All Metrel Products

Metrel MI3360 OmegaPAT XA PAT Tester – PAT Essentials Kit (Bundle 1)

SKU
OMEGAPATXABUNDLE1
Rating:
0%
(0)
Reward Points
:
1604
£1,924.80 £1,604.00
In Stock Free UK Delivery*
Choose a Special Offer
  • PASS The Complete Guide to EET (PAT) Testing Cover
    PASS The Complete Guide to EET (PAT) Testing, 5th Edition
    FREE
    £24.99
  • PASS The Complete Guide to EET (PAT) Testing, 5th Edition SKU: (PASS-PAT-HB)
    FREE
    £24.99
    PASS The Complete Guide to EET (PAT) Testing Cover
Advice & Support
Price Match Request
Free Complete Guide to EET (PAT) Testing
Metrel MI3360 OmegaPAT XA PAT Tester Essentials Kit (Bundle 1)
PASS PAT Guide

FREE - PASS The Complete Guide to EET (PAT) Testing, 5th Edition

Buy a PAT testing kit and get an updated PAT Testing Guide worth £24.99. This 129 page indepth PAT testing book is a great addition to your kit. View PAT Guide

The Metrel MI3360 OmegaPAT XA PAT Tester – PAT Essentials Kit (Bundle 1) consists of the Metrel MI3360 OmegaPAT XA PAT Tester supplied with the standard manufacturer's accessories, and a variety of additional PAT testing accessories including adapters, labels and a microwave leakage detector. For a comprehensive list of all the items included in this kit, please see the ‘What’s Included?’ section.

Please see the following description for further information regarding the Metrel MI3360 OmegaPAT XA PAT Tester. 

Metrel MI3360 OmegaPAT XA PAT Tester Description

The Metrel MI3360 OmegaPAT XA PAT Tester is a downloadable PAT tester optimised for testing Class I, Class II and Class III portable appliances often used in hotels, schools and other public institutions. As such it includes the following testing capabilities:

  • Visual inspection
  • Fuse test
  • Continuity/ earth bond resistance 200mA test
  • Insulation resistance (Riso, Riso-S) test
  • Substitute leakage current test
  • Differential leakage current test
  • PE leakage current test
  • Touch leakage current test
  • Polarity/ active polarity test
  • Power (P, S, Q, PF, THDu, THDi, CosØ, I, U) test
  • P-RCD (2-pole, 3-pole, K/Di (varistor), S (3-pole)) test
  • PRCD PE probe test
  • Open conductor test
  • PE conductor test
  • RCD (type A, AC, B, B+, F) test

When used with the OPTIONAL Metrel A1422 Active 3-phase Adapter Plus the Metrel MI3360 OmegaPAT XA PAT Tester can perform welding circuit leakage, primary leakage, and no-load voltage tests in accordance with IEC/ EN 60974-4. This expands the Metrel MI3360’s scope-for-use to include testing welding equipment. This instrument can also be used with Metrel’s A1283 Current Clamp Adapter (NOT included) to measure leakage current.

The Metrel MI3360 OmegaPAT XA PAT Tester includes a testing module for checking all types of fuses, as well as additional test terminals for testing hard-wired instruments.

As the Metrel MI3360 OmegaPAT XA PAT Tester is optimised for testing Class I, Class II and Class III appliances it includes a number of pre-programmed test sequences optimised for checking particular instruments. These tests can be accessed and run via the AUTOSEQUENCES® function. Moreover, the Metrel MI3360 OmegaPAT XA PAT Tester’s integrated filters ensure that the test sequences are relevant to the area of application and improve the ease with which the user can select the appropriate test.

It is also possible to create personalised test sequences which can be saved, along with test results, to the 8GB microSD memory card. Recalling and re-executing saved tests or test sequences for particular instruments is simple and efficient as a result of the microSD card’s intelligently structured memory.

Ease-of-use is also improved by the Metrel MI3360 OmegaPAT XA PAT Tester’s advanced user-interface; high-resolution, touch-screen, 4.3-inch, TFT display; and keyboard. The physical features ensure that the interface is simple to navigate and allows the user to enter information into the tester via his/her preferred method.

The Metrel MI3360 OmegaPAT XA PAT Tester supports multiple user accounts. As such, this portable appliance tester can be configured to suit each electrician. Each individual’s test setups (and test results) are then saved to his/her account ensuring that they remain unaltered while the Metrel MI3360 OmegaPAT XA PAT Tester is used by another electrician.

