The BAUR Protrac locates cable and sheath faults, combining methods for joint location and cable tracing into a single system. The Protrac has a two-level signal processing architecture that delivers exceptional sensitivity while effectively suppressing ambient noise.
Measurement data is transmitted in real time to the headphones and the control unit via Bluetooth. The system also features intelligent automation. Measurement parameters are adjusted automatically based on environmental factors, and the intuitive capacitive touchscreen makes operation straightforward, even for less experienced users.
Five sets are available to choose from.
Tracing Set | Pin-Pointing Set | Acoustics Set | Step Voltage Set | Audio Frequency Set | |
---|---|---|---|---|---|
CU control unit incl. Carrying strap 8 x rechargeable batteries, NiMH Mignon AA 1.2 V IEC LR6 Protrac tool Charger incl. country-specific adapter USB cable 2.0 for software updates |
✔ | ✔ | ✔ | ✔ | ✔ |
AGP acoustic ground probe incl. Contact bell, Ø 79 mm Tripod Telescopic handle Contact spikes: 50, 100, 150 mm 6 x rechargeable batteries, NiMH Mignon AA 1.2 V IEC LR6 Charger incl. country-specific adapter |
- | ✔ | ✔ | - | - |
SVP step voltage probes incl. SVP step voltage probe, red SVP step voltage probe, black Connection cables, red and black, 1.5 m each |
- | ✔ | - | ✔ | - |
AFP audio frequency probe incl. 6 x rechargeable batteries, NiMH Mignon AA 1.2 V IEC LR6 Charger incl. country-specific adapter |
✔ | - | - | - | ✔ |
Bluetooth headphones inc. USB charging cable Charger incl. country-specific adapter |
✔ | ✔ | ✔ | - | ✔ |
TG 20/50 audio frequency transmitter incl. Carrying strap, adjustable Mains supply cord, 2.5 m Earth cable, 3 m, with earth terminal Connection cables, red and black, touch-proof, 2 m each with connection clips Connection clip, black Connection clip, red Earth spike Connection cable, 25 m, on hand reel TG 20/50 user manual |
✔ | - | - | - | ✔ |
Protrac User Manual | ✔ | ✔ | ✔ | ✔ | ✔ |
Transport Bag | ✔ | ✔ | ✔ | ✔ | ✔ |
✔ Included in standard delivery -: Not available |
CU Control Unit | |
---|---|
Intuitive user interface in multiple languages | |
Loudspeaker | 3 W |
Display | Transmissive colour TFT |
Display Size | 4.3", 480 x 272 pixels |
Brightness | 800 cd/m² |
Touchscreen | Capacitive, operable with gloves |
Paste | Paste |
Rechargeable Battery Mode | 8 x NiMH Mignon AA 1.2 V IEC LR6 |
Non-Rechargeable Battery Mode | 8 x alkaline batteries AA 1.5 V IEC LR6 |
Rechargeable or Non-Rechargeable Battery Life | Approx. 6 h* |
Charging Time | Approx. 3.5 h |
Degree of Protection | IP54 |
Dimensions (W x H x D) | 205 x 143 x 69 mm |
Weight | Approx. 1.1 kg |
AFP Audio Frequency Probe | |
Methods | Maximum method Minimum method C-Max Direct depth measurement Current measurement 45° depth measurement Twist method Minimum distortion method |
Data Transmission | Bluetooth |
Frequency Range | 16 Hz - 15 kHz (40 Hz - 10 kHz for depth measurement) |
Accuracy | 1% at 1 m |
Dynamic Range | 10 mA - 10 kA @ 50 Hz 20 μA - 20 A @ 10 kHz |
Rechargeable Battery Mode | 6 x NiMH Mignon AA 1.2 V IEC LR6 |
Non-Rechargeable Battery Mode | 6 x alkaline batteries AA 1.5 V IEC LR6 |
Rechargeable or Non-Rechargeable Battery Life | Approx. 14 h* |
Charging Time | Approx. 3.5 h |
Degree of Protection | IP54 |
Dimensions (W x H x D) | 115 x 705 x 90 mm |
Weight | Approx. 1.8 kg |
AGP Acoustic Ground Probe | |
Data Transmission | Bluetooth |
Range | 40 m |
Rechargeable Battery Mode | 6 x NiMH Mignon AA 1.2 V IEC LR6 |
Non-Rechargeable Battery Mode | 6 x alkaline batteries AA 1.5 V IEC LR6 |
Rechargeable or Non-Rechargeable Battery Life | Approx. 16 h* |
Charging Time | Approx. 3.5 h |
Degree of Protection | IP65 |
Dimensions | Ø 225 x 146 mm |
Weight | Approx. 2.6 kg (without handle) Approx. 3.2 kg (with handle) |
Acoustic and Electromagnetic Pin-Pointing | |
Filter | ANS (Adaptive Noise Suppression) |
Acoustic Gain | Automatic/manual, 0 - 34 dB |
Electromagnetic Gain | Automatic/manual, 0 - 50 dB |
Propagation Time Measurement Range | 0 - 100 ms (approx. 50 m @ v = 500 m/s) |
Resolution | 21 μs (approx. 0.1 m @ v = 500 m/s) |
Acoustic Bandwidth | 1 Hz - 2 kHz |
Distance Indicator | In milliseconds, metres or feet with historic measured values |
Left/Right Indication | Yes |
Sheath Fault Location | |
Measurement Range | 1 μV - 220 V |
Noise Suppression | 50/60 Hz, 16 2/3 Hz, DC |
Zero Point Adjustment | automatic |
SVP Step Voltage Probes Length | Extendable, approx. 580 mm - 1,100 mm |
Weight per Probe | Approx. 0.9 kg |
General | |
Rechargeable Batteries, Charger - Power supply | 100 - 240 V, 50/60 Hz |
Rechargeable Batteries, Charger - Output voltage | DC 5 - 14.4 V, 1 A ±100 mA |
Safety/Work Safety | Volume limited to 85 db (A) |
Ambient Temperature (Operational) | -20°C to +55°C |
Storage Temperature | -20°C to +65°C |
Relative Humidity | Non-condensing |
Safety and EMC | CE-compliant in accordance with Low Voltage Directive (2014/35/EU) EMC Directive (2014/30/EU) EN 60068-2-ff Environmental testing |
* Operating period depends on environmental conditions |