The Metrel A1422 Active 3-Phase Adapter can be used to troubleshoot and test three-phase appliances, machinery and RCDs. It is designed for use with Metrel’s MI3321 MultiservicerXA, MI3360 OmegaGT PAT Tester and MI3310/ MI3310 25A SigmaGT PAT Testers and will automatically recognise the connected instrument.
When used with the aforementioned machine testers and PAT testers the Metrel A1422 Active 3-Phase Adapter can perform functional tests on equipment up to 40A. For an overview of the Metrel A1422 Active 3-Phase Adapter’s testing capabilities when used with MI 3310 PAT Testers or MI3321 MultiservicerXA, please see the following table.
| Tests/ Functions | MI3310/MI3310A | MI3321 |
| Earth bond/continuity resistance | ✔ | ✔ |
| Continuity (single / auto) | ✘ | ✔ |
| Insulation resistance | ✔ | ✔ |
| Insulation resistance-s | ✔ | ✔ |
| High voltage test | ✘ | ✔ |
| Loop impedance and prospective fault current | ✘ | ✔ |
| Discharging time | ✘ | ✔ |
| Voltage, frequency, three-phase rotary field | ✘ | ✔ |
| Substitute leakage current | ✔ | ✔ |
| Substitute leakage – s | ✔ | ✔ |
| Differential leakage current | ✔ | ✔ |
| 3-phase differential leakage current | ✔ | ✔ |
| Touch leakage current | ✔ | ✔ |
| Polarity test | ✔ | ✔ |
| Active polarity test | ✔ | ✔ |
| 3-phase polarity test / 3-phase active polarity test | ✔ | ✔ |
| Clamp current test | ✔ | ✔ |
| P/RCD test | ✔ | ✔ |
| 3-phase P/RCD test | ✔ | ✔ |
| Power / functional test | ✔ | ✔ |
| 3-phase power / functional test | ✔ | ✔ |
| Continuity test (according to IEC/ EN 60974-4) | ✔ | ✔ |
| Insulation resistance (according to IEC/ EN 60974-4) | ✔ | ✔ |
| Leakage current (according to IEC/ EN 60974-4) | ✔ | ✔ |
| No load voltage (according to IEC/ EN 60974-4) | ✔ | ✔ |
Additionally, the Metrel A1422 Active 3-Phase Adapter features several built-in socket-outlets enabling the testing of industrial extension leads, including those that are RCD protected. It is also able to test ARC Welding Equipment in accordance with EN 60974-4 and VDE 0544-4 and can perform open-circuit voltage tests at ARC welding units in accordance with these standards.
The Metrel A1422 Active 3-Phase Adapter is also capable of performing the following tests on three-phase equipment:
Its comprehensive testing capabilities make the Metrel A1422 Active 3-Phase Adapter suitable for advanced applications and enable it to test single- and three-phase ARC welding equipment, as well as carry out professional checks/ inspections on three-phase portable appliances and three-phase machines.
Its test procedures are identical to those used to check single-phase equipment: the sequences for three-phase test procedures are automatically set based on entered test codes and input voltages, again adding to the Metrel A1422 Active 3-Phase Adapter’s ease of operation.
Finally, the Metrel A1422 Active 3-Phase Adapter is supplied in a robust, waterproof case with all the accessories required to perform the aforementioned tests.
The Metrel A1422 Active 3-Phase Adapter is a complete, easy-to-use and versatile machine testing and PAT testing adapter. It is ideal for advanced, professional three-phase testing and troubleshooting applications.
| Industrial Systems | Switchboards / Controlgears |
| Machines / Power Loads | |
| Electrical Equipment / Appliances | |
| Working Places Health / Safety Care | |
| 3-phase system testing | |
| Special Installations/ Locations | Construction Sites |
| Ships / Boats / Marina Places | |
| Welding equipment testing | |
| Service / Repair / Rental Offices | |
| Buildings Facility Management | Portable Appliances / Fixed Wiring |
Get a free gift this Black! Even better, this bonus stacks with any other offer.
Free item will automatically add to your basket. Limited Stock. Offer is based on ex VAT basket total after discounts and before shipping costs. See Black Friday Offers for details.
