Chauvin Arnoux's highest spec multifunction installation tester, the CA6117 includes every function you'll need for completing, testing and verifying electrical installations.
Ergonomically-designed for comfortable use, the CA6117 is designed to make testing easier, quicker and safer. It has colour-coded connectors for making connections easier, an integrated, high-definition colour screen, switch for direct access to all measurements, navigation keys and a handy backlight for use in poor lighting conditions. A built-in contextual help function is also included and will guide users through functions (ideal for those who are unfamiliar with the system or new to electrical installations).
The CA6117 is packed full of features: it can test voltage/frequency, resistance/continuity, 3P earth, Z-Loop, Z-line, RCDs (including type B), current (using clamps - sold separately), phase sequence, power, harmonics and more!
This product is ideal for absolutely any installation application, including initial electrical testing of new installations, electrical testing after renovations, periodic testing and servicing/troubleshooting.
Continuity/Resistance | |
---|---|
I Rated / Range / Resolution | I > 200 mA / 39.99 Ω/ 0.01Ω / ± (1.5% of measurement + 2 cts) 12 mA / 39.99 Ω & 399.9 Ω / 0.01 & 0.1 Ω /± (1.5% of measurement + 5 cts) with beep |
Range / Resolution / Accuracy | 4 kΩ/ 1 Ω / ±(1.5 % of measurement + 5 cts) 40 kΩ - 400 kΩ/ 10 Ω - 100 Ω / ±(1.5 % of measurement + 2 cts) |
Insulation | |
Rated Voltage | Utest: 50 /100 / 250 / 500 / 1,000 V DC |
Range / Resolution / Accuracy | 0.01 MΩ to 2 GΩ / 10 kΩ to 1 MΩ / ±(5 % of measurement + 3 cts) |
Short Circuit Current | ≤ 3 mA |
Earth | |
3P Earth Range / Resolution / Accuracy |
0.50 Ω to 40 Ω/ 0.01 Ω / ±(2 % of measurement + 10 cts) 40 Ω to 15 kΩ / 0.1 Ω to 1 Ω / ±(2 % of measurement + 2 cts ) 15 kΩ to 40 kΩ / 10 Ω/ ±(10 % of measurement + 2 cts ) |
Others | Measurement of resistance of auxiliary stakes RH & RS (up to 40 kΩ) |
Ufk | Complies with SEV 3569 |
1P Selective Earth Range / Resolution / Accuracy |
0.20 Ω to 39.99 Ω - 40 Ω to 399.9 Ω / 0.01 Ω – 0.1 Ω / ±(10 % of measurement + 10 cts) (ISel via clamp) |
Loop Impedance (Zs (L-PE) and Zi (L-N or L-L)) - 1P Live Earth | |
Live Earth Installation Voltage / Frequency |
90 to 500 V / 15.8 to 17.5 Hz - 45 to 65 Hz |
High Current Mode with Trip Zs (L-PE) and Zi (L-N or L-L) Range / Resolution / Accuracy |
Max. test current: 7.5 A (0.050) 0.100 Ω to 0.5 Ω / 0.001 Ω/ ±(10% of measurement + 20 cts) • 0.5 Ω to 3.999 Ω / 0.001 Ω/ ±(5 % of measurement + 20 cts) 3.999 to 39.99 Ω/ 0.01Ω / ±(5% of measurement + 2 cts) • 39.99 Ω to 399.99 Ω / 0.1 Ω/ ±(5 % of measurement + 2 cts) |
No Trip Mode (Zs (L-PE) only) | Test current: 6 mA – 9 mA – 12 mA (as required) 0.20 Ω to 0.99 Ω / 0.01 Ω / ±(15 % of measurement + 10 cts) 1.00 to 1.99 Ω / 0.01 Ω / ±(15 % of measurement + 3 cts) 2.00 to 39.99 Ω / 0.01 Ω / ±(10 % of measurement + 3 cts) 40.00 Ω to 399.9 Ω / 0.1 Ω / ±(5 % of measurement + 2 cts) 400 to 3999 Ω / 1 Ω / ±(5 % of measurement + 2 cts) |
Calculation of lk Short Circuit Current (PFC (Zs)), I Sc PSCC (Zi) |
Fault current and short-circuit current: 0.1 A to 20 kA |
Integrated Fuse Table | Yes |
Voltage Drop ΔV%(Zi) | -40 % to + 40 % |
Others | Measurement of the resistive and inductive components of the Zs and Zi impedances |
AC and A-Type RCDs | |
Installation Voltage / Frequency | 90 V to 500 V / 15.8 Hz to 17.5 Hz and 45 Hz to 65 Hz |
IΔn | 10/30/100/300/500/650/1,000 mA (90 V – 280 V) or variable - 10/30/100/300/500 mA (280-550 V) or variable Ramp and pulse test |
No-Trip Test | at ½ IΔn – Duration: 1,000 ms or 2,000 ms |
Ramp Mode | 0.2 to 0.5 x IΔn (Uf) / 0.3 x IΔn to 1.06 x IΔn in increments of 3.3 % x IΔn |
Trip Time Measurement Range / Resolution / Accuracy |
0.2 to 0.5 x IΔn (Uf) / 0.5 x IΔn / 2 x IΔn (selective) / 5 x IΔn Pulse: 0 to 500 ms / 0.1 and 1 ms / 2 ms, Ramp mode: 0 to 200 ms / 0.1 ms / 2 ms |
B-Type RCDs | |
Installation Voltage / Frequency | 90 V to 275 V / 15.8 Hz to 17.5 Hz and 45 Hz to 65 Hz |
IΔn: ramp / pulse 2 x IΔn pulse 4 x IΔn |
10/30/100/300/500 mA 10/30/100 mA with pulse 4 IΔn Duration: 150 ms with 4 x IΔn or 300 ms with 2 x IΔn |
Test in Ramp Mode | 0.2 x IΔn to 2.2 x IΔn |
Trip test: 2 x IΔn 4 x IΔn |
IΔN ≤ 200 mA: 2.2 x 2 x IΔn IΔN > 200 mA: 1.1 x 2 x IΔn IΔN ≤ 100 mA: 2.2 x 4 IΔN |
Other Measurements | |
Current by Clamps C177/C177A | 5.0 mA to 199.9 A (C177A) |
Current by Clamp MN77 | 1 mA*) 5.0 mA to 19.99 A |
Voltage | 0 to 550 VAC/DC / DC and 15.8 to 500 Hz |
Frequency | 10 to 500 Hz |
Phase Rotation | 20 to 500 VAC |
Active Power | 0 to 110 kW single-phase - 0 to 330 kW three-phase Simultaneous display of voltage and current waveforms |
Harmonics | Voltage and current / up to 50th order / THD-F /THD-R |
General Specifications | |
Display | Large 5.7” backlit graphic colour LCD screen, 320 x 240 points |
Storage/Communication | via USB for data transfer and report creation |
Power Supply: Rechargeable Battery | Lithium-ion 10.8 V rated 5.8 Ah |
Battery Life | up to 30 hours |
Dimensions/Weight | 280 x 190 x 128 mm / 2.2 kg |
Protection | IP 53 / IK04 |
EMC | IEC 61326-1 |
Electrical Safety | IEC 61010 -1 – 600 V CAT III – 300 V CAT IV – IEC 61557 |