The Fluke 1673 FC Multifunction Tester & 115 Digital Multimeter Kit combines a mid-range multifunction tester with a true-RMS multimeter.
The Fluke 1673 FC tests standard electrical installations and electric vehicle charging stations. With features like automatic measurement validation, voltage drop tests, and dedicated EV testing, the 1673 FC can reduce testing time by up to 30%. Compatible with Fluke Connect and TruTest Software.
The Fluke 115 Digital Multimeter provides reliable readings of AC/DC voltage, current, resistance, continuity, frequency, capacitance, and diode function. True-RMS measurement and a LoZ mode provide accurate results even in challenging environments. Together with the 1673 FC, it forms a comprehensive toolkit for electricians who need both speed and precision.
For further information, please visit our 1673 FC Multifunction Tester and 115 Digital Multimeter listings.
We’ve already dropped this to our lowest Black Friday price! If you find it cheaper anywhere else, just let us know.
Buy a Fluke and Get a Free Fluke! Spend over £150 on a qualifying Fluke product and choose an additional Fluke product for Free. Offer is claimed directly from Fluke. Valid 15th Sept 25 - 31 Dec 2025. For more details visit buy a fluke offer.
Get a free gift this Black Friday! Even better, this bonus stacks with any other offer.
Free item will automatically add to your basket. Limited Stock. Offer is based on ex VAT basket total after discounts and before shipping costs. See Black Friday Offers for details.
| Full-colour touch screen | ✔ |
|---|---|
| Insulation at L-N, L-PE, N-PE inputs | ✔ |
| Auto Test sequence | ✔ |
| Auto pass/fail results | ✔ |
| Continuity at L-N, L-PE, N-PE inputs | ✔ |
| Test smooth DC sensitive RCDs (Type B/B+) | ✔ |
| Earth resistance | ✔ |
| Voltage AC, DC, and frequency | ✔ |
| Wiring polarity checker, detects broken PE and N wires | ✔ |
| Insulation resistance | ✔ |
| Continuity and resistance | ✔ |
| Measure motor windings with continuity test (@ 10 mA) | ✔ |
| Loop and line impedance | ✔ |
| Prospective Earth Fault Current (PEFC/IK) | ✔ |
| Prospective Short-Circuit Current (PSC/IK) | ✔ |
| RCD trip time | ✔ |
| RCD trip current (ramp test) | ✔ |
| Measures trip time and current for RCD type AC, A, and F in one test |
✔ |
| RCD variable test current | ✔ |
| Automatic RCD test sequence | ✔ |
| Phase sequence test | ✔ |
| Voltage drop measurement | ✔ |
| Other Features | |
| Fluke Connect compatibility | ✔ |
| Fluke Cloud storage | ✔ |
| On/Off switchable Auto Start for continuity, RCD, and loop test |
✔ |
| Illuminated display | ✔ |
| Memory, Interface | |
| Z Max memory | ✔ |
| Memory | ✔ |
| USB-C and BLE interface | USB-C/BLE |
| General Specifications | |
| Size | 26.25 cm x 14.19 cm x 11.93 cm (10.3 in x 5.6 in x 4.7 in) |
| Weight (incl. batteries) | 1.6 kg (3.5 lb) |
| Battery size, quantity | BP290, Li-ion, 10.8 V, 2500 mAh, 27 Wh |
| Ingress Protection | IEC 60529: IP40 |
