault Pinpointing | 0 … -20 kV DC Pulse rate 0.5:1, 1:2, 1:3, 1:4, and 1.5:0.5 |
| Safety | autom. discharging of the test object and the residual voltage indicator |
| Input Voltage | 100 V … 264 V, 50/60 Hz, 2000 VA |
| Duty Cycle | Continuous |
| Display | 7” colour-touchscreen |
| Interfaces | USB, LAN, wireless (coming soon) |
| Internal Memory | For at least 1000 measurements |
| Dimensions (W x H x D) | 530 (670*) x 640 x 510 mm 20.9 (26.4*) x 25.2 x 20.1 in. |
| Weight | 59 kg 130 lbs. |
| Protection Class | IP 21 |
| Operating Temperature | - 20 °C … + 55 °C -4 °F … 131 °F |
| Storage Temperature | - 20 °C … + 70 °C -4 °F … 158 °F |
| * incl. carrying handles | |