The Beha-Amprobe 2100-GAMMA PRO Electric Tester Kit includes the Beha-Amprobe 2100-Gamma Voltage Tester, holster, and a Beha-Amprobe 2100-ACCS Test Probe Extender Set. This kit is ideal for taking safe and reliable measurements in tight and/or hard-to-access spaces. The test fuse probe extenders are specifically designed to enable measurement at fuse switch disconnectors and busbars inside switchboards with isolators and isolation switches. The Beha-Amprobe 2100-GAMMA PRO Electric Tester Kit is suitable for ensuring reliable contact testing without having to remove protective covers.
The Beha-Amprobe 2100-GAMMA Pro Two-Pole Voltage Tester is a voltage and continuity indicator that measures voltage up to 1000V AC/ 1200V DC and resistance up to 1999Ω. It also offers non-contact voltage detection, low-resistance indication, as well as 10mA and 30mA RCD trip tests with a two-button switchable load. Measurements are indicated on the LCD panel and LCD screen; they can be frozen on the display using the Data Hold function. Other useful features present on the Beha-Amprobe 2100-GAMMA Pro Two-Pole Voltage Tester include a torch, wear-indicator test leads, and a test probe prorector cover with accessory storage.
Please follow this link for more information regarding the Beha-Amprobe 2100-GAMMA Pro Two-Pole Voltage Tester.
Specifically designed to take measurements at fuse switch disconnectors and busbars inside switchboards with isolators and isolation switches, the Beha-Amprobe 2100-ACCS Test Probe Extender Set enables safe and reliable measurement in tight and/or difficult-to-access spaces. The probe extenders are CAT IV 1000V AC/DC / CAT III 1500V DC safety rated, 102mm long, and feature an M3 thread for fast connection and reliable contact.
For more information about the Beha-Amprobe 2100-ACCS Test Probe Extender Set, please click here.
Spend £150+ (Ex VAT) on any qualified Fluke or Beha-Amprobe product(s) and claim a free tool of your choice from the list at Fluke Promotion. Valid February 17 2025 - July 31 2025.
Claims are made direct to Fluke. Terms and conditions apply.
2100-Alpha | 2100-Beta | 2100-Gamma | |
---|---|---|---|
Voltage Test |
|||
LED Voltage Range |
12…690 V AC/DC |
12…690 V AC/DC |
12…≥690 V AC/DC |
LED Indicator |
±12, ±24, 50, 120, 230, 400, 690 V |
±12, ±24, 50, 120, 230, 400, ≥690 V |
|
LED Tolerances |
acc. To EN 61243-3:2010 |
||
LCD Voltage Range |
- |
12…690 V AC/DC |
6…1000 V AC/ 6…1200 V DC |
LCD Resolution |
- |
1 V |
|
LCD Tolerance |
- |
± (3% rdg + 3 LSD) |
|
LED and LCD Response Time |
< 1s |
||
Frequency Range |
DC, 16 2/3 Hz…400 Hz |
||
Acoustic Indication |
≥ 50 V AC, ≥ 120 V DC |
||
Voltage Detection |
Automatic (AC/DC) |
||
Polarity Detection |
Full Range |
||
Range Detection |
Automatic |
||
Current I (load buttons not activated) |
≤3.5 mA AC/DC at 690 V AC/DC |
≤3.5 mAAC at 1000 VAC/ 4.5 mADC at 1200 VDC |
|
Internal Load (load buttons not activated) |
Approximately 2.4 W at 690 V AC/DC |
Approximately 3.5 W at 1000 VAC / Approximately 5.4 W at 1200 VDC |
|
Test Current Switchable Load (load buttons activated) |
≤350 mA AC/DC at 690 V AC/DC |
≤300 mAAC at 1000 VAC / ≤350 mADC at 1200 VDC |
|
Switchable Load (load buttons activated) |
Approximately 240 W at 690 V AC/DC |
Approximately 300 W at 1000 VAC / Approximately 420 W at 1200 VDC |
|
Automatic Power ON |
LED: >12 V (activated load buttons) >24 V (w/o load buttons) |
LED: >12 V (activated load buttons) >24 V (w/o load buttons) LCD: >12V |
LED: >12 V LCD: > 6V |
Trip Test RCD (earth leakage circuit breaker) |
|||
Test Current Switchable Load (load buttons activated) |
>30 mAAC at 230 VAC |
||
Single Pole Phase Test |
|||
Voltage Range |
180…690 VAC against earth |
100…1000 VAC against earth |
|
Frequency Range |
40Hz… 70Hz |
||
Acoustic Indication |
Yes |
||
Indication |
Red LED |
||
Continuity Test (Rx)/ Diode Test |
|||
Range |
0….500 kΩ |
||
Tolerance |
0% to +50% |
||
Test Current |
<5 μA |
||
Acoustic Indication |
Yes |
||
Diode Test |
Yes |
||
Indication |
RED LED |
||
Overvoltage Protection |
690 V AC/DC |
1000 VAC/ 1200 VDC |
|
Automatic Power ON |
< 500 kΩ |
||
Phase Rotation Indication |
|||
Voltage Range |
340…440 V AC phase to phase |
170…1000 V AC phase to phase |
|
Frequency Range |
47…63 Hz |
40…70 Hz |
|
Indication |
Red LED |
||
Resistance Measurement (Ω)/ Low Resistance Indication (2100-Gamma only) |
|||
Resistance Range on LCD |
0….1999 Ω |
||
Resolution |
1 Ω |
||
Tolerance |
± (5% rdg + 10 LSD) at 20°C |
||
Temperature Coefficient |
± (5 LSD / 10 K) |
||
Test Current |
<30 μA |
||
Low Resistance Indication |
Acoustic Indication <10…50Ω |
||
Overvoltage Protection |
690 V AC/DC |
1000 VAC/ 1200 VDC |
|
Non-Contact Voltage Indication/ Electric Field (NCV/EF) |
|||
Voltage Range |
- |
100…1000 VAC |
|
Frequency Range |
- |
50…60 Hz |
|
Indication |
_ |
3 levels shown by LCD segments |
|
Data Hold |
|||
Data Hold |
_ |
Only voltage measurements (12…690V AC/DC) |
Voltage and resistance measurements, NCV |
Measurement Illumination Area/ Torch Light |
|||
Torch Light |
White LED |
||
General Specifications |
|||
Operation Time (DT) |
30s |
||
Recovery Time |
240s |
||
Operating Temperature |
-15°C to +55°C |
||
Storage Temperature |
-15°C to +55°C |
||
Humidity |
Max. 95% RH |
||
Operating Altitude |
Up to 2000m |
||
Safety Rating (Overall Voltage Category) |
CAT IV / 600V, CAT III / 690V |
CAT IV / 600V, CAT III / 1000V |
|
Pollution Degree |
2 |
||
Protection Degree |
IP64 |
||
Safety Regulations |
IEC 61243-3:2009, EN 61243-3:2010, DIN VDE 0682-401:2011 |
||
Approvals, Compliance |
GS mark from TÜV Rheinland, CE |
||
Power Supply |
Battery 2 x 1.5V (AAA/ IEC LR03) |
||
Power Consumption |
Approximately 60mA |
||
Battery Lifetime |
More than 10000 measurements (<5 s/ per measurement) |
||
Dimensions (HxWxD) |
Approximately 280 x 78 x 35 mm (11.0 x 3.1 x 1.4 in) |
||
Weight |
Approximately 320 g (0.71 lb) |