Kewtech SMARTPAT PAT Tester
The Kewtech SMARTPAT PAT Tester is a Pass/Fail portable appliance tester which can be converted to a full downloading PAT tester when used with Kewtech’s KEWPAT app (more information below). The Kewtech PAT Tester will indicate whether a portable appliance has passed or failed a particular test by changing the large, LCD, backlit display’s colour to either green (pass) or red (fail).
Measuring Capabilities
It is capable of performing the following checks:
- Earth bond at 200mA (IT safe)
- Quick check continuity
- 5-second continuity
- 250V insulation test (ideal for testing surge protected extension leads)
- 500V insulation test
- Substitute leakage test
- Extension lead test
- Portable RCD tests
This PAT tester allows the user to select whether he or she wishes to run leakage tests at either 110V or 230V and is able to test 10mA and 30mA portable RCDs without tripping these instruments. The inclusion of an extension lead adapter and earth continuity test lead with probe and crocodile clip further extends this product’s scope-for-use.
The Kewtech SMARTPAT PAT Tester can also be adjusted to suit the user’s needs as he/she may use the KEWPAT app to create personalised test sequences. This instrument also includes automatic test sequences for Class I and Class II appliances which can be easily accessed using dedicated function buttons.
In addition to its extensive testing capabilities and adjustability, the Kewtech SMARTPAT PAT Tester has also been designed to ensure checks are as accurate as possible and to this end includes a test lead nulling feature.
It is also capable of running an appliance status pre-check which determines whether the appliance under investigation is powered on or off. This protects both the user and PAT tester from unnecessary harm.
Finally, this easy-to-use, battery operated PAT tester can be used for approximately 1400 tests before it becomes necessary to replace the batteries. It is an adaptable, portable PAT tester with extensive testing capabilities.
Key Features
- Pass/ Fail portable appliance tester that can be converted to a downloadable PAT tester using Kewtech’s KEWPAT app
- Indicates pass or fail by changing the colour of the display
- Green=pass
- Red=fail
- Large, backlit, LCD display
- Earth bond at 200mA (IT safe)
- Quick check continuity
- 5-second continuity
- 250V insulation test (ideal for testing surge protected extension leads)
- 500V insulation test
- Substitute leakage test
- Extension lead test
- Portable RCD tests
- Can run leakage tests at either 110V or 230V
- Can test 10mA and 30mA RCDs without tripping them
- Automatic test sequence for Class I and Class II appliances
- Automatic test sequences accessible via clearly labelled function buttons
- Can create personalised test sequences using the KEWPAT app
- Test lead nulling
- Appliance status pre-check
- Battery operated
- Can be used for approximately 1400 tests before batteries will need replacing
What’s Included?
- Kewtech SMARTPAT PAT Tester - Battery Operated
- Mains Lead
- Earth Lead with Probe and Crocodile Clip
- Extension lead Adapter
- Carry Bag with Strap
- Quickstart Manual
- End of Line Cal Cert
Kewtech PAT Tester Comparison
EZYPAT | EZYPAT Plus | SMARTPAT | |
---|---|---|---|
200mA continuity Test | Yes | ||
250V Insulation Test | Yes | ||
500V Insulation Test | Yes | ||
Substitute Leakage Measurement | Yes | ||
Polarity Check | Yes | ||
110V Load and Run Test | - | Yes | |
230V Load and Run Test | - | Yes | |
Portable RCD Test | - | - | Yes |
Compatible with KEWPAT App | - | Yes | |
Customisable Test Sequences | - | - | Yes |
KEWPAT App
PLEASE NOTE: this app is not included with the Kewtech SMARTPAT PAT Tester. It is available for FREE from the App Store (iOS) or Google Play (Android).
For a quick introduction to this app, please see the video below.
The KEWPAT App can be downloaded for FREE from the App Store (iOS) and Google Play (Android); it allows the user to control his/her Kewtech SMARTPAT PAT Tester via an iOS or Android smartphone.
Compatible Android and iOS smartphones can be used to program and initiate tests. The user is able to create customised test sequences and specify the pass limits, duration and the number of repeats required. Using the risk assessment feature, the operator can adjust any tests or test sequences in accordance with the Code of Practice.
Moreover, he/she need only enter the product type and establishment type into the risk assessment tool in order to view the recommended testing frequency. The recommended testing frequency can be adjusted to incorporate any extenuating factors, such as dampness.
Results derived from these tests are transmitted from the Kewtech SMARTPAT back to the user's smartphone. Please note that whilst optimised for use with the Kewtech SMARTPAT, this app can be used in Manual mode with Kewtech's EZYPAT and EZYPAT PLUS to collect data and create reports manually. Once data has been collected the user can enter additional information before either saving the record to a database or sending it to print. Labels printed using this app can be customised to include a company logo.
The KEWPAT App has been optimised to make data entry and collection as easy as possible. To this end, it includes auto-number increment, as well as drop-down menus for customer, site, location and product description information. Alternatively, this app can be used to scan barcodes and QR data codes to populate these fields automatically.
In addition to recording written data, this app facilitates the user's ability to save images of appliances-under-test, which serve as evidence of visual inspections, to the product register.
