About the Megger TORKEL 930 Battery Load Unit Tester

The upgraded version of Megger's Torkel 910 Battery Load Unit Tester, the TORKEL 930 has higher maximum current and voltage as well as additional BVM functionality, charging measurement capabilities and built-in memory storage with full reporting functionality.

Megger TORKEL units provide professional technicians with the means to perform load and discharge testing on various types of battery system. Batteries can be tested while in service so there's no drops needed; the TORKEL will test the overall efficiency of your battery system and allow you to make adjustments or changes as needed to ensure optimal power efficiency.

Take a look at the TORKEL series in action in this video from Megger:

Megger TORKEL 900

Megger TORKEL units are designed to perform high accuracy testing while shortening the actual time you spend testing. With high discharge capacity at up to 220A, tests can be conducted at constant current, constant power, constant resistance or in accordance with a pre-selected load profile. If higher current is needed, it also possible to link two or more TORKEL units together or extra battery load units to the TORKEL 930.

As this is the upgraded version of the TORKEL 910, the 930 comes with additional functionality. This includes:

  • Full Report Functionality - store your results in internal memory and transfer to PC using USB connection for further analysis
  • Battery Voltage Monitoring - using an optional BVM module, the TORKEL 930 can be used to automatically log battery cell voltage during testing
  • Charging Measurements - calculate how batteries are operating during the charging cycle

Expand Your Capabilities with Extra Load Units

Megger's TORKEL 930's capabilities can be expanded further for use with larger battery banks by using optional TXL extra load units.

There are four loads available - the TXL830, TXL850, TXL870 and TXL890. Please see Megger's datasheet (available as a download further below) for a comprehensive breakdown of the capabilities of each of the battery load units.

Megger TORKEL 930 Battery Load Tester Key Features

  • Perform load and discharge testing on battery systems to determine actual capacity
  • Allows batteries to be tested while still in service
  • Dynamic discharge technology gives full power at all voltages
  • Maximum current of 110A
  • Maximum voltage of 300V
  • Built-in touchscreen for easy operation
  • Safety built-in with emergency stop button, spark-free contacts and blocked airflow detection
  • Real-time monitoring of battery status during the testing procedure
  • BVM battery voltage monitoring possible using optional BVM module
  • Integrated memory storage with transfer to PC using USB stick
  • Charging measurement

What's Included?

  • Megger TORKEL 930 Battery Load Tester
  • Mains Cable
  • Cable Set (2 x 3m, 25mm²)
  • Soft Case for Cables
  • TORKEL Viewer Software
  • USB Memory Stick

If ordering the CS-19391 version, the soft case is replaced with:

  • Large Transport Case

Optional Accessories

These extra accessories can be ordered by calling our sales team quoting the part numbers shown.

Extra Loads
Part Number Description
BS-59093 TXL830 Extra Load including cable set GA-09550, Control Cables 2 x 2m and Transport Case
BS-59095 TXL850 Extra Load including cable set GA-09550, Control Cables 2 x 2m and Transport Case
BS-59095 TXL870 Extra Load including cable set GA-00550, Control cables 2 x 2m and Transport Case
BS-59099 TXL890 Extra Load including cable set GA-00550, Control cables 2 x 2m and Transport Case
Other Items
Part Number Description
GA-00550 Cable set, 2 x 3m, 25mm², female/clamp. 110A, 3.0kg
GA-00552 Extension cable for GA-00550 cable set, 2 x 3m, 25mm², male/female
GA-09550 High rating cable set, 2 x 3m, 70mm², female/fork. 270A, 5.0kg
GA-09552 High rating extension cable for GA-09550 cable set, 2 x 3m, 70mm², male/female
GA-00210 Sensing lead set for measuring voltage at battery terminals. 2 x 5m (16.4ft)
XA-12992 DC clamp-on probe, 200A
XA-12990 DC clamp-on probe, 1000A
CJ-59092 System of 16 BVM voltage monitoring units
CJ-59093 System 31 BVM voltage monitoring units
CJ-590906 System of 61 BVM monitoring units
CJ-59198 BVM special 600V
CJ-59090 BVM single unit

Megger TORKEL 900 Series Technical Specifications

Environment
Application Field Intended for use in high voltage substations and industrial environments
Temperature Operating: 0 to +50°C (32 to +122°F), power derating at temperatures over +35°C
Storage: -40 to +70°C (-40 to +158°F)
Humidity 5 to 95% RH, non-condensing
Shock/Vibration/Fall Instrument only: ETSI EN 300 019-2-7 class 7M2
Instrument in transport case: ITSA 2A
Altitude Operating: 3000m
Storage: 10,000m
Encapulsation class: IP20
CE Marking LVD: IEC61010-1: 2010 and IEC 61010-2-030
EMC: IEC61326-1
General Specifications
Mains Voltage 100 to 240V AC, 50/60Hz
Power Consumption 200W max
Power Interruption 40ms max
Protection Thermal cutouts, automatic overload protection, emergency stop button
Dimensions 519 x 315 x 375mm (20.5 x 12.5 x 14.7")
Weight 19.5kg (43.0lbs) instrument
31.9kg (70.3lbs) including transport case
37kg (82lbs) including large transport case
Display 7" LCD, capacitive touch screen
Available Languages English, French, German, Spanish and Swedish
Measuement Specifications
Current
Display Range 0.0 to 2999.0A
Basic Inaccuracy ±(0.5% of reading +0.1A)
Resolution 0.1A
Input for Clamp-On Probe
Range 0 to 1000mV DC
mV/A ratio 0.30mV/A to 100.00mV/A
Input Impedance >1MΩ
Voltage
Range 0 to 500V DC
Inaccuracy ±(0.5% of reading + 0.1V DC)
Resolution 0.1V
Sample Rate 10Hz, values are saved when change is >10mV
Time Measurement
Inaccuracy ±0.1% of reading ±1 digit
Load Section
Battery Voltage 7.5 to 300V/500V
Power 15kW max
Load Patterns Constant current, constant power, constant resistance, current or power profile
Constant I
TORKEL 910 0 to 110.0A
TORKEL 930/950 0 to 220.0A
Inaccuracy ±(0.5% + 0.2A)
Resolution 0.1A
Ripple Max 0.5A peak
Constant R
Range 300mΩ to 3kΩ
Inaccuracy ±1% typical
Resolution 100mΩ
Constant P
Range 0 to 15kW
Inaccuracy ±1% typical
Resolution 10W
Inputs
Plus 7.5 to 300V, 7.5 to 500V
Minus 0V
I EXT ≤ 1V 1V DC, 300V DC to ground
Voltage Sense Impedance to the current terminals is more than 1MΩ
Outputs
Alarm Relay Contact 28V DC, 8A, 240V AC, 8A
Devices higher than CAT II must not be attached
TXL STOP Relay Contact 250V DC, 0.28A. 28V DC, 8A, 250V AC, 8A
9V DC 9V DC, ±7% max 100mA
Communication Ports
BVM1, BVM2 USB connection for BVM units
USB port USB connection for USB memory
Service For service of the instrument