Professional reports can be created using saved test data and the included Metrel ES Manager BASIC Software. This software can also be used to create and upload test structures and AUTOSEQUENCES® to the Metrel MI3360 OmegaPAT XA PAT Tester.

Alternatively, the PAT tester’s Bluetooth capabilities can be utilised in order to facilitate a connection to the Metrel aMESM Android SW App. This app allows the user to scan QR codes with his/her phone. The information contained within these barcodes is then used to populate the Metrel MI3360’s test fields, enabling quick and simple re-testing. (It is also possible to read QR codes using Metrel’s compatible Bluetooth QR Scanners (NOT included).) After test completion, updated test information can be written into a QR code and printed using Metrel’s Bluetooth QR Label Printers (NOT included).

The Metrel MI3360 OmegaPAT XA PAT Tester is a sophisticated, adaptable and comprehensive downloadable portable appliance tester. It is ideal for checking Class I, Class II and Class III appliances.

Electric Kettle | Testing of Class I Appliances | MI 3360 | How To Video (UK)

Portable RCD | Testing of Class II Appliances | MI 3360 | How To Video (UK)

Metrel MI3360 OmegaPAT XA PAT Tester Key Features

  • A downloadable portable appliance tester
  • Optimised for checking Class I, Class II and Class III portable appliances
  • Visual inspection
  • Fuse test
  • Continuity/ earth bond resistance 200mA test
  • Insulation resistance (Riso, Riso-S) test
  • Substitute leakage current test
  • Differential leakage current test
  • PE leakage current test
  • Touch leakage current test
  • Polarity/ active polarity test
  • Power (P, S, Q, PF, THDu, THDi, CosØ, I, U) test
  • P-RCD (2-pole, 3-pole, K/Di (varistor), S (3-pole)) test
  • PRCD PE probe test
  • Open conductor test
  • PE conductor test
  • RCD (type A, AC, B, B+, F) test
  • Use with the OPTIONAL A1422 Metrel A1422 Active 3-phase Adapter Plus to perform welding circuit leakage, primary leakage and no-load voltage tests in accordance with IEC/ EN 60974-4
  • When used with the OPTIONAL A1422 Adapter the tester is suitable for checking welding equipment
  • Use with Metrel’s A1283 Current Clamp Adapter (NOT included) to measure leakage current
  • Includes a testing module for checking all fuse types
  • Additional test terminals for hard-wired instruments
  • Pre-programmed test sequences for particular appliances
  • Access and run pre-programmed test sequences via the AUTOSEQUNCES® function
  • Integrated filters ensure that test sequences are relevant to the application
  • Integrated filters improve the ease with which the user can select the relevant test
  • Create personalised test sequences
  • Save test sequences to the 8GB microSD memory card
  • Save test results to the 8GB microSD memory card
  • The structure of the microSD card’s memory makes test recall and re-execution easy
  • Advanced user interface
  • High-resolution, touch-screen, 4.3-inch, TFT display
  • Keyboard
  • Supports multiple user accounts
  • Test setups and records can be saved to each user account, ensuring they remain unaltered except by the authorised user
  • Create professional reports using test data and the Metrel ES Manager BASIC Software
  • Create and upload test structures and AUTOSEQUENCES® to the tester using the above software
  • Bluetooth capabilities
  • Connect to the Metrel aMESM Android SW App, compatible Metrel Bluetooth QR Scanners (NOT included), and compatible Metrel Bluetooth QR Label Printers (NOT included) via Bluetooth
  • A sophisticated, adaptable and comprehensive downloadable portable appliance tester
  • Ideal for checking Class I, Class II and Class III portable appliances

What’s Included in the Metrel MI3360 OmegaPAT XA PAT Tester – PAT Essentials Kit (Bundle 1)?

  • Metrel MI3360 OmegaPAT XA PAT Tester
  • Accessory Bag (supplied by Metrel)
  • Smartball Pen with Touchscreen Function (supplied by Metrel)
  • Black Crocodile Clip (supplied by Metrel)
  • Black Test Lead (supplied by Metrel)
  • Black Test Tip (supplied by Metrel)
  • 2m IEC Test Cable (supplied by Metrel)
  • Mains Cable (supplied by Metrel)
  • USB Cable (supplied by Metrel)
  • Calibration Certificate (supplied by Metrel)
  • Short Form Instruction Manual (supplied by Metrel)
  • CD with Instruction Manual (supplied by Metrel)
  • Metrel ES Manager BASIC Software (supplied by Metrel)
  • Socket Tester
  • eLearning PAT Testing Course - Includes Exam and Certificate
  • Microwave Leakage Detector
  • 2x 110V Adapters
  • 3x IEC Adapters
  • 5 Piece Insulated Screwdriver Kit
  • 1000x Passed PAT Testing Labels
  • 500x Circular Passed PAT testing Labels
  • 500x Cable Wrap Labels
  • 250x Failed PAT Testing Labels

