The Di-LOG ALVA MFT represents a new era in multifunction electrical testing, combining professional-grade precision with automation and future-ready EV testing capabilities. It has intelligent 2/3 wire high-current loop detection automatically identifying the correct Loop/PSCC measurement, Continuity & Earth Loop Auto Start, and 6mA RDC-PD/MD testing.
The ALVA MFT also supports a range of RCD types, including AC, A, B, B+, EV, and F, and performs variable RDC tests with custom mA settings. The Dynamic Non-Trip Loop technology delivers low-current Earth Loop readings.
Additional features include selectable insulation test voltages (50V–1000V), line-to-line impedance with dynamic phase rotation indication, and in-built fuse tables to maintain compliance with maximum permitted Zs Loop values.
The full-colour TFT display and intuitive interactive controls allow users to set pass/fail criteria, while on-screen guides assist in test lead configuration and overall operation. The ALVA MFT is fully compliant with BS EN 61557.
Discover the full Di-Log ALVA range: the ALVA MFT Pro Multifunction Installation Tester, the ALVA MFT EV Multifunction Installation Tester Kit , and the ALVA MFT Pro EV Multifunction Installation Tester Kit .
Purchase a Di-LOG ALVA Series MFT from us and receive the following free gift upon registration with Di-Log:
Once received, register your product online and Di-LOG will send your FREE CombiVolt item directly to you. Ends 30 April 2026.
Automatically adds to your basket when the total exceeds £500+ (ex VAT). Limited Stock. More details here.
| Measurement Range | Resolution | Basic Accuracy |
|---|---|---|
| Voltage & Frequency | ||
| AC Voltage TRMS 0V - 550V |
1V | ±2% ± 2 dgts |
| DC Voltage 0V - 550V |
1V | ±2% ± 2 dgts |
| Frequency 10 - 499Hz |
0.1Hz | ±0.2% ± 1 dgts |
| Phase Rotation | ||
| 0V - 550V Measurement range BS EN 61557-7 |
Right:1-2-3 ; Left: 3-2-1 | |
| Continuity | ||
| Low R (200mA) | 0.01Ω - 19.99Ω 20.1Ω - 99.9Ω 100Ω - 1999Ω |
±3% ± 3 dgts ±5% ± 5 dgts ±5% ± 5 dgts |
| Insulation | ||
| 50V, 100V & 250V (50kΩ-80MΩ @ 50V | 100kΩ-199.9MΩ @ 100V & 250V) |
<0.01MΩ - 19.999MΩ 19.99MΩ - 99.99MΩ 20.0MΩ - >199.9MΩ |
±5% ± 3 dgts ±5% ± 3 dgts ±5% ± 5 dgts |
| 500V & 1000V (500kΩ-199.9MΩ @ 500 & 1000V) |
<0.01MΩ - 19.999MΩ 19.99MΩ - 99.99MΩ 20.0MΩ - >199.9MΩ 200MΩ - >999MΩ |
±5% ± 3 dgts ±5% ± 3 dgts ±5% ± 5 dgts ±10% |
| Line Impedance (L-L | L-N) | ||
| 0.20Ω - 9999Ω Measurement range BS EN 61557-3 is 0.25Ω - 1999Ω |
0.01Ω - 19.99Ω 20.0Ω - 99.9Ω 100Ω - 9999Ω |
±5% ± 5 dgts |
| Perspective Short Circuit Current (PSC) | ||
| 0.00A - 19.99A 20.0A - 99.9A 100A - 999A 1.00kA - 9.99kA 10.0kA - 100.0kA |
0.01A 0.1A 1A 0.01kA 0.1kA |
Calculated value taking into account the Earth Loop Accuracy of ±5% ± 5 dgts |
| Earth Fault Loop Impedance (Z-loop L-PE High Current) | ||
| 0.20Ω - 9999Ω Measurement range BS EN 61557-3 is 0.25Ω - 1999Ω |
0.01Ω - 19.99Ω 20.0Ω - 99.9Ω 100Ω - 9999Ω |
±5% ± 5 dgts |
| Perspective Earth Fault Current (PFC - High Current) | ||
| 0.00A - 19.99A 20.0A - 99.9A 100A - 999A 1.00kA - 9.99kA 10.0kA - 100.0kA |
0.01A 0.1A 1A 0.01kA 0.1kA |
Calculated value taking into account the Earth Loop Accuracy of ±5% ± 5 dgts |
| Earth Fault Loop Impedance (Z-Loop (Zs) Non-Trip) | ||
| 0.40Ω - 19.99Ω 20.0Ω - 9999Ω Measurement range BS EN 61557 is 0.75Ω - 1999Ω |
0.01Ω - 19.99Ω 20.0Ω - 99.9Ω 100Ω - 9999Ω |
±5% ± 10 dgts ±10% |
| Perspective Earth Fault Current (PFC-Non-Trip) | ||
| 0.00A - 19.99A 20.0A - 99.9A 100A - 999A 1.00kA - 9.99kA 10.0kA - 100.0kA |
0.01A 0.1A 1A 0.01kA 0.1kA |
Calculated value taking into account the Earth Loop Accuracy of ±5% ± 5 dgts |
| RCD Tripping Time | ||
| 0.0 - 500.0ms (Measurement range BS EN 61557-6) |
0.1ms | ±3ms |
| Test Current - ½ x I∆n | 1 x I∆n | 2x I∆n | 5 x I∆n | ||
| RCD Types- AC | A | B | B+ | EV | F | S (Selective - Time Delayed) | ||
| RCD Tripping Current | ||
| 0.0 - 500.0ms (Measurement range BS EN 61557-6) |
0.1ms | ±3ms |
| 0.2 x IΔn - 1.1 IΔn (AC type) 0.2 x IΔn - 1.5 IΔn (A type, IΔn ≧30mA ) 0.2 x IΔn - 2.2 IΔn (A type, IΔn ≧10mA ) 0.2 x IΔn - 2.2 IΔn (B type) |
0.05 x IΔn | ±0.1 x IΔn |
| Nominal RCD Currents- 6mA | 10mA | 30mA | 100mA | 300mA | 500mA | ||
| Contact Voltage | ||
| 3.0V - 9.9V 10.0V - 99.9V |
0.1V | -0/+10% ±10 dgts |
| General Information | ||
| EN61010 Overvoltage Safety Rating | CAT III 600V | CAT IV 300V |
| Display | 480 x 320 TFT | LCD Screen |
| Power supply | 6 x AA Alkaline batteries (included) | |
| Recharge Option | ALVA Recharge Pack A available | |
| Dimensions | 250 x 107 x 135 mm | |
| Weight | 1300g (Excluding batteries) | |