Free Tyre Inflator. Spend £500+ (ex VAT) View

Megger TM1700 Circuit Breaker Analyser System

Free Tyre Inflator (Spend £500+)
All Megger Products
  • Analogue options
  • Touch screen On/Off
  • On-screen keyboard On/Off
SKU
MEG-TM1700

Read More

The Megger TM1700 Series Circuit Breaker Analyser Systems are designed for reliable and accurate circuit breaker time and travel testing, including DualGround testing in electrically noisy high-voltage substations. Based on technology from Megger’s TM1800 series, the instruments combine active interference suppression with galvanically isolated inputs and outputs to provide dependable measurements, including PIR times and values.

DualGround capability allows testing with both sides of the breaker grounded, helping to reduce the risk of induced high voltages during testing. The standalone models feature a large colour touchscreen and an intuitive interface, with software for creating custom test templates, while computer-controlled operation is available via CABA Win software. The range is available in different configurations to suit varying testing requirements, with analogue options supplied with 10 m (33 ft) analogue cables.

Complete test on medium voltage circuit breaker with TM1700

Key Features

  • Input for external clamp-on CT
  • Control section:
    • Three independent contact functions
    • Pre-programmed sequences C, O, C-O, O-C, O-C-O
    • Timing of a and b auxiliary contacts
    • Coil current, voltage and resistance
  • Timing Aux section:
    • Six galvanically isolated channels
    • Polarity insensitive
    • Dry and wet auxiliary contacts
  • Timing M/R section:
    • Six inputs
    • High-resolution 15 μV and up to 40 kHz sampling
    • Main and parallel resistor contact timing
    • Resistance value of parallel resistors
  • Analogue section:
    • Six channels (three optional)
    • Supports industrial analogue transducers
    • Insulated channels, measure up to 250 V without volt. div.
    • High resolution 0.3 mV, sampling rate 40 kHz
  • Digital section:
    • Six channels
    • Incremental transducers with RS422
    • Up to ±32000 pulses resolution
    • Up to 40 kHz sampling
  • Mains input
  • DC out:
    • General voltage source,12 V
  • DRM
  • Earth (ground) terminal
  • Ethernet port
  • USB ports
  • Trig IN:
    • Used for external trig of the unit. Contact make / break or voltage signal.
  • DCM interface
  • Navigation buttons:
    • Works in parallel with the touch screen buttons.
    • Most of the CABA Local functions are controlled by the ten navigation buttons.
  • Touch screen On/Off
  • On-screen keyboard On/Off
  • Display (touch screen):
    • High brightness for good visibility in direct sunlight.
  • Brightness setting
  • POSITION:
    • Indicates the position of the circuit breaker main contacts if the coil circuit is connected to the control section.
  • SEQUENCE:
    • Indicates the next operation of the circuit breaker. If Auto-detect breaker state is enabled in CABA Local or CABA Win, only possible sequences for the circuit breaker are selectable.
  • OPERATE/MEASURE:
    • Initiates the selected operation sequence and makes the measurement. The green “READY” LED must be lit before turning the rotary switch. The yellow “OPERATING” LED is lit as long as the sequence is performed.
  • On/Off switch

Product Range

  • Megger TM1710 Circuit Breaker Analyser System
  • Megger TM1710 Circuit Breaker Analyser System with Analogue Option
  • Megger TM1720 Circuit Breaker Analyser System
  • Megger TM1720 Circuit Breaker Analyser System with Analogue Option
  • Megger TM1740 Circuit Breaker Analyser System
  • Megger TM1740 Circuit Breaker Analyser System with Analogue Option
  • Megger TM1750 Circuit Breaker Analyser System
  • Megger TM1750 Circuit Breaker Analyser System with Analogue Option
  • Megger TM1760 Circuit Breaker Analyser System
  • Megger TM1760 Circuit Breaker Analyser System with Analogue Option
Call for Pricing

We require additional information

Call 01642 931 329 or complete the form:

Offers

Free Tyre Inflator (Spend £500+)

Automatically adds to your basket when the total exceeds £500+ (ex VAT). Limited Stock. More details here.