Metrel MI3360 OmegaPAT XA PAT Tester Technical Specifications 

Continuity / Protective Earth Resistance
Continuity
Ranges 0.00 Ω … 19.99 Ω / 20.0 Ω … 99.9 Ω / 100.0 Ω … 199.9 Ω / 200 Ω … 999 Ω 
Resolution 0.01 Ω / 0.1 Ω / 0.1 Ω / 1 Ω \
Accuracy ±(2 % of reading + 2 D) / ± 3 % of reading / ± 5 % of reading / indicative
Operating range (acc. to EN 61557-4) 0.08 Ω … 199.9 Ω
Test currents 0.2 A,10 A, 25 A
Current source (at nominal mains voltage, use of standard accessories)  > 0.2 A at R < 2 Ω
> 10 A at R < 0.1 Ω at 230 V
> 25 A into short circuit at 230 V
Open circuit voltage < 9 V a.c.
Test Terminals
Continuity
R (200 mA) P/S – PE, Socket PE; Socket PE – IEC PE
R (10 A, 25 A) P/S – Socket PE; Socket PE – IEC PE
Protective Earth Resistance
R (200 mA) P/AP – PE, Socket PE
R (10 A, 25 A) P/AP – Socket PE
Insulation Resistance (Riso, Riso-S)
Insulation resistance, Insulation resistance –S (250 V, 500 V)
Range 0.00 MΩ … 19.99 MΩ / 20.0 MΩ … 99.9 MΩ / 100.0 MΩ … 199.9 MΩ 
Resolution 0.01 MΩ / 0.1 MΩ / 0.1 MΩ 
Accuracy ±(3 % of reading + 2 D) / ± 5 % of reading /± 10 % of reading
Output voltage (Um)
Range 0 V … 600 V 
Resolution 1V 
Accuracy ±(3 % of reading + 2 D)
Operating range (acc. to EN 61557-2) 0.08 MΩ … 199.9 (999) MΩ
Nominal voltages Un 250 V, 500 V (- 0 %, + 10 %)
Short circuit current max. 2.0 mA
Test terminals Riso LN, Socket LN – PE, Socket PE, P/S
Riso-S LN, Socket LN – P/S
Sub-Leakage Current, Substitute Leakage Current - S (Isub, Isub-S)
Range 0.00 mA … 1.99 mA / 2.00 mA … 19.99 mA 
Resolution 0.01mA / 0.01mA 
Accuracy ±(3 % of reading + 3 D) / ±(5 % of reading)
Operating range (acc. to EN 61557-16) 0.02 mA … 19.99 mA
Open circuit voltage 230 V a.c., 110 V a.c.
Current calculated to mains supply voltage (110 V or 230 V) is displayed.
Test Terminals Isub LN, Socket LN – PE, Socket PE, P/S
Isub-S LN, Socket LN – P/S
Differential leakage current (Idiff)
Differential leakage current
Range 0.000 mA … 1.999 mA / 2.00 mA … 19.99 mA 
Resolution 1 µA / 0.01 mA 
Accuracy ±(3 % of reading + 3 D) / ±(5 % of reading)
Power (active) (P)
Range 0 W … 999 W / 1.00 kW … 3.70 kW 
Resolution 1W / 10W
Accuracy ±(5 % of reading + 5 D) / ±5 % of reading
Operating range (acc. to EN 61557-16) 0.010 mA … 19.99 mA
Influence of load current < 0.02 mA/A
Test terminals Idiff Socket L,N – Socket PE, P/S
P Socket L – Socket N
PE leakage current (Ipe)
PE leakage current
Range 0.000 mA … 1.999 mA / 2.00 mA … 19.99 mA 
Resolution 1µA / 0.01mA 
Accuracy ±(3 % of reading + 3 D) / ±(5 % of reading)
Power (active) (P)
Range 0 W … 999 W / 1.00 kW … 3.70 kW 
Resolution 1W / 10W 
Accuracy ±(5 % of reading + 5 D) / ±5 % of reading
Operating range (acc. to EN 61557-16) 0.010 mA … 19.99 mA
Test terminals Ipe Socket L,N – Socket PE
P Socket L – Socket N
Touch leakage current (Ipe)
Touch leakage current
Range 0.000 mA … 1.999 mA / 2.00 mA … 19.99 mA
Resolution 1 µA / 0.01mA 
Accuracy ±(3 % of reading + 3 D) / ±(5 % of reading)
Power (active) (P)
