Important Notice
This item is made-to-order exclusively for you once your order is placed. As a result, it is not eligible for cancellation or return under our standard policy. Your statutory rights remain unaffected.
The Martindale HPAT425 is a compact portable appliance tester that provides automatic test sequences for Class I, Class II, and IEC power leads, with a clear PASS/FAIL indication on a high-contrast greyscale display. An IT-safe 200 mA earth bond test is included, along with selectable 250 V or 500 V insulation testing.
The unit is USB-C rechargeable with fast charging support and incorporates a power-saving mode.
| HPAT425 | HPAT550 | HPAT650 | |
|---|---|---|---|
| Class I, Class II Test & Lead Tests | ✔ | ✔ | ✔ |
| Pass / Fail Indication | ✔ | ✔ | ✔ |
| 200mA Earth Continuity Test Current | ✔ | ✔ | ✔ |
| Insulation Test Voltage 250V & 500V | ✔ | ✔ | ✔ |
| Rechargeable (via USB-C) | ✔ | ✔ | ✔ |
| Sequenced Test Mode | ✔ | ✔ | ✔ |
| Test Values Displayed | ✘ | ✔ | ✔ |
| Greyscale Display | ✔ | ✘ | ✘ |
| Full Colour Display | ✘ | ✔ | ✔ |
| Earth Bond Probe Nulling | ✘ | ✔ | ✔ |
| Single Test Execution Mode | ✘ | ✘ | ✔ |
| Memory (100 Results) | ✘ | ✘ | ✔ |
| Substitute Leakage Test | ✘ | ✘ | ✔ |
| Selectable Pass Limits | ✘ | ✘ | ✔ |
| HPAT425 | HPAT550 | HPAT650 | |
|---|---|---|---|
| Earth Continuity | |||
| Test Voltage | >4V DC (into open circuit) | ||
| Test Current | >200mA DC (into short circuit) | ||
| Range | 0.01 - 20Ω | ||
| Resolution | - | 0.01Ω | |
| Accuracy | ± (5% of reading + 2 digits) | ||
| Fixed / Default Pass Limits | ≤0.1Ω 0.11Ω to ≤0.30Ω long lead 0.31Ω to ≤0.50Ω extra long lead |
Fixed ≤0.1Ω ≤0.5Ω selectable pass for long cable |
Default ≤0.1, user settable ≤0.5Ω selectable pass for long cable |
| User-Settable Limits | - | - | ≤0.1Ω to ≤0.9Ω in 0.1Ω steps |
| Insulation | |||
| Test Voltage | User selectable >250V DC at 1mA
/ >500V DC at 1mA (<312.5V DC open circuit / <625V DC open circuit) |
||
| Test Current | <2mA (into short circuit) | ||
| Range | 0.01MΩ - 100MΩ | ||
| Resolution | - | 0.01MΩ (10kΩ - 2MΩ) 0.1MΩ (2MΩ - 20MΩ) 1MΩ (20MΩ - 100MΩ) |
|
| Accuracy | 5% reading + 2 digits | ||
| Pass Level | Lead: ≥ 1.0MΩ Class I: ≥1.0MΩ Class II: ≥2.0MΩ |
||
| User-settable Pass Level | - | - | ≥0.3MΩ to ≥ 1MΩ in 0.1MΩ steps ≥1MΩ to ≥ 10MΩ in 1MΩ steps |
| Substitute Leakage Test | |||
| Test Voltage | - | - | <50V AC (into open circuit) 0.02-20mA DC (into short circuit) |
| Accuracy | - | - | ± (5% reading + 2 digits) |
| Pass Level | - | - | <5mA |
| Memory | |||
| Test Records | - | - | 100 tests stored for on-screen recall |
| Power | |||
| Batteries | 3.7V 5000mAh lithium polymer battery (non-user replaceable) | ||
| Battery Life | Fully charged, minimum 1700 complete tests, approx. | ||
| Auto Power Down | Auto dimming after 3 minutes, Auto power down after 5 minutes of inactivity | ||
| Environmental | |||
| Location | Suitable for indoor and outdoor use in dry weather conditions only | ||
| Altitude | Up to 2000m | ||
| Operating Temperature | 0°C to 40°C | ||
| Humidity | ≤80% RH up to 31°C, decreasing linearly to 50°C RH at 40°C | ||
| Ingress Protection Class | IP20 | ||
| Pollution Degree | 2 | ||
| General | |||
| Overload Protection | 300V AC/DC | ||
| Protection Class | IP20 | ||
| Safety | Complies with BS EN 61010-1 | ||