This promotional kit is available for a limited time only and includes Fluke’s 1664 FC Multifunction Installation Tester and Fluke T6-1000 PRO Electrical Tester, both with standard accessories.
The Fluke 1664 FC Multifunction Tester & T6-1000 PRO Electrical Tester Kit delivers a powerful combination for electricians who need advanced installation testing alongside everyday troubleshooting capability.
The Fluke 1664 FC includes Auto Test and Insulation PreTest functions, memory storage, and USB download. It is also EVSE test compliant and wirelessly compatible with Fluke Connect.
The Fluke T6-1000 PRO Electrical Tester is an open-fork meter with FieldSense technology. It permits non-contact measurement of AC voltage, current, and frequency, measuring up to 1000V and 200A with True RMS accuracy.
For further information, please visit our 1664 FC Multifunction Installation Tester and T6-1000 PRO Electrical Tester listings.
Call 01642 931 329 or complete the form:
| AC/DC Voltage (TRMS) | ||||
|---|---|---|---|---|
| Range | Resolution | Input Impedance | Overload Protection | |
| 500V | 0.1V | 3.3MΩ | 660V rms | |
| Continuity Testing (Rlo) | ||||
| Range (Autoranging) | Resolution | Open Circuit Voltage | ||
| 20Ω | 0.01Ω | >4V | ||
| 200Ω | 0.1Ω | |||
| 2000Ω | 1Ω | |||
| Insulation Resistance Measurement (Riso) | ||||
| Model Number | Test Voltages | |||
| 1662 | 100, 250, 500 and 1000V | |||
| 1663/1664 FC | 50, 100, 250, 500 and 1000V | |||
| Test Voltage | Insulation Resistance Range | Resolution | Test Current | |
| 50V | 20MΩ/50MΩ | 0.01MΩ/0.1MΩ | 1mA @ 50kΩ | |
| 100V |
20MΩ/100MΩ |
0.01MΩ/0.1MΩ | 1mA @ 100kΩ | |
| 250V | 20MΩ/200MΩ | 0.01MΩ/0.1MΩ | 1mA @ 250kΩ | |
| 500V | 20MΩ/200MΩ/500MΩ | 0.01MΩ/0.1MΩ/1MΩ | 1mA @ 500kΩ | |
| 1000V | 20MΩ/200MΩ/1000MΩ | 0.01MΩ/0.1MΩ/1MΩ | 1mA @ 1MΩ | |
| Insulation Pretest | ||||
| Insulation Safety Pretest | Requires the unit to be connected to L, N and PE | |||
| Loop and Line Impedance (Zi) | ||||
| Range | Resolution | |||
| 10Ω (Hi current mΩ mode) 20Ω/200Ω/2000Ω | 1mΩ / 0.01Ω / 0.1Ω / 1Ω | |||
| RCD Testing | ||||
| Model Number | Types Tested | |||
| 1662 | AC, G, S, A/F | |||
| 1663/1664 FC | A/F, AC, B/B+, G and S | |||
| RCD Trip Time Test (ΔT) | ||||
| Current Range | Step Size | Dwell Time | Measurement Accuracy | |
| Type G | Type S | |||
| 30 to 110% of RCD Rated Current | 10% of index IΔN | 300ms/step | 500ms/step | ±5% |
| Notes 30 % to 210 % for Type A IΔN = 10mA 20 % to 210 % for Type B |
Specified trip current ranges (EN 61008-1): 50 % to 100 % for Type AC 35 % to 140 % for Type A (>10 mA) 35 % to 200 % for Type A (≤10 mA) 50 % to 200 % for Type B |
|||
| Earth Resistance Test (RE) - Only Available On 1664 FC and 1663 | ||||
| Range | Resolution | Frequency | Output Voltage | |
| 200Ω | 0.1Ω | 128Hz | 25V | |
| 2000Ω | 1Ω | 128Hz | 25V | |