Range 0 W … 999 W / 1.00 kW … 3.70 kW 
Resolution 1W / 10W
Accuracy ±(5 % of reading + 5 D) / ±5 % of reading
Operating range (acc. to EN 61557-16) 0.010 mA … 19.99 mA
Test terminals Itou: Socket L,N – P/S
P: Socket L – Socket N
Power
Power (active) (P)
Range 0 W … 999 W / 1.00 kW … 3.70 kW 
Resolution 1W / 10W 
Accuracy  ±(5 % of reading + 5 D) / ±5 % of reading
Power (apparent) (S)
Range 0 VA … 999 VA / 1.00 kVA … 3.70 kVA 
Resolution 1 VA / 10VA 
Accuracy ±(5 % of reading + 5 D) / ±5 % of reading
Power (reactive) (Q)
Range ±(0 VAr … 999) VAr / ±(1.00 kVAr … 3.70) kVAr 
Resolution 1 VAr / 10 VAr
Accuracy ±(5 % of reading + 5 D) / ±5 % of reading
Power factor (PF)
Range 0.00i … 1.00i / 0.00c … 1.00c 
Resolution 0.01
Accuracy ±(5 % of reading + 5 D)
Total Harmonic Distortion (voltage) (THDU)
Range 0.0 % … 99.9 % 
Resolution 0.1 %
Accuracy ±(5 % of reading + 5 D)
Total Harmonic Distortion (current) (THDI)
Range 0.00 A … 16.00 A 
Resolution  0.01 A 
Accuracy ±(3 % of reading + 5 D)
Cosinus Φ (Cos Φ)
Range 0.00i … 1.00i / 0.00c … 1.00c 
Resolution 0.01 
Accuracy ±(5 % of reading + 5 D)
Current (I)
Range 0.00 A … 16.00 A 
Resolution  0.01 A
Accuracy ±(3 % of reading + 5 D)
Voltage (U)
Range 0.0 V … 199.9 V / 200 V … 264 V 
Resolution 0.1V / 1V
Accuracy ±(3 % of reading + 10 D) / ±3 % of reading
Test terminals
P,S,Q,PF,THDU,THDI, Cos Φ, I, U Socket L – Socket N
Leaks & Power
Power (active) (P)
Range 0 W … 999 W / 1.00 kW … 3.70 kW 
Resolution 1W / 10W 
Accuracy ±(5 % of reading + 5 D) / ±5 % of reading
Touch leakage current: (Itou)
Range 0.000 mA … 1.999 mA / 2.00 mA … 19.99 mA
Resolution 1 µA / 0.01 mA
Accuracy ±(3 % of reading + 3 D) / ±(5 % of reading)
Operating range (acc. to EN 61557-16) 0.010 mA … 19.99 mA
Differential leakage current (Idiff)
Range 0.000 mA … 1.999 mA / 2.00 mA … 19.99 mA 
Resolution 1 µA / 0.01 mA 
Accuracy ±(3 % of reading + 3 D) / ±(5 % of reading)
Operating range (acc. to EN 61557-16) 0.010 mA … 19.99 mA
Influence of load current < 0.02 mA/A
Power (apparent) (S)
Range 0 VA … 999 VA / 1.00 kVA … 3.70 kVA 
Resolution 1 VA / 10VA 
Accuracy ±(5 % of reading + 5 D) / ±5 % of reading
Power (reactive) (Q)
Range ±(0 VAr … 999) VAr / ±(1.00 kVAr … 3.70) kVAr 
Resolution 1 VAr / 10 VAr
Accuracy ±(5 % of reading + 5 D) / ±5 % of reading
Power factor (PF)
Range 0.00i … 1.00i / 0.00c … 1.00c 
Resolution 0.01 
Accuracy ±(5 % of reading + 5 D)
Total Harmonic Distortion (voltage) (THDU)
Range 0.0 % … 99.9 % 
Resolution 0.1 % 
Accuracy ±(5 % of reading + 5 D)
Total Harmonic Distortion (current) (THDI)
Range 0.00 A … 16.00 A 
Resolution 0.01 A 
Accuracy ±(3 % of reading + 5 D)
Cosinus Φ (Cos Φ)
Range 0.00i … 1.00i / 0.00c … 1.00c 
Resolution 0.01 
Accuracy ±(5 % of reading + 5 D)
Current (I)
Range 0.00 A … 16.00 A 
Resolution 0.01 A 
Accuracy ±(3 % of reading + 5 D)
Voltage (U)  
Range 0.0 V … 199.9 V / 200 V … 264 V 
Resolution 0.1V / 1V 
Accuracy ±(3 % of reading + 10 D) / ±3 % of reading