Comprehensive data collection and ease-of-use are at the forefront of this app's design. As such, it includes voice prompt helps and can be used to manage databases and customer information. Further to this, the transferring of information is also simple as the KEWPAT App can be connected to the user's PC via Wi-Fi.
The KEWPAT App is a sophisticated tool, ideal for extending the capabilities of the Kewtech SMARTPAT PAT Tester and conducting PAT testing operations remotely.
Key Features
- FREE app for iOS and Android smartphones
- Control the Kewtech SMARTPAT PAT Tester remotely
- Program and initiate tests remotely
- Create customised test sequences
- Specify pass limits, duration and the number of repeats
- Integrated risk assessment feature allows the user to ascertain the recommended testing frequency of an appliance in accordance with the Code of Practice
- Testing frequency can be adjusted to include extenuating circumstances, such as dampness
- Results are sent to the user's smartphone from the SMARTPAT
- Can be used with the EZYPAT and EZYPAT PLUS in Manual mode, allowing the user to enter data and create reports
- Add additional information to collected results
- Save records to a database or send them to print
- Labels can be printed with a company logo
- Auto-number increment
- Drop-down menus for customer, site, location and product description
- Scan barcodes and QR data codes
- New description or repeat
- Appliance description
- Images of appliances-under-test can be saved to the product register
- Voice prompt helps
- Manage databases
- Manage customer information
- Connect to a PC via Wi-Fi
Kewtech EZYPAT/ SMARTPAT Comparision Table
The Kewtech SMARTPAT PAT Tester has two sister products: the Kewtech EZYPAT and EZYPAT PLUS PAT Testers; please see the table below for a brief comparison of the three models.
Specification | EZYPAT | EZYPAT PLUS | SMARTPAT |
200mA Continuity Test | X | X | X |
250V Insulation Test | X | X | X |
500V Insulation Test | X | X | X |
Substitute Leakage Test | X | X | X |
Polarity Check | X | X | X |
110V Load and Run Test | X | X | |
230V Load and Run Test | X | X | |
Portable RCD Test | X | ||
Compatible with KEWPAT App | X | ||
Customisable Test Sequences | X |
Kewtech SMARTPAT PAT Tester - Battery Operated Techncial Specifications
Protective Conductor Resistance Test | ||
Measuring range | 0.00 - 20.00 Ω (NULL value inc)* | |
Over-range indication | > 20.00 Ω | |
Resolution | 0.01Ω | |
Open-circuit voltage | 5 V ±0.4 V DC | |
Measuring current | 200 mA DC (nominal value) | |
Accuracy | ±3%rdg ±5dgt | |
* Resistances exceeding 3 Ω cannot be cancelled by NULL function | ||
Mains Voltage | ||
Display range | 30 - 270 V | |
Hi/ Lo indication | < 30 V: No voltage indication > 270 V: 270 V | |
Resolution & Accuracy | 1 V ±3%rdg ±5dgt | |
Insulation | ||
Rated Voltage | 250V | 500V |
Measuring range | 0.00 - 20.00 MΩ | |
Over-range indicatio | > 20.00 MΩ | |
Resolution | 0.01 MΩ | |
No-load voltage | 250 V DC +20%, -0% | 500 V DC +20%, -0% |
Short-circuit current | 1.5 mA DC or less | |
Rated current | 1 -1.2 mA with a load of 0.25 MΩ | 1 to 1.2 mA with a load of 0.5 MΩ |
Accuracy | ±2%rdg±3dgt | |
Substitute Leakage | ||
Measuring range | 0.10 - 12.00 mA rms | |
Over-range indication | > 12.00 mA | |
Resolution | 0.01mA | |
Open-circuit voltage/ Freq | 30 V ±5 V rms / 50 Hz ±5% | |
Measuring current | 1.2 mA AC ±0.5 mA (when measuring 12.00 mA) | |
Accuracy | ±3%rdg±5dgt | |
Insuyltation Test Between L-N | ||
Open-circuit voltage | 4.5 V ±0.5 V DC | |
Criteria of judgement | 100 kΩ ±20 kΩ or less: LCD shows “<0.10 MΩ” and the measurement is halted | |
Run Leakage | ||
Item | Load Current | Leakage Current |
Mains voltage range | 100 - 253 V / 50 Hz | |
Measuring range | 0.10 - 13.00 A rms | 0.10 - 20.00 mA rms |
Display range | 0.00 - 13.00 A | 0.00 - 20.00 mA |
Over-range indication | > 13.00 A | > 20.00 mA |
Resolution | 0.01A | 0.01mA |
Accuracy | ±10%rdg ±5dgt | ±3%rdg ±5dvgt |
Max. rating | 3 kVA max. / 15 sec. cont. | |
RCD Test | ||
Rated voltage | 230 V - 15% to +10% / 50Hz | |
Rated current | 10 mA / 30 mA | |
Test duration | ×1: 0.0 ms - 500.0 ms | ×5: 0.0 ms - 40.0 ms |
Test current accuracy | 2% - 8% | |
Operating time accuracy | ±2 ms ( 40 ms) ±8 ms (>40 ms) |
Reviews
SKU | SMARTPAT |
---|---|
Manufacturer Part Code | SMARTPAT |
Model Ref | SMARTPAT |