The HVPD PDS Insight™ 2 Portable On-line PD Detector is a lightweight, simple-to-use handheld partial discharge detector with an LCD. It can be used to test switchgear, cables and transformers reliably and safely and is ideal for applications such as condition-based maintenance and substation access safety.
Accurate, dependable measurements are made possible by the HVPD PDS Insight™ 2 Portable On-line PD Detector’s Phase Resolved Partial Discharge (PRPD) feature which eliminates background noise from true partial discharge sources. The HVPD PDS Insight™ 2 Portable On-line PD Detector is also equipped with a function checker, in-built TEV & AA sensors, an external AA sensor input, and internal data storage. Results can be transferred via Bluetooth to a PC or tablet (NOT included) for analysis, benchmarking and trending using HVPD’s OLPD Manager for Windows Software or OLPD Manager™ App (NOT included).
In addition to this, the HVPD PDS Insight™ 2 Portable On-line PD Detector is compatible with an HFCT sensor and, to this end, features an external HFCT sensor connection. It is supplied with headphones and a docking station.
The HVPD PDS Insight™ 2 Portable On-line PD Detector is an easy-to-use, ergonomic and effective meter that can be used to prevent in-service failures and expensive, unplanned outages.
Please note that this model is NOT supplied with a tablet.
Get a free gift this Black! Even better, this bonus stacks with any other offer.
Free item will automatically add to your basket. Limited Stock. Offer is based on ex VAT basket total after discounts and before shipping costs. See Black Friday Offers for details.
Remember: We will not be beaten on price. Contact us if you've seen a cheaper price.
| TEV Sensor | |
| Measurement Range (Peak) | 0-70 dbmV |
| Measurement Range (Cumulative Activity) | 0 - 350,000 mV/cycle |
| Frequency Response | 5 - 60 MHz |
| Resolution | 1 dB |
| Accuracy | ±1 dB |
| HFCT Sensor | |
| Measurement Range (HFCT 100/50, Ztr=3.9) | 100pC - 100nC |
| Measurement Range (Cumulative Activity) | 200 pC/cycle - 20,000 nC/cycle |
| Frequency Response (-3 dB response) | 100 kHz - 20 MHz |
| Resolution | 1 dB |
| Accuracy | ±1 dB |
| AA Sensor | |
| Measurement Range | 0 - 70 dBμV |
| Centre Frequency | 40 kHz |
| Resolution | 1 dB |
| Accuracy | ±1 dB |
| Gain Stages | 1 |
| Phase Resolved PD (PRPD) | |
| Synchronisation Methods | Optical/ Mains Field Detector/ BNC input (selectable) |
| PRPD Plot Types | 2D & 3D |
| Hardware | |
| Enclosure | Polycarbonate ABS/ TPE |
| Display | 3.5” 320 x 240 65k colour LCD |
| Control | 5 button membrane keypad |
| I/O Connections | BNC (HFCT), LEMO (external AA) USB Micro B (charger), 3.5mm Jack (headphones) |
| Operating Environment | |
| IP Classification | IP54 |
| Temperature | -20°C to +55°C |
| Humidity | 0 - 90% RH non - condensing |
| Power | |
| Internal Battery | Lithium-ion, 3.7 V, 4.5 Ah |
| Operating Time | Approx. 8 hours |
| Charge Time from Empty | Approx. 4 hours |
| Battery Charger | |
| Input (Vin) | 90 - 264 V, AC, 50/60Hz, max: 0.5A |
| Output (Vout) | 5 V DC (USB 1x 1A, 1x 2A) |
| Country Adapters | UK, EU, AU, USA |
| Operating Temperature | 0°C to 40°C |
| Humidity | 10 - 90% RH non- condensing |
| OLPD Manager™ Application | |
| Operating System | Android™ (tablet) and Windows ® 7/8/10 (PC) |
| Functionality | Bluetooth ® synchronisation with PDS Insight ™ (tablet) USB synchronisation with PDS Insight (PC), associate POA barcodes to physical plant |
| Results Display | Graphical representation of PD levels in the substation, trending graphs, summary tables, PRPD patterns |
| Report Format | Microsoft Excel |
| Microsoft Excel | Yes |