Test terminals
P,S,Q,PF,THDU,THDI, Cos Φ, I, U Socket L – Socket N 
Idiff Socket L,N – Socket PE, P/S
Itou Socket L,N – P/S
PRCD test
Trip-out time (tΔN)
Range 0 ms … 300 ms (999 ms*) (½xI∆N) / 0 ms … 300 ms (I∆N) / 0 ms … 40 ms (5xI∆N)
Resolution 1ms / 1ms / 1ms 
Accuracy ±3ms / ±3ms / ±3ms
*According to standard AS/NZS 3017
Trip out-current (IΔ)
Range 0.2xI∆N … 2.2xI∆N 
Resolution  0.05xI∆N 
Accuracy ±0.1xI∆N
Test current type sine-wave (AC), pulsed (A,F), smooth DC (B,B+)
Test currents (IΔN) 10 mA, 15 mA, 30 mA;.................100 mA and 300 mA with A1322, A1422
Test current size (PRCD standard is AS/NZS 3017) ±5%
Test current size (general) -0/+10%
Test terminals tΔN, IΔ Socket – IEC
RCD Test
Trip-out time (tΔN)
Range 0 ms … 300 ms (999 ms*) (½xI∆N) / 0 ms … 300 ms (I∆N) / 0 ms … 40 ms (5xI∆N)
Resolution 1ms / 1ms / 1ms 
Accuracy ±3ms / ±3ms / ±3ms
*According to standard AS/NZS 3017
Trip out-current (IΔ)
Range 0.2xI∆N … 2.2xI∆N 
Resolution 0.05xI∆N 
Accuracy ±0.1xI∆N
Contact voltage (Uc)
Range 0.0 V … 19.9 V / 20.0 V … 99.9 V 
Resolution 0.1V / 0.1V 
Accuracy  (-0 % / +15 %) of reading ± 10 D / 0.1 V (-0 % / +15 %) of reading
Test current type sine-wave (AC), pulsed (A,F), smooth DC (B,B+)
Test currents (IΔN) 10 mA, 15 mA, 30 mA
Test current size (RCD standard is AS/NZS AS/NZS) 5%
Test current size (EN 61008/EN 61009) -0/+10%
Test terminals tΔN, IΔ Mains Socket
PE conductor (PRCD)
PE conductor (Type = 2 pole, 3 pole, S(3 pole)) (R)
Range 0.00 Ω … 19.99 Ω / 20.0 Ω … 99.9 Ω / 100.0 Ω … 199.9 Ω / 200 Ω … 999 Ω 
Resolution 0.01 Ω / 0.1 Ω / 0.1 Ω / 1 Ω 
Accuracy ±(2 % of reading + 2 D) / ± 3 % of reading / ± 5 % of reading / indicative
Operating range (acc. to EN 61557-4) 0.08 Ω … 199.9 Ω
Current source (at nominal mains voltage, use of standard accessories) > 0.2 A at R < 2 Ω
Open circuit voltage < 9 V a.c.
Test terminals R Socket PE – IEC PE
PE conductor (Type = K/ Di (varistor))
Test principle: A voltage is applied between PE connections of the PRCD-K. There is a ‘PASS’ if PRCD trips.
Open circuit voltage 24 V
Output resistance 220 Ω ± 10 % (IΔN = 30 mA), 620 Ω ± 10 % ((IΔN = 10 mA)
Test terminals Result: Socket – IEC
Open conductor (PRCD)
Test principle: Mains voltage is applied to the mains test socket. Disconnection of the L, N and PE connections is performed inside the instrument. There is a ‘PASS’ if the PRCD trips.
Test terminals L open, N open, PE open Socket – IEC
PRCD PE probe test
Test principle: Mains voltage is applied to the mains test socket. A safe voltage sufficiently high to activate the protection circuit in the PRCD is applied to the P/S terminal.
Test terminals Result (manual): Socket, P/S
Result (auto): Socket – IEC, P/S
Polarity
Test voltage (normal) < 50 V
Test voltage (active) mains voltage
Power consumption of tested device during the active test < 25 VA
Test terminals Result (normal, active) Socket – IEC
Clamp current (I, Idiff, Ipe)
True RMS current using 1000:1 current clamp