| Safety | Complies with IEC/EN 61010-1, IEC 61010-2-030, IEC 61010-2-03 |
| Safety rating | CAT III 600 V, CAT IV 300 V |
| Performance | IEC 61557-1 to IEC/EN 61557-8 and IEC 61557-10 |
| Maximum Voltage Between any Terminal and Earth Ground | 600 V | |
| Surge Protection | 6 kV peak per IEC 61010-1 600 VCAT III, Pollution Degree 2 | |
| Display | Digital:6,000 counts, updates 4 per second | |
| Bar Graph | 33 segments, updates 32 per second | |
| Operating Temperature | -10 °C to + 50 °C | |
| Storage Temperature | -40 °C to + 60 °C | |
| Battery Type | 9 volt Alkaline, NEDA 1604A/ IEC 6LR61 | |
| Battery Life | 400 hours typical, without backlight | |
| Accuracy | ||
| DC millivolts | Range: | 600.0 mV |
| Resolution: | 0.1 mV | |
| Accuracy: | ± ([% of reading] + [counts]): 0.5% + 2 | |
| DC volts | Range/Resolution: | 6.000 V / 0.001 V |
| Range/Resolution: | 60.00 V / 0.01 V | |
| Range/Resolution: | 600.00 V / 0.1 V | |
| Accuracy: | ± ([% of reading] + [counts]): 0.5% + 2 | |
| AC millivolts 1 true-rms | Range: | 600.0 mV |
| Resolution: | 0.1 mV | |
| Accuracy: | 1.0 % + 3 (dc, 45 Hz to 500 Hz)2.0 % + 3 (500 Hz to 1 kHz) | |
| AC volts 1 true-rms | Range/Resolution: | 6.000 V / 0.001 V |
| Range/Resolution: | 60.00 V / 0.01 V | |
| Range/Resolution: | 600.0 V / 0.1 V | |
| Accuracy: | 1.0 % + 3 (dc, 45 Hz to 500 Hz)2.0 % + 3 (500 Hz to 1 kHz) | |
| Continuity | Range: | 600 Ω |
| Resolution: | 1 Ω | |
| Accuracy: | Beeper on < 20 Ω, off > 250 Ω; detects opens or shorts of 500 μs or longer. | |
| Ohms | Range/Resolution: | 600.0 Ω / 0.1 Ω |
| Range/Resolution: | 6.000 kΩ / 0.001 kΩ | |
| Range/Resolution: | 60.00 kΩ / 0.01 kΩ | |
| Range/Resolution: | 600.0 kΩ / 0.1 kΩ | |
| Range/Resolution: | 6.000 MΩ / 0.001 MΩ | |
| Accuracy: | 0.9 % + 1 | |
| Range/Resolution: | 40.00 MΩ / 0.01 MΩ | |
| Accuracy: | 5 % + 2 | |
| Diode Test | Range/Resolution: | 2.00 V / 0.001 V |
| Accuracy: | 0.9% + 2 | |
| Capacitance | Range/Resolution: | 1000 nF / 1 nF |
| Range/Resolution: | 10.00 µF / 0.01 µF | |
| Range/Resolution: | 100.0 µF / 0.1 µF | |
| Range/Resolution: | 9999 µF / 1 µF | |
| Range/Resolution: | 100 µF to 1000 µF | |
| Accuracy: | 1.9% + 2 | |
| Range/Resolution: | > 1000 µF | |
| Accuracy: | 5% + 20% | |
| Lo-Z Capacitance | Range: | 1 nF to 500 µF |
| Accuracy: | 10% + 2 typical | |
| AC amps true-rms (45 Hz to 500Hz) | Range/Resolution: | 6.000 A / 0.001 A |
| Range/Resolution: | 10.00 A / 0.01 A | |
| Accuracy: | 1.5% + 3 | |
| 20 A overload for 30-seconds max | ||
| DC amps | Range/Resolution: | 6.000 A / 0.001 A |
| Range/Resolution: | 10.00 A / 0.01 A | |
| Accuracy: | 1.0% + 3 | |
| 20 A overload for 30-seconds max | ||
| Hz (V or A input) 2 | Range/Resolution: | 99.99 Hz / 0.01 Hz |
| Range/Resolution: | 999.9 Hz / 0.01 Hz | |
| Range/Resolution: | 9.999 kHz / 0.001 kHz | |
| Range/Resolution: | 50 kHz / 0.01 kHz | |
| Accuracy: | 0.1% + 2 | |
| Mechanical & General | ||
| Size | 167 x 84 x 46 mm (6.57" x 3.31" x 1.82") | |
| Weight | 550 g | |