The Di-LOG ALVA MFT Pro EV integrates automated diagnostics, intelligent loop and RCD testing, and EV charger verification into a single, professional-grade device. The ALVA MFT Pro EV ensures that every measurement complies with stringent industry standards, including full BS EN 61557.
The full-colour TFT display with interactive pass/fail indicators provides feedback on each test. The automated Continuity & Earth Loop Auto Start, combined with intelligent two- or three-wire high-current loop detection, reduces manual errors. The instrument offers comprehensive RCD support for AC, A, B, B+, EV, and F types.
It includes 4mA continuity testing for inductive loads, Zmax and Imax tracking for loop impedance, and perspective short-circuit current analysis. It also has RCD-LOC+ dynamic non-trip loop testing. The EV Auto Test Sequence simplifies EV charger verification by automating earth loop, RDC-PD/MD, AC RCD, ramp, and voltage tests.
The included Di-LOG DLEV1 EVSE Charge Point Adaptor Kit enables full Mode 3 charge point verification. Control pilot status checks, CP Error E detection, PE error monitoring, and pre-test functionality are all included. For site installations, the ALVA MFT Pro EV also supports three- or four-pole earth resistance testing with optional accessories and can store up to 1,000 recorded measurements, facilitating documentation and traceability. Please visit our Di-Log DLEV1 EVSE Charge Station Adapter Kit for further information.
Discover the full Di-Log ALVA range: the ALVA MFT Multifunction Installation Tester , the ALVA MFT Pro Multifunction Installation Tester, and the ALVA MFT EV Multifunction Installation Tester Kit .
Get a free gift this Black! Even better, this bonus stacks with any other offer.
Free item will automatically add to your basket. Limited Stock. Offer is based on ex VAT basket total after discounts and before shipping costs. See Black Friday Offers for details.
Remember: We will not be beaten on price. Contact us if you've seen a cheaper price.
| Measurement Range | Resolution | Basic Accuracy | |
|---|---|---|---|
| Voltage & Frequency | |||
| AC Voltage TRMS 0V - 550V |
1V | ±2% ± 2 dgts | |
| DC Voltage 0V - 550V |
1V | ±2% ± 2 dgts | |
| Frequency 10 - 499Hz |
0.1Hz | ±0.2% ± 1 dgts | |
| Phase Rotation | |||
| 0V - 550V Measurement range BS EN 61557-7 |
Right:1-2-3 ; Left: 3-2-1 | ||
| Continuity | |||
| Low R (200mA) | 0.01Ω - 19.99Ω 20.1Ω - 99.9Ω 100Ω - 1999Ω |
±3% ± 3 dgts ±5% ± 5 dgts ±5% ± 5 dgts |
|
| Continuity (4mA) | 0.1Ω - 99.99Ω 100Ω - 1999Ω |
±5% ± 3 dgts ±5% ± 5 dgts |
|
| Insulation | |||
| 50V, 100V & 250V (50kΩ-80MΩ @ 50V | 100kΩ-199.9MΩ @ 100V & 250V) |
<0.01MΩ - 19.999MΩ 19.99MΩ - 99.99MΩ 20.0MΩ - >199.9MΩ |
±5% ± 3 dgts ±5% ± 3 dgts ±5% ± 5 dgts |
|
| 500V & 1000V (500kΩ-199.9MΩ @ 500 & 1000V) |
<0.01MΩ - 19.999MΩ 19.99MΩ - 99.99MΩ 20.0MΩ - >199.9MΩ 200MΩ - >999MΩ |