Remember: We will not be beaten on price. Contact us if you've seen a cheaper price.
| Range | Resolution | Accuracy |
| Differential leakage current (230/400 VAC or 120/208 VAC) - Differential leakage current readout | ||
| 0.00 mA ÷ 9.99 mA | 0.01 mA | ±(5 % of reading + 5 digits) |
| Power / Functional test (230/400 VAC or 120/208 VAC) - Apparent power readout | ||
| 0.00 kVA ÷ 24.00 kVA | 0.01 kVA | ±(5 % of reading + 5 digits) |
| Active power readout | ||
| 0.00 kW ÷ 24.00 kW | 0.01 kW | ±(5 % of reading + 5 digits) |
| Reactive power readout | ||
| 0.00 kW ÷ 24.00 kVAr | 0.01 kVAr | ±(5 % of reading + 5 digits) |
| Power factor readout | ||
| 0.00 ÷ 1.00 | 0.01 | ±(5 % of reading + 5 digits) |
| 3-phase RCD / Test current (10 mA, 15 mA, 30 mA, 100 mA, 300 mA) - Portable RCD trip-out time readout (AC and A type PRCD) | ||
| 0 ms ÷ 300 ms (½ x I∆N, I∆N ) | 1 ms | ±3 ms |
| 0 ms ÷ 150 ms (2 x I∆N | 1 ms | |
| 0 ms ÷ 40 ms (5 x I∆N) | 1 ms | |
| Portable RCD trip-out current readout (B type PRCD) | ||
| 0.2 x I∆N ÷ 2.2 x I∆N | 0.05 x I∆N | ±0.1 x I∆N |
| Continuity of the protective circuit (according to IEC/ EN 60974-4) - Test current set to 10 A | ||
| 0.00 Ω ÷ 1.99 Ω | 0.01 Ω | ±(5 % of reading + 3 digits) |
| 2.00 Ω ÷ 19.99 Ω | 0.01 Ω | ±10 % |
| Test current set to 200 mA | ||
| 0.00 Ω ÷ 1.99 Ω | 0.01 Ω | ±(5 % of reading + 3 digits) |
| 2.00 Ω ÷ 9.99 Ω | 0.01 Ω | ±10 % |
| 10.0 Ω ÷ 19.9 Ω | 0.1 Ω | |
| Insulation resistance (supply circuit to protective circuit); (welding circuit to protective circuit); (Insulation resistance supply circuit to welding circuit; (according to IEC/ EN 60974-4) - Insulation LN-PE readout; W-PE readout; LN-W readout: | ||
| 0.000 MΩ ÷ 0.500 MΩ | 0.001 MΩ | ±(10 % of reading + 5 digits) |
| 0.501 MΩ ÷ 1.999 MΩ | 0.001 MΩ | ±(5 % of reading + 3 digits) |
| 2.00 MΩ ÷ 19.99 MΩ | 0.01 MΩ | |
| 20.0 MΩ ÷ 199.9 MΩ | 0.1 MΩ | |
| Insulation resistance (supply circuit of class II equipment to accessible surfaces) (according to IEC/ EN 60974-4) - Insulation LN-P readout: | ||
| 0.000 MΩ ÷ 0.500 MΩ | 0.001 MΩ | ±(10 % of reading + 5 digits) |
| 0.501 MΩ ÷ 1.999 MΩ | 0.001 MΩ | ±(5 % of reading + 3 digits) |
| 2.00 MΩ ÷ 19.99 MΩ | 0.01 MΩ | |
| Welding circuit leakage current; Primary leakage current (according to IEC/ EN 60974-4) - Welding circuit leakage current readout; Primary leakage current readout: | ||
| 0.00 mA ÷ 14.99 mA | 0.01 mA | ±(5 % of reading + 5 digits) |
| No load voltage (acc. to IEC/ EN 60974-4) - No load voltage readout: (AC peak or DC peak) | ||
| 0.0 V ÷ 199.9 V | 0.1 V | ±(5 % of reading + 5 digits) |
| No load voltage readout: (AC RMS) | ||
| 0.0 V ÷ 139.9 V | 0.1 V | ±(5 % of reading + 5 digits) |
| Notes | Polarity test Standard test (<60 VAC and DC) | |
| Polarity test Active (Mains supply voltage, over-current protection) | ||
| General Specifications | ||
| Supply voltage 1-phase | 230 V ±10 % | |
| Supply voltage 3-phase | 230/400 V ±10 % | |
| 120/208 V ±10 % | ||
| Maximum test current | 32 A, 40 A max (10 min) | |
| Overvoltage category | CAT II / 300 V | |
| Protection classification | I | |
| Pollution degree | 2 | |
| Protection degree | IP 65 (closed and locked cover | |
| IP 20 (connectors) | ||
| Case | Shockproof plastic, portable | |
| Dimensions (w x h x l) | 335 x 160 x 335 mm | |
| Weight | 7.2 kg | |
| Working temperature range | 0 °C ÷ 40 °C | |
| Maximum relative humidity | 85 %RH (0 °C ÷ 40 °C) | |