| Phase Sequence Indication | ||||
| Icon | Range | Display | ||
| Shows icon when active | 100 to 500V | 1-2-3 or 3-2-1 | ||
| General Specifications | ||||
| Dimensions | 10cm (L) x 25cm (W) x 12.5cm (H) | |||
| Weight (Including Batteries) | Approx 1.3kg | |||
| Battery Size | 1.5V type AA (IEC LR6) x 6 | |||
| Sealing | IP40 | |||
| Safety | Complies with IEC/EN61010-1, UL61010, ANSI/ISA - s82.02.01 and CAN/CSA c22.2 No. 1010 | |||
| Overvoltage | CAT III 500V, CAT IV 300V | |||
| Performance | EC/EN61557-1 to IEC/EN61557-7 and IEC/EN61557-10 | |||
| Function | ||
|---|---|---|
| FieldSense ac voltage | Requires test leads | No |
| Range | 1000 V | |
| Resolution | 1 V | |
| Accuracy | ±(3 % + 3 counts) 45 Hz - 66 Hz[1] [2] | |
| FieldSense ac current | Requires test leads | No |
| Range | 200.0 A | |
| Resolution | 0.1 A | |
| Accuracy | ±(3 % + 3 counts) 45 Hz - 66 Hz | |
| FieldSense frequency (Hz) | Requires test leads | No |
| Range | 45 Hz – 66 Hz | |
| Resolution | 1 Hz | |
| Accuracy | ±(1 % + 2 counts) | |
| Volts ac | Requires test leads | Yes |
| Range | 1000 V | |
| Resolution | 1 V | |
| Accuracy | ±(1.5 % + 2 counts) 45 Hz - 66 Hz | |
| Volts dc | Requires test leads | Yes |
| Range | 1000 V | |
| Resolution | 1 V | |
| Accuracy | ±(1 % + 2 counts) | |
| Resistance | Requires test leads (all ranges) | Yes |
| Range | 2000 Ω | |
| Resolution | 1 Ω | |
| Range | 20.00 kΩ | |
| Resolution | 0.01 kΩ | |
| Range | 100.0 kΩ | |
| Resolution | 0.1 kΩ | |
| Accuracy (all ranges) | ±(1 % + 2 counts) | |
| Notes | Accuracy[1]: ± ( [ % of reading] + [number of least significant digits] ). Accuracy is specified for 1 year after calibration, at 18 °C to 28 °C (64 °F to 82 °F) with relative humidity to 90 %. AC conversions are ac-coupled, RMS responding. | |
| Accuracy[2]: FieldSense specified from 16V to 1000V. | ||
| General | ||
| Calibration | 1-year calibration cycle | |
| Dimensions | 61 mm x 259 mm x 43 mm | |
| Weight | 0.35 kg (0.78 lb) | |
| Fork opening | 17.8 mm (0.7”) | |
| Temperature | Operating | -10 °C to +50 °C (14 °F to 122 °F) |
| Storage | -30 °C to +60 °C (-22 °F to +140 °F) | |
| Altitude | Operating | 2,000 m (6,562 feet) |
| Storage | 10,000 m (32,808 feet) | |
| Relative Humidity | 0 % to 90 %, 5 °C to 30 °C (41 °F to 86 °F) | |
| 0 % to 75 %, 30°C to 40 °C (86 °F to 104 °F) | ||
| 0 % to 45 %, 40°C to 50 °C (104 °F to 122 °F) | ||
| Battery | Type | 2x AA (IEC LR6) |
| Life | 360 hour continuous, typical is 200 hour using the FieldSense function | |
| Temperature coefficient | 0.1 x (specified accuracy) / °C for <18°C or >28 °C (< 64.4 °F or > 82.4 °F) | |
| Safety | General | IEC 61010-1: Pollution Degree 2 |
| Measurement T6-1000 PRO | IEC 61010-2-032: CAT IV 600 V / CAT III 1000 V | |
| Electromagnetic Compatibility | IEC/EN 61326-1: Portable | |