Range 0.10 mA … 9.99 mA / 10.0 mA … 99.9 mA / 100 mA … 999 mA / 1.00 A … 9.99 A / 10.0 A … 24.9 A 
Resolution 0.01 mA / 0.1 mA / 1 mA / 0.01 A / 0.1 A
Accuracy ±(5 % of reading + 10 digits) / ±(5 % of reading + 5 digits) / ±(5 % of reading + 5 digits) / ±(5 % of reading + 5 digits) / ±(5 % of reading + 5 digits)
Notes Accuracy of current transformer is not considered.
Frequency range of current clamp is not considered.
Test terminals I, Idiff, Ipe: CLAMPS terminals
Insulation resistance Riso (welding equipment)
Riso
Range 0.00 MΩ … 19.99 MΩ / 20.0 MΩ … 99.9 MΩ / 100.0 MΩ … 199.9 MΩ 
Resolution 0.01 MΩ / 0.1 MΩ / 0.1 MΩ
Accuracy ±(3 % of reading + 2 D) / ±5 % of reading / ±10 % of reading
Output voltage (Um)
Range 0 V … 600 V 
Resolution 1 V 
Accuracy ±(3 % of reading + 2 D)
Operating range (acc. to EN 61557-2) 0.08 MΩ … 199.9 (999) MΩ
Nominal voltages Un 500 V (- 0 %, + 10 %)
Short circuit current max. 2.0 mA
Test terminals
Riso LN-W: A 1422 Socket L1 L2 L3 N (16A-5p, 32A-5p or 16A-3p) – W1 W2
Riso W-PE A 1422: Socket PE (16A-5p, 32A-5p or 16A-3p) – W1 W2
Riso LN-PE A 1422: Socket L1 L2 L3 N (16A-5p, 32A-5p or 16A-3p) – Socket PE (16A-5p, 32A-5p or 16A-3p)
Riso LN (Class II) - P A 1422: Socket L1 L2 L3 N (16A-5p, 32A-5p or 16A-3p) – MI 3360: P/S
General Specifications
Mains supply
Supply voltage, frequency 110 V / 230 V AC, 50 Hz / 60 Hz
Supply voltage tolerance 10 %
Max. power consumption 300 VA (without load on test socket)
Max. load 10 A continuous, 16 A short duration, 1.5 kW motor
Mains supply overvoltage category CAT II / 300V
Altitude ≤ 2000 m
Measuring categories
Instrument Cat II / 300 V
Test socket Cat II / 300 V
Plug test cable Cat II / 300 V
Altitude ≤ 2000 m
Protection classifications
Power supply Mains supply
Pollution degree 2
Degree of protection IP40
IP20 (mains test socket)
Case Shock proof plastic / portable
Display Colour TFT display, 4.3 inch, 480 x 272 pixels
Touch screen Capacitive
Communication
Memory depends on microSD card size
RS232 interfaces 2
USB 2.0 Standard USB Type B
Bluetooth Class 2
Dimensions (w×h×d) 31 cm × 13 cm × 25 cm
Weight 6.1 kg
Reference conditions
Reference temperature range 15 ˚C … 35 ˚C
Reference humidity range 35 % … 65 % RH
Operation Conditions 
Working temperature range 0 ˚C … +40 ˚C
Maximum relative humidity 85 % RH (0 ˚C … 40 ˚C), non-condensing
Storage Conditions
Temperature range -10 ˚C … +60 ˚C
Maximum relative humidity 90 % RH (-10 ˚C … +40 ˚C)
80 % RH (40 ˚C … 60 ˚C)
Notes Accuracies apply for 1 year in reference conditions. Temperature coefficient outside these limits is 0.2 % of measured value per ˚C plus 1 digit, otherwise noted.
Fuses 2 x T 16 A / 250 V, 32 mm  6.3 mm / 1500 A
0 Reviews Overall Rating
Write a Review
Write Your Own Review
You're reviewing:Metrel MI3360 OmegaPAT XA PAT Tester – PAT Essentials Kit (Bundle 1)
Your Rating
Additional Information
SKU OMEGAPATXABUNDLE1
Manufacturer Part Code OMEGAPATXABUNDLE1
International Enquiry