The lightweight Metrel MI 3309 DeltaGT BT PAT Tester is capable of conducting a wide range of electrical tests which make it a perfect instrument for high volume safety testing of portable appliances.
Reading of results, indications, measurement parameters and messages is made easy thanks to the large graphic LCD screen, which is backlit for use in dimly lit conditions.
The two lights on either side of this tester provide additional PASS/FAIL indication and the inbuilt battery recharger means there is no need to spend extra money on an external charger.
The powerful inbuilt memory can store up to 1500 sets of test data and it is fully compatible with the new Metrel PATLink PRO PC software package which lets you download, view, analyse, print and export test results. It is also compatible with the Metrel app: aPAT link.
FREE Manufacturer's Calibration / Conformity Certificate included - We recommend adding a new Calibration Certificate to ensure your Tester is calibrated and accurate from the date of purchase, not date of manufacture.
Please Note - If you require the certificate in any particular company or individual name please email us the details that you want to appear on the certificate rather than adding a note to your order as it may be missed by our automated system, feel free to contact one of our advisors if you want to discuss any aspect of this service 01642 626140.
Get a free gift this Black! Even better, this bonus stacks with any other offer.
Free item will automatically add to your basket. Limited Stock. Offer is based on ex VAT basket total after discounts and before shipping costs. See Black Friday Offers for details.
Remember: We will not be beaten on price. Contact us if you've seen a cheaper price.
| Earth continuity (200 mA in to 2.00 Ω) | ||
| Range | Resolution | Accuracy |
| 0.00 Ω ÷ 19.99 Ω | 0.01 Ω | ± (5 % of reading + 3 digits) |
| 20.0 Ω ÷ 199.9 Ω | 0.1 Ω | Indication only |
| 200 Ω ÷ 1999 Ω | 1 Ω | Indication only |
| Insulation resistance, Insulation – S resistance (250 VDC, 500 VDC) | ||
| Range | Resolution | Accuracy |
| 0.00 MΩ ÷ 19.99 MΩ | 0.01 Ω | ± (5 % of reading + 3 digits) |
| 20.0 MΩ ÷ 49.9 MΩ | 0.1 Ω | ± (5 % of reading + 3 digits) |
| 50.0 MΩ ÷ 199.9 MΩ | 0.1 Ω | Indication only |
| Differential leakage current (230 VAC) | ||
| Range | Resolution | Accuracy |
| 0.00 MA ÷ 19.99 MA | 0.01 Ω | ± (5 % of reading + 3 digits) |
| Touch leakage current (230 VAC) | ||
| Range | Resolution | Accuracy |
| 0.00 mA ÷ 7.0 mA | 0.01 Ω | ± (10 % of reading + 5 digits) |
| Substitute leakage current (30 VAC) | ||
| Range | Resolution | Accuracy |
| 0.00 mA ÷ 9.99 mA | 0.01 Ω | ± (5 % of reading + 3 digits) |
| 10.0 mA ÷ 20.0 mA | 0.1 mA | ± (5 % of reading + 3 digits) |
| (P)RCD testing (10 mA, 15 mA, 30 mA) | ||
| Range | Resolution | Accuracy |
| 0 ms ÷ 300 ms (½xI∆N) | 0.1 ms | ±3 ms |
| 0 ms ÷ 300 ms (I∆N) | 0.1 ms | ±3 ms |
| 0 ms ÷ 40 ms (5xI∆N) | 0.1 ms | ±1 ms |
| Power measurement (230 VAC) | ||
| Range | Resolution | Accuracy |
| 0.00 kVA ÷ 4.00 kVA | 0.01 kVA | ±(5 % of reading + 3 digits) |
| Voltage TRMS measurement | ||
| Range | Resolution | Accuracy |
| 80 ÷ 300 V | 1 V | ±(2 % of reading + 2 digits) |