The Martindale Essentials Kit is built around the HPAT425 Portable Appliance Tester. The tester itself handles Class I, Class II, and IEC leads with automatic test sequences and clear PASS/FAIL results. It also offers an IT-safe 200 mA earth bond test and selectable 250 V or 500 V insulation testing.
The bundle includes dedicated test leads and adaptors, a carry case setup, and a full range of labelling and logging materials. It also includes supporting tools such as a socket tester, a microwave leakage detector, insulated screwdrivers, and an eLearning PAT testing course with certification.
For further information on each item, please click on the relevant image in the comparison chart.
| Essentials Kit | Professional Kit | |
|---|---|---|
![]() Martindale HPAT425 Portable Appliance Tester |
✔ | ✔ |
![]() CK Tools AVIT 5 x Insulated Screwdriver Set |
✔ | ✔ |
![]() PASS Oxford Black Large Test Equipment Carry Case |
✔ | ✔ |
![]() PASS PAT Testing Logbook |
✔ | ✔ |
![]() PASS Microwave Leakage Detector Tester |
✔ | ✔ |
![]() PASS IEC (C13 Female) to Cloverleaf (C6 Male) PAT Adaptor |
✔ | ✔ |
![]() PASS PAT Adaptor - IEC Plug (C14) to Fig 8 (C7) |
✔ | ✔ |
![]() PASS PAT Adaptor - IEC Plug (C14) to Clover Leaf (C5) |
✔ | ✔ |
![]() PASS eLearning PAT Testing Course |
✔ | ✔ |
![]() UNI-T UT07A Socket Tester |
✔ | ✔ |
![]() PASS 500 x PAT Testing Labels - Passed |
✔ | ✔ |
![]() PASS 250 x PAT Testing Cable Wrap Labels |
✔ | ✔ |
![]() PASS 500 x Passed Circular PAT Testing Labels |
✔ | ✔ |
![]() PASS 250 x PAT Testing Labels - Failed |
✔ | ✔ |
![]() Simply Pats Manual Entry PAT Testing Software |
✘ | ✔ |
Automatically adds to your basket when the total exceeds £500+ (ex VAT). Limited Stock. More details here.
| HPAT425 | |
|---|---|
| Earth Continuity | |
| Test Voltage | >4V DC (into open circuit) |
| Test Current | >200mA DC (into short circuit) |
| Range | 0.01 - 20Ω |
| Accuracy | ± (5% of reading + 2 digits) |
| Fixed / Default Pass Limits | ≤0.1Ω 0.11Ω to ≤0.30Ω long lead 0.31Ω to ≤0.50Ω extra long lead |
| Insulation | |
| Test Voltage | User selectable >250V DC at 1mA / >500V DC at 1mA (<312.5V DC open circuit / <625V DC open circuit) |
| Test Current | <2mA (into short circuit) |
| Range | 0.01MΩ - 100MΩ |
| Accuracy | 5% reading + 2 digits |
| Pass Level | Lead: ≥ 1.0MΩ Class I: ≥1.0MΩ Class II: ≥2.0MΩ |
| Power | |
| Batteries | 3.7V 5000mAh lithium polymer battery (non-user replaceable) |
| Battery Life | Fully charged, minimum 1700 complete tests, approx. |
| Auto Power Down | Auto dimming after 3 minutes, Auto power down after 5 minutes of inactivity |
| Environmental | |
| Location | Suitable for indoor and outdoor use in dry weather conditions only |
| Altitude | Up to 2000m |
| Operating Temperature | 0°C to 40°C |
| Humidity | ≤80% RH up to 31°C, decreasing linearly to 50°C RH at 40°C |
| Ingress Protection Class | IP20 |
| Pollution Degree | 2 |
| General | |
| Overload Protection | 300V AC/DC |
| Protection Class | IP20 |