The Metrel MI3144 Euro-Z 800V Multifunction Installation Tester is a portable, practical, precise multifunctional tester suitable for verifying the effectiveness of automatic trip out protection in HV equipment such as transformers, generators, turbines, contractors, distribution boards and switchyards.
The Metrel MI3144 Euro-Z 800V Multifunction Installation Tester can be powered using a Li-ion battery or mains supply and is intended for use with the following Metrel products:
The Metrel MI3144 Euro-Z 800V Multifunction Installation Tester is able to communicate with Metrel's app and testers via Bluetooth.
Its rugged, practical design, as well as its comprehensive measurement capabilities and features, make the Metrel MI3144 Euro-Z 800V Multifunction Installation Tester suitable for checking industrial systems. With its case closed the Metrel MI3144 Euro-Z 800V Multifunction Installation Tester is rated IP65, it has an IP54 rating with the case open. This tester is equipped with the following measurement features and capabilities:
As a result of the Metrel MI3144 Euro-Z 800V Multifunction Installation Tester extensive testing capabilities, it can be used for a variety of applications in addition to the aforementioned verification of trip-out protection. This high-precision 4-wire 300A Z line and loop impedance tester is suitable for use in the following capacities:
The Metrel MI3144 Euro-Z 800V Multifunction Installation Tester is a comprehensive, durable, accurate tester suitable for checking industrial and electrical systems.
Get a free gift this Black! Even better, this bonus stacks with any other offer.
Free item will automatically add to your basket. Limited Stock. Offer is based on ex VAT basket total after discounts and before shipping costs. See Black Friday Offers for details.
Remember: We will not be beaten on price. Contact us if you've seen a cheaper price.
| Function | Measuring Range | Resolution | Accuracy |
|
Impedance [Z] Z line mΩ Z loop mΩ |
0.1 mΩ … 199.9 mΩ | 0.1 mΩ | ±(5 % of reading + 3 mΩ) |
| 200 mΩ … 1999 mΩ | 1 mΩ | ||
| 2.00 Ω … 19.99 Ω | 10 mΩ | ±(5 % of reading + 3 digits) | |
|
Impedance [Z] High current ΔR |
0.1 mΩ … 199.9 mΩ | 0.1 mΩ | ±(5 % of reading + 3 mΩ) |
| 200 mΩ … 1999 mΩ | 1 mΩ | ||
| 2.00 Ω … 19.99 Ω | 10 mΩ | ±(5 % of reading + 3 digits) | |
|
Impedance [Z] High current Rsel |
0.1 mΩ … 199.9 mΩ | 0.1 mΩ | ±(8 % of reading + 3 mΩ) |
| 200 mΩ … 1999 mΩ | 1 mΩ | ||
| 2.00 Ω … 19.99 Ω | 10 mΩ | ±(8 % of reading + 3 digits) | |
|
DC resistance [R] R line mΩ |
0 mΩ … 1999 mΩ | 1 mΩ | ±(5 % of reading + 3 digits) |
| 2.00 Ω … 19.99 Ω | 10 mΩ | ||
|
Earth potential [U] Utouch |
0.0 V … 199.9 V | 0.1 V | Calculated value |
| 200 V … 999 V | 1 V | ||
|
Earth potential [U] Um |
1 mV … 1999 mV | 1 mV | ±(2 % of reading + 2 digits) |
| 2.00 V … 19.99 V | 10 mV | ||
| 20.0 V … 199.9 V | 0.1 V | ||
|
ELR test [I and t] ELR I |
0.1 mA … 199.9 mA | 0.1 mA | ±(5 % of reading + 3 digits) |
| 200 mA … 1999 mA | 1 mA | ||
| 2.00 A … 19.99 A | 10 mA | ||
|
ELR test [I and t] ELR t |
0.1 ms … 199.9 ms | 0.1 ms | ±(2 % of reading + 3 digits) |
| 200 ms … 1999 ms | 1 ms | ||
| 2.00 s … 20.00 s | 10 ms | ||
| General Data | |||
| Battery power supply | 7.2 V DC (4.4 Ah Li-ion) | ||
| Battery charging time | typical 3.0 h (deep discharge) | ||
| Mains power supply | 90 ... 260 V AC, 45 ...65 Hz, 80 VA | ||
| Over-voltage category | 300 V CAT II | ||
| Protection classification | reinforced insulation | ||
| Measuring category | 600 V CAT IV | ||
| Pollution degree | 2 | ||
| Degree of protection | IP 65 (case closed), IP 54 (case open) | ||
| Dimensions (w x h x d) | 36 cm x 16 cm x 33 cm | ||
| Weight | 6.5 kg (without accessories) | ||