The EVX100 and MFT-X1 form a comprehensive testing kit for automated diagnostics of single- and three-phase Mode 3 AC electric vehicle charging stations (EVSE). Eliminating the need for manual adaptors or control boxes, the MFT-X1 instantly recognises the EVX100 and provides all necessary testing functions without manual intervention.
The Megger MFT-X1 Multifunction Tester is designed for CAT IV 300V applications, marking Megger’s initial foray into platform-based multifunction testers. It is ideal for testing single-phase and three-phase electrical installations in domestic, commercial, and industrial environments. The tester offers a wide range of tests, enabling in-depth fault diagnostics and fulfilling all commissioning, maintenance, routine checks, and certification needs.
For more information please visit the Megger MFT-X1 Multifunction Tester.
The EVX100 is a fully integrated add-on for the MFT-X1, offering an automated testing interface for single- and three-phase Mode 3 AC electric vehicle charging stations (EVSE). This setup removes the necessity for a conventional remote manual adaptor or control box. Upon connection, the MFT-X1 instantly detects the EVX100 and presents the necessary testing functions without requiring manual input.
For more information please visit the Megger EVX100 Electric Vehicle Charge-Point Adaptor.
Get a free gift this Black! Even better, this bonus stacks with any other offer.
Free item will automatically add to your basket. Limited Stock. Offer is based on ex VAT basket total after discounts and before shipping costs. See Black Friday Offers for details.
Remember: We will not be beaten on price. Contact us if you've seen a cheaper price.
| Voltage Measurement | |
|---|---|
| Voltage range | 0.001 V to 2 V (mV range) 2 V to 600 V (V range), 1000 V DC (on-CAT rated circuits) |
| Voltage type | Trms, AC, DC |
| Phase sequence | Automatic phase sequence testing on detection of valid three-phase supplies |
| Current Measurement (non-contact) | |
| AC Trms | Using optional accessories: MCC1010 current clamp |
| Measurement Range | MCC1010: 1 mA to 300 A |
| Continuity/Resistance | |
| Measurement range Digital display | 0.01 Ω to 999 kΩ Auto-ranging |
| Measurement Range Analogue arc | 0 Ω to 1 MΩ log scale |
| Test voltage | 4 V DC to 5 V DC |
| Test current (Nominal) | >200 mA 0 Ω >< 2 Ω 10 mA Auto reduction on high resistance (actual current reported in the display) |
| Test polarities | Forward polarity |
| Buzzer resistance range | > 0.01 Ω < 2 kΩ |
| Buzzer threshold | 0.3, 0.5, 1, 2, 3, 4, 5, 10, 20, 30, 40, 50, 100, 200 Ω |
| Insulation Testing | |
| Measurement range Digital display | 0.001 MΩ to 999 MΩ Auto-ranging |
| Measurement range Analogue arc | 0.001 MΩ to >1000 MΩ log scale |
| Insulation test voltages | 50 V DC to 1000 V DC + Variable 50 V to 999 V |
| Test current | 1 mA to 2 mA |
| Stabilised output voltage | Output test voltage stabilised to -0% +2% +2 V |
| Loop Impedance Testing | |
| 2-Wire – all modes | |
| Test types | Mode 1: Non-Trip |
| Mode 2: High current | |
| Mode 3: High resolution | |
| Resolution | Non-Trip: 0.01 Ω |
| High current: 0.01 Ω | |
| High resolution: 0.001 Ω | |
| Voltage range | Non-trip: 48 V AC to 280 V AC |
| High current: 48 V AC to 550V AC | |
| High resolution: 48 V AC to 550 V AC | |
| Frequency range | 45 Hz to 65 Hz (all modes) |
| Phases | Non-trip: Single phase |
| High current: Three-phase | |
| High resolution: Three-phase | |
| 3-Wire - Non-trip | |
| Test types | RCD (non-trip) RCD EV (non-trip on 6mA EV RDCs) |
| Resolution | 0.01 Ω |
| Voltage range | 48 V AC to 280 V |
| Frequency range | 45 Hz to 65 Hz |
| Phases | Single phase |
| Volt Drop | |
| Volt drop calculation | Requires Zref (Ze) and circuit current (I-vdrop) |
| Accuracy | Dependent on loop impedance accuracy |
| RCD Testing | |
| RCD types supported | Type AC, A, B, AC(S), A(S), B(S) |
| Auto RCD sequence | 1/2x I∆n, 1x I∆n, 2x I∆n, 5x I∆n, Ramp, 0º/180º (customer configurable) |
| Ramp testing | 10 mA to 1000 mA |
| RDC testing | 6 mA RDC |
| Fault (Touch) voltage | 0 V to 253 V |
| Earth Testing | |
| 2-wire | 2-wire earth resistance test |
| Power Supply | Internal battery: Li-ion 3180 mAh |
|---|---|
| Recharging | Type C USB (required supply is 5 V, 1 A maximum) |
| Charging Status | LED |
| Input Voltage | 230 V AC nominal max 253 V AC 400 V AC nominal max 440 V AC |
| Input Frequency | 50/60 Hz |
| CP State Verification | A1, A2, B1, B2, C1, C2, E, F |
| Connection Options | Fixed Type 2: IEC 62196-1 |
| Safety | IEC61010-1:2010 61010-031:2015, CAT II 250 V |
| Temperature Range | Working: -10 °C to +55 °C Storage: -25 °C to +70 °C |
| Humidity Range | 90% R.H at +40 °C max |
| Ingress Protection | IEC 660529: IP 54 - protected against dust and water splashes; suitable for indoor and outdoor use |
| Vibration | MIL-PRF-28800F: Class 2 |
| Maximum Operating Altitude | 2000 m |
| Pollution Degree | 2 |
| Mechanical | EVX Case Dimensions: 133.5 x 115 x 56 mm (5.2 x 4.5 x 2.2 inches) excl. cable |
| Unpackaged Weight | 976 g |
| Packaged Dimensions | 350 x 280 x 75 mm (13.8 x 11.02 x 2.96 inches) |
| Packaged Weight | 1580 g |
| Cable Length | 2 m |