The Martindale HPAT650 PAT Professional Kit is a complete, no-nonsense solution built for fast, accurate, and fully trackable appliance testing. Designed for practical, real-world use, the HPAT650 features onboard memory for storing and recalling up to 100 results, plus both single and sequenced test modes, adjustable pass limits for long leads, and a substitute leakage test—perfect for situations where powering the appliance isn’t an option.
The tester supports Class I, Class II, and IEC lead testing, with selectable 250 V and 500 V insulation voltages, a safe 200 mA earth bond test for IT equipment, and clear PASS/FAIL indicators on a high-quality colour screen. It’s compact, USB‑C rechargeable, and simple to use, even for less experienced testers, thanks to optional on-screen help prompts.
The Professional Kit takes it further by including Simply Pats Manual Entry Software, making it easier to log and manage test data for reporting and compliance. Alongside the tester, you get a rugged carry case packed with essential accessories: multiple IEC adaptors, a microwave leakage detector, UK socket tester, earth bond probe, screwdriver set, carbonless register booklet, online PAT training, and over 1,000 pass/fail labels, everything you need to hit the ground running on any PAT testing job.
Earth Continuity | |
---|---|
Test Voltage | >4V DC (into open circuit) |
Test Current | >200mA DC (into short circuit) |
Range | 0.01 - 20Ω |
Resolution | 0.01Ω |
Accuracy | ± (5% of reading + 2 digits) |
Fixed / Default Pass Limits | Default ≤0.1, user settable ≤0.5Ω selectable pass for long cable |
User-Settable Limits | ≤0.1Ω to ≤0.9Ω in 0.1Ω steps |
Insulation | |
Test Voltage | User selectable >250V DC at 1mA / >500V DC at 1mA (<312.5V DC open circuit / <625V DC open circuit) |
User Selectable Voltage | |
Test Current | <2mA (into short circuit) |
Range | 0.01MΩ - 100MΩ |
Resolution | 0.01MΩ (10kΩ - 2MΩ) 0.1MΩ (2MΩ - 20MΩ) 1MΩ (20MΩ - 100MΩ) |
Accuracy | 5% reading + 2 digits |
Pass Level | Lead: ≥ 1.0MΩ Class I: ≥1.0MΩ Class II: ≥2.0MΩ |
User-settable Pass Level | ≥0.3MΩ to ≥ 1MΩ in 0.1MΩ steps ≥1MΩ to ≥ 10MΩ in 1MΩ steps |
Substitute Leakage Test | |
Test Voltage | <50V AC (into open circuit) 0.02-20mA DC (into short circuit) |
Accuracy | ± (5% reading + 2 digits) |
Pass Level | <5mA |
Memory | |
Test Records | 100 tests stored for on-screen recall |
Power | |
Batteries | 3.7V 5000mAh lithium polymer battery (non-user replaceable) |
Battery Life | Fully charged, minimum 1700 complete tests, approx. |
Auto Power Down | Auto dimming after 3 minutes, Auto power down after 5 minutes of inactivity |
Environmental | |
Location | Suitable for indoor and outdoor use in dry weather conditions only |
Altitude | Up to 2000m |
Operating Temperature | 0°C to 40°C |
Humidity | ≤80% RH up to 31°C, decreasing linearly to 50°C RH at 40°C |
Ingress Protection Class | IP20 |
Pollution Degree | 2 |
General | |
Overload Protection | 300V AC/DC |
Protection Class | IP20 |
Safety | Complies with BS EN 61010-1 |