Technical Information
Specification
Environment
Application Field For use in high-voltage substations and industrial environments
Operating Temperature -20°C to +50°C (-4°F to +122°F)
Storage & Transport Temperature -40°C to +70°C (-40°F to +158°F)
Humidity 5% - 95% RH, non-condensing
CE-Marking
EMC 2004/108/EC
LVD 2006/95/EC
General
Mains input (nominal) 100 - 240 V AC, 50 / 60 Hz
125 - 340 V DC
Power Consumption 200 VA (max)
Dimensions 500 x 185 x 410 mm (19.7” x 7.3” x 16.1”)
Weight 12 kg (26.5 lbs)
External Input - TRIG IN Voltage Mode
Input Range 0 - 250 V AC / DC
0 - 350 V DC
Threshold Level User configurable in software in steps of 1 V
External Input - TRIG IN Contact Mode
Open Circuit Voltage 30 V DC ±15%
Short Circuit Current 10 - 40 mA
Threshold Level 1 - 2 kΩ
External Outputs - DC OUT
General Voltage Source 12 V ±10%, short-circuit protection 1.7 A
External Outputs - DRM Only for SDRM202 and DRM1800, Voltage Mode
Output Voltage 12 V DC ±10%
Short Circuit Protection PTC 750 mA
Switching Current <750 mA, resistive load
Communication Interfaces
USB Universal Serial Bus ver. 2.0
Ethernet 100 base-Tx Fast Ethernet
HMI, Human-Machine Interface
CABA Local Circuit breaker analysis software
Available Languages English, French, German, Russian, Spanish, Swedish. Translation kit available
Display High brightness SVGA 800x600, Touch screen
Diagonal Size 21 cm (8”)
Keyboard On screen
Control section (1 or 2) - General
No. of Channels 3
Time Base Inaccuracy ±0.01% of reading ±1 sample interval
Max. Sample Rate 40 kHz
Measurement Time 200 s at 10 kHz sample rate
Control section (1 or 2) - Non-Bouncing Switch
Max Current 60 A AC / DC, pulse ≤ 100 ms
Duration User configurable in steps of 1 ms
Delay User configurable in steps of 1 ms
Control section (1 or 2) - Current Measurement
Measurement Range 0 to ±80 A AC / DC
Resolution 16 bits
Inaccuracy ±2% of reading ±0.1% of range
Control section (1 or 2) - External Current Measurement, CT
Max Input ±1 V peak
Scaling 100 A / 1 V
Range ±80 A / ±0.8 V
Control section (1 or 2) - Voltage Measurement
Measurement Range 0 - 250 V AC, 0 to ±300 V DC
Resolution 12 mV
Inaccuracy ±1% of reading ±0.1% of range
Timing M/R Section (1) - General
No. of Channels 6
Time Base Inaccuracy ±0.01% of reading ±1 sample interval
Min. Resolution 0.05 ms
Max. Sample Rate 40 kHz
Measurement Time 200 s at 10 kHz sample rate
Timing M/R Section (1) - Timing of Main and Resistive Contacts
Open Circuit Voltage 6 V or 26 V ±10% (Toggling at every second sample)
Short Circuit Current 9.7 mA or 42 mA ±10%
Timing M/R Section (1) - Status Threshold
Main Closed < 10 Ω < Open
Main and Resistor Main < 10 Ω <PIR < 10 kΩ < Open
Timing M/R Section (1) - PIR Resistance Measurement
Supported PIR Types Linear PIR
Measurement Range 30 Ω - 10 kΩ
Inaccuracy ±10% of reading ±0.1% of range
Timing M/R Section (1) - Voltage Measurement
Measurement Ranges ±50 Vpeak, ±15 Vpeak, ±0.5 Vpeak
Resolution 16 bits
Inaccuracy ±1% of reading ±0.1% of range
Analogue Section (none, 1 or 2) - General
No. of Channels 3 isolated channels
Time Base Inaccuracy ±0.01% of reading ±1 sample interval
Max. Sample Rate 40 kHz
Measurement Time 200 s at 10 kHz sample rate
Transducer Resistance 500 Ω - 10 kΩ at 10 V output
Analogue Section (none, 1 or 2) - Output
Voltage Output 10 V DC ±5%, 24 V DC ±5%
Max. Output Current 30 mA
Analogue Section (none, 1 or 2) - Current Measurement
Measurement Range ±22 mA
Resolution 16 bits
Inaccuracy ±1% of reading ±0.1% of range
Analogue Section (none, 1 or 2) - Voltage Measurement
Input Voltage Range 0 - 250 V AC, 0 to ±300 V DC
Measurement Ranges ±10 V, ±400 V
Resolution 16 bits
Inaccuracy 250 V range: ±1% of reading ±0.1% of range
10 V range: ±0.1% of reading ±0.01% of range
Digital Section - General
No. of Channels 6
Supported Types Incremental transducers, RS422
Time Base Inaccuracy ±0.01% of reading ±1 sample interval
Max. Sample Rate 40 kHz
Measurement Time 200 s at 10 kHz sample rate
Digital Section - Output
Voltage 5 V DC ±5% or 12 V DC ±5%
Max. Output Current 700 mA
Digital Section - Digital Input
Range ±32000 pulses
Resolution 1 pulse
Inaccuracy ±1 pulse
Timing Aux Section - General
No. of Channels 6 isolated channels
Time Base Inaccuracy ±0.01% of reading ±1 sample interval
Max. Sample Rate 40 kHz
Measurement Time 200 s at 10 kHz sample rate
Timing Aux Section - Voltage Mode
Input voltage range 0 - 250 V AC, 0 to ±300 V DC
Status Threshold ±10 V
Inaccuracy ±0.5 V
Timing Aux Section - Contact Mode
Open Circuit Voltage 25 - 35 V DC
Short Circuit Current 10 - 30 mA DC
Status Threshold Closed < 100 Ω, Open> 2 kΩ
DCM Module (Optional) - General
No. of Channels 6
Weight 1.4 kg (3.1 lbs)
Dimensions 145 x 160 x 70 mm (5.7” x 6.3” x 2.6”)
DCM Module (Optional) - Output
Voltage 0 - 5 V rms AC
Current 0 - 70 mA rms AC
Document Downloads
Megger TM1700 Circuit Breaker Analyser System Datasheet Datasheet
Additional Information
SKU
MEG-TM1700

Customer Reviews

 
Megger TM1700 Circuit Breaker Analyser System