±5% ± 3 dgts ±5% ± 3 dgts ±5% ± 5 dgts ±10% |
|
| Line Impedance (L-L | L-N) | |||
| 0.20Ω - 9999Ω Measurement range BS EN 61557-3 is 0.25Ω - 1999Ω |
0.01Ω - 19.99Ω 20.0Ω - 99.9Ω 100Ω - 9999Ω |
±5% ± 5 dgts | |
| Perspective Short Circuit Current (PSC) | |||
| 0.00A - 19.99A 20.0A - 99.9A 100A - 999A 1.00kA - 9.99kA 10.0kA - 100.0kA |
0.01A 0.1A 1A 0.01kA 0.1kA |
Calculated value taking into account the Earth Loop Accuracy of ±5% ± 5 dgts | |
| Earth Fault Loop Impedance (Z-loop L-PE High Current) | |||
| 0.20Ω - 9999Ω Measurement range BS EN 61557-3 is 0.25Ω - 1999Ω |
0.01Ω - 19.99Ω 20.0Ω - 99.9Ω 100Ω - 9999Ω |
±5% ± 5 dgts | |
| Perspective Earth Fault Current (PFC - High Current) | |||
| 0.00A - 19.99A 20.0A - 99.9A 100A - 999A 1.00kA - 9.99kA 10.0kA - 100.0kA |
0.01A 0.1A 1A 0.01kA 0.1kA |
Calculated value taking into account the Earth Loop Accuracy of ±5% ± 5 dgts | |
| Earth Fault Loop Impedance (Z-Loop (Zs) Non-Trip) | |||
| 0.40Ω - 19.99Ω 20.0Ω - 9999Ω Measurement range BS EN 61557 is 0.75Ω - 1999Ω |
0.01Ω - 19.99Ω 20.0Ω - 99.9Ω 100Ω - 9999Ω |
±5% ± 10 dgts ±10% |
|
| Perspective Earth Fault Current (PFC-Non-Trip) | |||
| 0.00A - 19.99A 20.0A - 99.9A 100A - 999A 1.00kA - 9.99kA 10.0kA - 100.0kA |
0.01A 0.1A 1A 0.01kA 0.1kA |
Calculated value taking into account the Earth Loop Accuracy of ±5% ± 5 dgts | |
| RCD Tripping Time | |||
| 0.0 - 500.0ms (Measurement range BS EN 61557-6) |
0.1ms | ±3ms | |
| Test Current - ½ x I∆n | 1 x I∆n | 2x I∆n | 5 x I∆n | |||
| RCD Types- AC | A | B | B+ | EV | F | S (Selective - Time Delayed) | |||
| RCD Tripping Current | |||
| 0.0 - 500.0ms (Measurement range BS EN 61557-6) |
0.1ms | ±3ms | |
| 0.2 x IΔn - 1.1 IΔn (AC type) 0.2 x IΔn - 1.5 IΔn (A type, IΔn ≧30mA ) 0.2 x IΔn - 2.2 IΔn (A type, IΔn ≧10mA ) 0.2 x IΔn - 2.2 IΔn (B type) |
0.05 x IΔn | ±0.1 x IΔn | |
| Nominal RCD Currents- 6mA | 10mA | 30mA | 100mA | 300mA | 500mA | 650mA | 1A | |||
| Contact Voltage | |||
| 3.0V - 9.9V 10.0V - 99.9V |
0.1V | -0/+10% ±10 dgts | |
| Earth Resistance RE (3-Wire & 4-Wire Method) | |||
| 1.0Ω - 9999Ω Measurement range BS EN 61557-5 is 100Ω - 1999Ω |
1.00Ω - 19.99Ω 20.0Ω - 99.9Ω 100Ω - 9999Ω |
±5% ± 5 dgts | |
| Earth Resistance Ro (4-Wire Wenner Method) | |||
| 6.0 Ωm … 99.9 Ωm 100 Ωm ... 999 Ωm 1.00 kΩm ... 9.99 kΩm 10.0 kΩm ... 99.9 kΩm 100 kΩm ... 9999 kΩm Measurement range BS EN 61557-5 is 100Ω - 1999Ω |
0.1 Ωm 1 Ωm 0.01 kΩm 0.1 kΩm 1 kΩm 20.0Ω - 99.9Ω 100Ω - 9999Ω |
±5 % of + 5 dgts ±5 % of + 5 dgts ±10% ( Re 2kΩ…19.99kΩ) ±10% Re (2kΩ…19.99kΩ) ±20% Re (> 20 kΩ) |
|
| General Information | |||
| EN61010 Overvoltage Safety Rating | CAT III 600V | CAT IV 300V | |
| Display | 480 x 320 TFT | LCD Screen | |
| Power supply | 6 x AA 2100mAh NiMH batteries (included) | ||
| Recharge Time | Typical 6 hours | ||
| Dimensions | 250 x 107 x 135 mm | ||
| Weight | 1300g (Excluding batteries) | ||