All T and R Products

T&R KV30-40D MK4 Test System

SKU
TR245
Rating:
0%
(0)
Call For Pricing

This is a bulky item and requires a shipping quote

or Call 01642 931 329 to discuss product options

T&R KV30-40D MK4 Test System

The T&R KV30-40D MK4 Test System is a high-voltage, general-purpose test instrument optimised for checking insulation systems and measuring breakdown voltage on electrical plants and components. It offers a 0 to 30kV variable output voltage and a 1.2kVA output capability. The output voltage and current are indicated on dedicated true RMS digital meters. These backlit displays have a digit height of 19mm. A zero-voltage interlock ensures that the output may only be energised with the voltage control at zero.

Additionally, an adjustable current trip protects both the output and test object. The current trip level can be adjusted in 10% stages to between 10% and 110% of the rated output. The breakdown of the test object is visibly indicated. After a trip condition, the T&R KV30-40D MK4 Test System must be manually reset before testing can resume.

Furthermore, the T&R KV30-40D MK4 Test System includes an integrated test timer allowing you to run tests of five, ten, fifteen, twenty, or thirty seconds or one, two, three, or five minutes. An audible alarm will alert you when the test has ended.

Housed in a compact, portable case with a permanently connected 2m-long HV output lead, the T&R KV30-40D MK4 Test System features automatic mains voltage selection and includes an external 24V DC interlock circuit for connection to emergency off switches and enclosure interlocks. The T&R KV30-40D MK4 Test System is also supplied with a T&R ES30 Earthing Stick.

The T&R KV30-40D MK4 Test System is a robust, reliable high-voltage tester.

T&R KV30-40D MK4 Test System Key Features

  • High-voltage, general-purpose test instrument
  • Check insulation systems
  • Measure breakdown of electrical plants and components
  • Variable output voltage: 0-30kV
  • 1.2kVA output capability
  • Output voltage and current are indicated on dedicated true RMS digital meters
  • Backlit displays with 19mm digit height
  • Zero-voltage interlock
  • Adjustable current trip (10-110% of the rated output in 10%) protects both the output and test object
  • Visible indication of the test object breakdown
  • Integrated test timer with audible alert
  • Dual overload protection
  • Key-operated supply switch to prevent unauthorised operation
  • Compact, portable
  • Permanently connected 2m-long HV output lead
  • Automatic mains voltage selection
  • 24V DC interlock circuit
  • T&R ES30 Earthing Stick
  • A robust, reliable high-voltage tester

What’s Included?

  • T&R KV30-40D MK4 Test System
  • T&R ES30 Earthing Stick

T&R KV30-40D MK4 Test System Technical Specifications

Supply Requirements 115V/230V±10% auto-selecting 50/60Hz 1ph 1200VA max
Output The output of the KV30-40D mk3 is supplied via a
permanently connected partially screened high voltage
cable. This stows in the lid for transit along with the ES30 earthing stick.
The output of the KV30-40D is rated at 40mA on a duty
cycle of 5 minutes on/15 minutes off or 20mA
continuously. These ratings are based on an ambient
temperature of 25°C.
Metering The output voltage and current are metered by large,
accurate true RMS digital meters. The meters are backlit
and have a digit height of 19mm.
Test Timer
Meter  Full Scale  Resolution  Accuracy
kV 35.0kV 0.01kV ±0.5% rdg±4d
mA 50.0mA 0.02mA ±0.15% rdg±4d
Note  A pre-selectable test timer is provided for timed tests of 5, 10, 15, 20, 30 seconds, 1, 2, 3 or 5 minutes. An alarm sounds when the test time has ended.
Overload Protection Two overload protection circuits are provided on the units. The first is user selectable, and allows trip currents between 10% and 110% of the rated output to be set. A trip condition is indicated by an illuminated push button and an audible alarm. The second trip circuit is a magnetic circuit breaker operating on the primary of the HV transformer. This operates on large overloads (such as flashovers).
Protection and Safety In addition to the output protection the input and control
supplies are protected by fuses.
All units are designed to meet the requirements of BS
EN61010.
An earth terminal is provided on the transformer which
must be connected to a low-impedance local earth.
An emergency stop will cut all power to the output when activated.
Temperature Range
Storage -20°C to 60°C
Operating 0°C to 45°C
Dimensions 300 x 400 x 470mm
Weight 42kg
Accessories supplied with unit Supply lead, spare fuse set, operating manual, 5m earth
lead, ES30 earthing stick
Special Products If you require a different output voltage test system,
please contact us with your specification and we will
quote for a custom design.
0 Reviews Overall Rating
Write a Review
Write Your Own Review
You're reviewing:T&R KV30-40D MK4 Test System
Your Rating
Additional Information
SKU TR245
Manufacturer Part Code 245
International Enquiry