The Sonel MZC-306 Loop Impedance Meter can measure fault loop impedance to a resolution of 0.01Ω and can determine low-current impedance measurements in circuits protected by RCD ≥30mA (100 to 440V). In addition to this, the Sonel MZC-306 Loop Impedance Meter delivers the following:
1.2m, 5m, 10m and 20m test leads or a power network plug adapter can be connected to the Sonel MZC-306 Loop Impedance Meter. Up to 990 readings can be saved to the Sonel MZC-306 Loop Impedance Meter’s integrated memory. Stored data can be transferred via a USB interface.
Support for a wide range of operating voltages (100V to 750V) means the Sonel MZC-306 Loop Impedance Meter can be used to determine measurements for an array of network types. This makes the Sonel MZC-306 Loop Impedance Meter suitable for use in homes, public buildings and facilities, and small workshops and factories. The Sonel MZC-306 Loop Impedance Meter also has an operating frequency of 45 to 65Hz.
The Sonel MZC-306 Loop Impedance Meter is a versatile, lightweight and professional fault loop meter.
Get a free gift this Black Friday! Even better, this bonus stacks with any other offer.
Free item will automatically add to your basket. Limited Stock. Offer is based on ex VAT basket total after discounts and before shipping costs. See Black Friday Offers for details.
| Measurement of fault loop impedance ZL-PE, ZL-N, ZL-L | ||
| Range | Resolution | Accuracy |
| 0.00...19.99 Ω | 0.01 Ω | ±(5% m.v. + 3 Digits) |
| 20.0...199.9 Ω | 0.1 Ω | ±(4% m.v. + 3 Digits) |
| 200...1999 Ω | 1 Ω | ±(4% m.v. + 3 Digits) |
| Notes |
Measuring range according to IEC61557: 0,13…1999 Ω for 1,2 m test leads; 0,25…1999 Ω for UNI-SCHUKO adapter |
|
|
rated operating voltage UnL-N/ UnL-L: 110/190 V, 115/200 V, 127/220 V, 220/380 V, 230/400 V, 240/415 V, 290/500 V, 400/690 V, |
||
|
operating voltage range: 100…440 V (for ZL-PE and ZL-N) and 100…750 V (for ZL-L) |
||
| high current measurement (up to 30 A) | ||
| Operating frequency range: 45…65 Hz | ||
| Control of correctness of PE terminal connection by means of a contact electrode (applicable to ZL-PE) | ||
| measurement is also possible when L and N circuits are swapped | ||
| measurement of resistance and reactance components | ||
| short circuit current calculation | ||
| Measurement of short circuit loop impedance ZL-PE[RCD] (RCD protected) | ||
| Range | Resolution | Accuracy |
| 0.00...19.99 Ω | 0.01 Ω | ±(6% m.v. + 10 Digits) |
| 20.0...199.9 Ω | 0.1 Ω | ±(6% m.v. + 5 Digits) |
| 200...1999 Ω | 1 Ω | ±(6% m.v. + 5 Digits) |
| Notes | operating voltage range: 100 ... 440 V | |
| rated operating voltage Un: 110 V, 115 V, 127 V, 220 V, 230 V, 240 V, 390 V, 400 V | ||
| control of correctness of PE terminal connection by means of a contact electrode | ||
| measurement is also possible when L and N circuits are swapped | ||
| measurement of resistance and reactance components | ||
| short circuit current calculation | ||
| Voltage Measurement | ||
| Range | Resolution | Accuracy |
| 0.0...249.9 V | 0.1 V | ±(2% m.v. + 4 Digits) |
| 250...750 V | 1 V | ±(2% m.v. + 2 Digits) |
| Notes | frequency range 45…65 Hz | |
| overvoltage alarm | ||
| Electrical Safety | ||
| Type of insulation according to IEC 61010-1 and IEC 61557 |
double | |
| Measurement category according to EN 61010-1 |
IV 600 V / III 1000 V | |
| Protection class acc. to EN 60529 | IP54 | |
| Other Technical Data | ||
| Power supply | rechargeable / alkaline batteries, LR14 (4 pcs) |
|
| Dimensions | 288 x 223 x 75 mm | |
| Weight | ca. 2 kg | |
| Operating temperature | 0…+45°C | |
| Storage temperature | -20…+60°C | |
| Humidity | 20…80% | |
| Reference temperature | +23 ± 2°C | |
| Reference humidity | 40…60% | |
| Altitude | <2000 m | |
| Time to Auto-OFF | 300 seconds | |
| Number of Z measurements (for rechargeable/alkaline batteries) |
>5000 (2 measurements/minute) | |
| Display | LCD segmented | |
| Quality standard | ISO 9001 | |
| The device meets the requirements of | IEC 61557 | |
| The product meets EMC requirements of | EN 61326-1 and EN 61326-2-2 | |